Plan Review Details - Permit 03050569
Plan Review Stops For Permit 03050569
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-05-09 Cont ID  
Sent By pkrauss Date 2003-05-07 Time 13:04 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-05 Time 16:22 Rev Time 0.33
Received By btrobaug Date 2003-05-06 Time 14:28 Sent To M
Notes
2003-05-06 00:00:00 
 NO ELECTRICAL PLANS OR DRAWINGS
 SUBMITTED FOR REVIEW./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 16:22 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 16:22 Sent To E
Notes
2003-05-05 00:00:00BT DESK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-07 Cont ID  
Sent By btrobaug Date 2003-05-06 Time 14:36 Rev Time 0.40
Received By pkrauss Date 2003-05-07 Time 12:11 Sent To B
Notes
2003-05-07 00:00:00PROVISO:
  
 1.RETURN AIR OR TRANSFER AIR FROM
 BEDROOM AREAS REQUIRED AS PER 2001
 FBC(M) 601.4.
  
 2.PLAN INDICATES A TRANSFER GRILLE TO
 AHU CLOSET.AHU CLOSET SHALL COMPLY
 WITH 2001 FBC(M) 603.9, MECHANICAL
 CLOSETS.
  
 3.CLOSET SHALL NOT BE USED FOR STORAGE
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-05-09 Cont ID  
Sent By lmartine Date 2003-05-09 Time 11:25 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-05-09 00:00:00SUBMIT INFORMATION WITH PLUMBING
 CONTRACTORS APPLICATION