2003-06-20 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) HURRICANE MISSILE IMPACT PROTECTION |
| SHUTTERS.THE SUBMITTED ARCH ALUMINUM |
| DOOR PRODUCT APPROVAL NOA# 01-0910.09 |
| REQUIRES THE INSTALLATION OF HURRICANE |
| PROTECTION FOR THIS DOOR.SUBMIT A |
| PRODUCT APPROVAL FOR SHUTTERS AND |
| ANNOTATE ON THE PLANS. |
| |
| 2) THE SUBMITTED COPIES OF ARCH ALUMINUM |
| DOOR PRODUCT APPROVAL NOA# 01.0910.09 |
| ARE OF POOR QUALITY.THE INFORMATION, |
| INCLUDING THE FASTENER SCHEDULE (SHEET 4 |
| OF 4) IS NOT LEGIBLE.SUBMIT LEGIBLE |
| COPIES.MIAMI-DADE PRODUCT APPROVALS |
| CAN BE PRINTED FROM THEIR WEBSITE,WWW. |
| MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM |
| |
| 3) FBC 1606.1.7WIND LOAD.THE PLANS |
| SHALL STATE THE BASIC WIND SPEED, WIND |
| IMPORTANCE FACTOR, WIND EXPOSURE |
| CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| AND EXTERIOR COMPONENT AND CLADDING |
| DESIGN WIND PRESSURES SO THAT THEY CAN |
| BE COMPARED TO THE PRODUCT APPROVAL. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |
| E-MAIL: [email protected] |