Plan Review Details - Permit 03050558
Plan Review Stops For Permit 03050558
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-08 Cont ID  
Sent By btrobaug Date 2003-05-08 Time 11:26 Rev Time 1.00
Received By btrobaug Date 2003-05-08 Time 09:49 Sent To  
Notes
2003-05-08 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A DETAILED DRAWING
 INDICATING THE LOCATION OF ALL DEVICES
 TO BE INSTALLED,INCLUDING LOW VOLTAGE
 IF TO BE DONE UNDER THIS PERMIT,BEFORE
 CALLING FOR ROUGH INSPECTION.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 4} THE LOAD CALCULATION MUST SHOW THE
 DRYER LOAD PER 220-18.(5000 VA.)
  
 5} PLEASE INDICATE THE AMPERE RATING OF
 THE DISCONNECTS AND PANELS ON THE RISER
 DIAGRAM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-06 Time 08:53 Rev Time 0.00
Received By shernand Date 2003-05-06 Time 08:53 Sent To E
Notes
***NONE***