Plan Review Stops For Permit 03050558 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2003-05-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-05-08 |
Time |
11:26 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2003-05-08 |
Time |
09:49 |
Sent To |
|
|
Notes |
2003-05-08 00:00:00 | PROVISO | | ~~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE A DETAILED DRAWING | | INDICATING THE LOCATION OF ALL DEVICES | | TO BE INSTALLED,INCLUDING LOW VOLTAGE | | IF TO BE DONE UNDER THIS PERMIT,BEFORE | | CALLING FOR ROUGH INSPECTION. | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2} PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG. | | | | 3} PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE PER 210-12. | | | | 4} THE LOAD CALCULATION MUST SHOW THE | | DRYER LOAD PER 220-18.(5000 VA.) | | | | 5} PLEASE INDICATE THE AMPERE RATING OF | | THE DISCONNECTS AND PANELS ON THE RISER | | DIAGRAM. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-05-06 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-06 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-06 |
Time |
08:53 |
Sent To |
E |
|
Notes |
|
|
|