Plan Review Details - Permit 03050855
Plan Review Stops For Permit 03050855
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-11 Cont ID  
Sent By rmcdouga Date 2003-08-11 Time 12:21 Rev Time 2.50
Received By rmcdouga Date 2003-08-11 Time 12:21 Sent To  
Notes
2003-08-11 00:00:00BUILDING PROVISO
  
 1) SUBMIT A REVISED TRUSS ANCHOR
 SCHEDULE WITH VALUES THAT DO NOT HAVE
 A ONE-THIRD INCEASE ON THE STEEL
 CALCULATIONS PER FBC 1609.4. SEE THE
 2003 USP CATALOG AND THE 2002 SIMPSON
 HIGH WIND-RESISTANT CONSTRUCTION
 CATALOG FOR THE PROPER VALUES.
  
 2) THE TRUSS DRAWINGS AND LAYOUT FOR
 SINGLE FAMILY DWELLINGS ARE NOT REQUIRED
 TO BE SUBMITTED FOR PLAN REVIEW. THEY
 ARE REQUIRED TO BE GIVEN TO THE FIELD
 INSPECTOR AT THE ROOF FRAMING INSPECTION
 NOTE: THE DRAWINGS DO NOT HAVE THE
 ORIGINAL WET SIGNATURE OF THE TRUSS
 ENGINEER ON THEM AND THE DRAWINGS HAVE
 DIFFERENT MEAN ROOF HEIGHTS LISTED ON
 THEM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-23 Cont ID  
Sent By alange Date 2003-07-31 Time 13:48 Rev Time 4.00
Received By rmcdouga Date 2003-06-23 Time 14:57 Sent To  
Notes
2003-06-23 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUBMIT A SOIL BORING TEST REPORT.
  
 4) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED ON ZERO LOT LINE. SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND
 LISTING INFORMATION FOR FIRE RATED GLASS
 BLOCK.
  
 5) THE DOOR IN THE WALL ADJACENT TO THE
 UNCONDITIONED GARAGE IS REQUIRED TO BE
 SOLID CORE OR INSULATED PER FBC CHAPTER
 13. PLEASE INDICATE ON PLANS.
  
 6) DETAIL 2 ON A3.3B INCORRECTLY
 SPECIFIES 5/8" STUCCO ON THE WALL. ASTM
 C 926 REQUIRES STUCCO APPLIED VERTICALLY
 ON LATH OVER SOLID BASE IS REQUIRED TO
 BE 7/8" THICK. PLEASE CORRECT.
  
 7) SPECIFY THE SHEATHING TYPE, FASTENER
 TYPE AND SPACING, VAPOR BARRIER, ETC.
 FOR THE EXTERIOR WALL THAT IS FORMED BY
 THE ROOF TRUSSES AS INDICATED BY THE
 DETAILS ON S4.
  
 8) SUBMIT ENGINEERED DRAWINGS, SPECS.,
 ETC. FOR THE BUTT GLASS WINDOW AS
 REQUIRED BY FBC 2406.2.
  
 9) FBC 1609.4 NO LONGER ALLOWS THE ONE-
 THIRD STRESS INCREASE ON STEEL ALLOWABLE
 STRESS DESIGN VALUES. PLEASE REVISE THE
 TRUSS ANCHOR SCHEDULE TO VALUES THAT DO
 NOT INCLUDE A STRESS INCREASE ON THE
 STEEL CALCULATIONS. SEE THE 2003 USP
 CATALOG AND THE 2002 SIMPSON HIGH-WIND
 CATALOG. THEUSP TA & TAR WITH (5) 10D
 X 1-1/2" NAILS HAS AN UPLIFT VALUE OF
 1230#, THE SIMPSON HETAL 12 WITH (15)
 10D X 1- 1/2" NAILS IS 1365#, ETC.
  
 10) PLEASE CLARIFY THAT THE G2 ANCHOR
 REQUIRES (2) STRAPS ON EACH TRUSS OF THE
 TWO MEMBER GIRDER.
  
