Plan Review Details - Permit 03051220
Plan Review Stops For Permit 03051220
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-01-10 Cont ID  
Sent By shill Date 2004-01-10 Time 18:00 Rev Time 0.50
Received By shill Date 2004-01-10 Time 18:00 Sent To  
Notes
2004-01-10 00:00:00REVISION DATED 12/9/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-12-16 Cont ID  
Sent By dpalmer Date 2004-01-07 Time 14:33 Rev Time 0.50
Received By shill Date 2003-12-16 Time 16:19 Sent To  
Notes
2003-12-16 00:00:00****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)HAVE THE PLANS STAMPED BY HISTORIC
 PRESERVATION DEPARTMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-16 Cont ID  
Sent By dpalmer Date 2003-12-12 Time 07:02 Rev Time 1.50
Received By sthyng Date 2003-07-16 Time 14:25 Sent To P
Notes
2003-07-16 00:00:00TO KS DESK
  
 PROVISO - SUBMIT PRODUCT APPROVALS
 FOR MULLIONS, CYPRESS DOORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-06 Cont ID  
Sent By dpalmer Date 2003-07-16 Time 11:06 Rev Time 0.00
Received By sthyng Date 2003-06-04 Time 18:35 Sent To  
Notes
2003-06-06 00:00:00*******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 3.)ADDITIONAL FEES DUE, $3.22.
  
 4.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 5.)STUCCO REQUIRED TO BE 7/8, FBC
 2504.2.2, ASTM C1063.
  
 6.)FIRESTOP REQUIRED FBC705.3.
  
 7.)SUBMIT PRODUCT APPROVALS FOR
 THE CYPRESS DOORS, ROOF COVERING,
 DOUBLE DOORS, IMPACT WINDOWS (ALL TYPES)
 AND WINDOW MULLIONS.
  
 8.)SHOW SIZES AND TYPES OF WINDOWS
 BEING REPLACED.INDICATE BEDROOM
 WINDOWS AND SHOW COMPLIANCE WITH
 EMERGENCY EGRESS REQUIREMENTS FBC1005.4.
 THE WINDOWS MARKED "SH EGRESS WIN"
 SCALED IS 33" X 51".THIS SIZE DOES NOT
 MEET EGRESS REQUIREMENTS UNLESS IT IS
 A SPECIAL EGRESS WINDOW.BE SURE TO
 SUBMIT THE CORRECT PRODUCT APPROVAL IF
 THIS IS THE PRODUCT TO BE USED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-01-07 Cont ID  
Sent By dpalmer Date 2004-01-07 Time 14:33 Rev Time 0.33
Received By dpalmer Date 2004-01-07 Time 14:33 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-12-12 Cont ID  
Sent By csiegber Date 2004-01-05 Time 15:24 Rev Time 0.33
Received By dpalmer Date 2003-12-12 Time 07:02 Sent To B
Notes
2003-12-12 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULE W/ LOAD SHOWN. PLEASE
 SEE NOTE #1 FROM ORIG REVIEW ONLINE.
 MOST IS THE SAME.
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. PER 210.8A6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IFTHERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-16 Cont ID  
Sent By csiegber Date 2003-12-09 Time 10:50 Rev Time 0.33
Received By dpalmer Date 2003-07-16 Time 11:06 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-07-14 Time 08:28 Rev Time 0.50
Received By dpalmer Date 2003-05-19 Time 17:53 Sent To M
Notes
2003-05-19 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS/OCP/WIRE SIZE.
 PANELS SHOWS 125 MAIN W/ 158A LOAD.
 RISER SHOWS 200A, BUT ONLY HAS 1/0`S?
 PLEASE SIZE PER 310-15B6/310-16
  
 2)NOTE: PLEASE PROVIDE NOTE TO ATTACH TO
 FOOTER STEEL. 250-50
  
 3)NOTE: PLEASE CLARIFY WHERE NEW SERVICE
 IS GOING/SHOW ON PLAN.
  
 4)NOTE: PLEASE CLARIFY WHAT/IF ANY NEW
 ELECTRCIAL. PERMIT APPLICATION MENTIONS
 PARTIAL REMOD?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected].

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-05 Cont ID  
Sent By csiegber Date 2004-01-05 Time 15:24 Rev Time 0.00
Received By csiegber Date 2004-01-05 Time 15:24 Sent To E
Notes
2004-01-05 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-09 Cont ID  
Sent By csiegber Date 2003-12-09 Time 10:50 Rev Time 0.00
Received By csiegber Date 2003-12-09 Time 10:50 Sent To E
Notes
2003-12-09 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-14 Cont ID  
Sent By shernand Date 2003-07-14 Time 08:28 Rev Time 0.00
Received By shernand Date 2003-07-14 Time 08:28 Sent To E
Notes
2003-07-14 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-17 Cont ID  
Sent By dpalmer Date 2003-05-17 Time 03:59 Rev Time 0.00
Received By dpalmer Date 2003-05-17 Time 03:59 Sent To E
Notes
2003-05-17 00:00:00ELEC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-14 Cont ID  
Sent By sgraham Date 2003-05-15 Time 11:55 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 15:06 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-20 Cont ID  
Sent By dpalmer Date 2003-05-19 Time 17:54 Rev Time 0.30
Received By pkrauss Date 2003-05-20 Time 12:57 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-18 Cont ID  
Sent By kstevens Date 2003-07-18 Time 10:55 Rev Time 0.25
Received By kstevens Date 2003-07-18 Time 10:55 Sent To  
Notes
2003-07-18 00:00:00CHECKED ROOF DRAINAGE - 0K

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-05-22 Cont ID  
Sent By sthyng Date 2003-07-16 Time 14:25 Rev Time 0.25
Received By kstevens Date 2003-05-22 Time 09:14 Sent To B
Notes
2003-05-22 00:00:00NO PLUMBING PLANS SUBMITTED.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-14 Time 15:06 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***