Plan Review Details - Permit 03050831
Plan Review Stops For Permit 03050831
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-21 Cont ID  
Sent By rmcdouga Date 2003-07-21 Time 16:03 Rev Time 3.00
Received By rmcdouga Date 2003-07-21 Time 16:03 Sent To  
Notes
2003-07-21 00:00:00BUILDING PROVISO
  
 1) SUBMIT (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR STRUCTURAL WINDOW MULLIONS
 OUTSWING STEEL DOORS AND OVERHEAD GARAGE
 DOOR PRIOR TO INSTALLATION.
  
 2) SUBMIT KEY PLANS AND INSTALLATION
 SCHEDULES FOR THE STORM PANELS PRIOR TO
 INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-19 Cont ID  
Sent By kstevens Date 2003-07-18 Time 12:30 Rev Time 4.00
Received By rmcdouga Date 2003-06-19 Time 09:35 Sent To  
Notes
2003-06-19 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) SPECIFY THE SIZE OF THE ATTIC VENTS
 ON THE WALL SECTION ON SHEET 2. SEE FBC
 2309.7.
  
 5) SPECIFY THE SIZES OF THE (2) ATTIC
 ACCESS OPENINGS ON THE FLOOR PLAN ON
 SHEET 2. SEE FBC 2309.6.
  
 6) THE 1-1/2" RECESS FOR THE BLOCK AT
 THE EXTERIOR WALL IS REQUIRED BY CITY
 AMENDMENTS TO FBC 2111.1.9. THE WALL
 SECTION ON SHEET 2 INDICATES THAT THE
 RECESS IS OPTIONAL. PLEASE CORRECT.
  
 7) SPECIFY ON THE PLANS THAT THE WALL
 BETWEEN THE GARAGE AND CONDITIONED SPACE
 IS INSULATED AS REQUIRED BY FBC CHAPTER
 13.
  
 8) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALCULATION FORM.
 FBC CHAPTER 13
  
 9) FBC 1609.4 NO LONGER ALLOWS THE ONE
 THIRD STRESS INCREASE FOR STEEL
 CALCULATIONS. PLEASE REVISE THE FASTENER
 SCHEDULE ON SHEET 2 TO UPLIFT VALUES
 THAT DO NOT INCLUDE THIS INCREASE. SEE
 THE 2003 USP OR 2002 SIMPSON HIGH WIND
 RESISTANT CONSTRUCTION CATALOGS FOR
 VALUES AND NAILING REQUIREMENTS.
  
 10) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL MULLIONS
 - OUTSWING STEEL DOORS (THE INFORMATION
 SUBMITTED IS NOT ACCEPTABLE)
 - OVERHEAD GARAGE DOOR (NEED THE SBCCI
 EVALUATION REPORT IN ADDITION TO THE
 DRAWINGS)
 - STORM PANELS (NEED THE NOA REPORT AND
 THE APPROVED DRAWINGS)
  
 11) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 NOTE: IN ORDER TO FACILITATE PLAN REVIEW
 TIME, PLEASE RETURN OLD PLANS WITH
 RESUBMITTALS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By btrobaug Date 2003-07-17 Time 15:08 Rev Time 0.50
Received By btrobaug Date 2003-07-17 Time 14:47 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-07-14 Time 08:53 Rev Time 0.50
Received By btrobaug Date 2003-05-21 Time 11:30 Sent To P
Notes
2003-05-21 00:00:00 
 UNSAT
 ~~~~~
 PLEASE NOTE THE FOLLOWING COMMENTS,MAKE
 NECESSARY CORRECTIONS TO THE PLANS AND
 RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT THE GROUNDING
 ELECTRODE CONDUCTOR MUST COMPLY WITH
 250-50 INCLUDING THE FOOTER STEEL.
  
 2} NOTE #17 INCORRECTLY REFERENCES THE
 1996 NEC.SHOULD REFERENCE THE 1999 NEC.
  
 3} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-14 Cont ID  
Sent By shernand Date 2003-07-14 Time 08:53 Rev Time 0.00
Received By shernand Date 2003-07-14 Time 08:53 Sent To E
Notes
2003-07-14 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-05-09 Time 09:07 Rev Time 0.00
Received By shernand Date 2003-05-09 Time 09:07 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-18 Cont ID  
Sent By pkrauss Date 2003-09-18 Time 10:51 Rev Time 0.25
Received By pkrauss Date 2003-09-18 Time 10:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By kstevens Date 2003-05-23 Time 18:44 Rev Time 0.25
Received By pkrauss Date 2003-06-04 Time 07:56 Sent To B
Notes
2003-06-04 00:00:00MECHANICAL PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-18 Cont ID  
Sent By kstevens Date 2003-07-18 Time 12:29 Rev Time 0.33
Received By kstevens Date 2003-07-18 Time 12:29 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-23 Cont ID  
Sent By btrobaug Date 2003-07-17 Time 15:08 Rev Time 0.25
Received By kstevens Date 2003-05-23 Time 18:44 Sent To M
Notes
2003-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN. BATH #1 IS NOT
 SHOWN ON RISER DIAGRAM. PLEASE MAKE THE
 CORRECTION AND RESUBMIT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-12 Cont ID  
Sent By shernand Date 2003-05-09 Time 09:07 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***