 11) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - MULLIONS (UNCLIPPED) EXPIRED
 - 16'X 8' GARAGE DOOR (DESIGN LOAD IS
 NOT ADEQUATE FOR THE -39.7 THAT IS
 REQUIRED)
 - OUTSWING DOOR WITH TWO SIDELITES
 - OUTSWING FRENCH DOOR
 - ARCHED TOP FIXED GLASS WINDOWS
 (DESIGNER WINDOWS)
  
 12) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-05-11 Cont ID  
Sent By dpalmer Date 2004-05-11 Time 09:22 Rev Time 0.25
Received By dpalmer Date 2004-05-11 Time 09:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-05-05 Cont ID  
Sent By dpalmer Date 2004-05-05 Time 08:38 Rev Time 0.25
Received By dpalmer Date 2004-05-05 Time 08:38 Sent To  
Notes
2004-05-05 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULE CONDUCTORS.
 RISER DIAGRAM SHOWS 2/0'S AND PANELS
 SHOWS #1'S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-05-04 Time 09:21 Rev Time 0.33
Received By dpalmer Date 2004-04-27 Time 18:43 Sent To  
Notes
2004-04-27 00:00:00****** UNSAT *********
  
 1)NOTE: PLEASE CORRELATE PANEL SCHEDULES
 /RISER DIAGRAM.
 PANEL SHOWS EACH PANEL TO BE 200A SERV-
 -ICE. MAIN BRKRS HAVE NOW BEEN CHANGED
 TO 200A INSTEAD OF 150A AS SHOWN BEFORE.
 PLEASE SEE CONDUCTORS UNDER NOTE ON
 PANEL SCHEDULE. STILL SHOWS #1 FOR FEED-
 -ERS??310.16
 PLEASE SEE NOW SERVICE HAS BEEN CHANGED
 TO READ 400A. PLEASE SIZE GEC TO 250.66,
 PER 310.15B6
 PLEASE SEE METERMAIN STILL ONLY INDICATE
 -S 2-200A MCB'S? WHERE IS BRKR, (60A)?
 FOR SUB PANEL???
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-26 Time 09:28 Rev Time 0.50
Received By dpalmer Date 2004-04-20 Time 07:12 Sent To  
Notes
2004-04-20 00:00:00************ UNSAT ********************
  
 1)NOTE: PLEASE SEE A NEW PANEL "C" IS
 BEING SHOWN COMING FORMMETERMAIN.
 PLEASE INDICATE OCP. RISER MENTIONS TWO
 150A MB'S ONLY?
  
 2)NOTE: PLEASE ALSO SEE PANEL SCHEDULES
 MENTIONS SERVICE TO BE PROVIDED FOR
 EACH PANEL TO BE 200A'S YET 150A BRKRS
 FEED EACH.? SERVICE IS ALSO SHOWN AS
 400A.
  
 3)NOTE: PANEL "C" SHOWS 30A OCP FOR #12
 AWG FOR POOL PUMP.
  
 RECEPT ON PENINSULAR REDLINED TO BE GFI.
 210.8A6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-21 Cont ID  
Sent By csiegber Date 2004-04-14 Time 11:09 Rev Time 0.50
Received By btrobaug Date 2003-05-21 Time 08:25 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-04 Time 09:21 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 09:21 Sent To E
Notes
2004-05-04 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-26 Cont ID  
Sent By csiegber Date 2004-04-26 Time 09:28 Rev Time 0.00
Received By csiegber Date 2004-04-26 Time 09:28 Sent To E
Notes
2004-04-26 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 11:09 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 11:09 Sent To E
Notes
2004-04-14 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 13:48 Rev Time 0.00
Received By alange Date 2003-07-31 Time 13:48 Sent To B
Notes
2003-07-31 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 16:57 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 16:57 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-11 Cont ID  
Sent By pkrauss Date 2003-08-11 Time 14:21 Rev Time 0.30
Received By pkrauss Date 2003-08-11 Time 14:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-06-04 Cont ID  
Sent By kstevens Date 2003-05-24 Time 05:38 Rev Time 0.25
Received By pkrauss Date 2003-06-04 Time 07:36 Sent To B
Notes
2003-06-04 00:00:00MECHANICAL PERMIT 03050857
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.ENERGY & MANUAL J CALCULATIONS
 SUBMITTED & APPROVED.
  
 SHOULD GAS DRYER BE INSTALLED:
 1.DETERMINE IF LAUNDRY ROOM IS A
 CONFINED OR UNCONFINED SPACE AS PER
 2001 FBC(M) 702.
  
 2.CONFINED SPACE SHALL COMPLY WITH
 SECTION 703 OF THE 2001 FBC(M).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-24 Cont ID  
Sent By btrobaug Date 2003-06-24 Time 08:26 Rev Time 0.25
Received By kstevens Date 2003-05-24 Time 05:38 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-05-14 Time 16:57 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***