Plan Review Details - Permit 03050246
Plan Review Stops For Permit 03050246
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-04-12 Cont ID  
Sent By shill Date 2005-04-12 Time 14:25 Rev Time 1.00
Received By shill Date 2005-04-12 Time 14:25 Sent To  
Notes
2005-04-12 00:00:00REVISION DATED 3/28/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-02-20 Cont ID  
Sent By shill Date 2004-02-20 Time 14:09 Rev Time 0.00
Received By shill Date 2004-02-20 Time 14:09 Sent To  
Notes
2004-02-20 00:00:00SEE PROVISO, PREVIOUS REVIEW
  
 PENDING ZONING STAMP
 ZONING STAMP OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-02-20 Cont ID  
Sent By shill Date 2004-02-20 Time 12:28 Rev Time 3.00
Received By shill Date 2004-02-20 Time 12:28 Sent To  
Notes
2004-02-20 00:00:00PROVISO
  
 SINKS REQUIRED TO BE ACCESSIBLE ARE TO
 COMPLY WITH FBC11-4.24, SUBMIT DETAILS.
  
 BALUSTER GUARDRAIL TO COMPLY WITH
 FBC1608.2.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-12-18 Cont ID  
Sent By csiegber Date 2004-01-14 Time 14:35 Rev Time 3.00
Received By shill Date 2003-12-18 Time 13:41 Sent To  
Notes
2003-12-18 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE HANDRAIL DETAIL ON SHEET A1.1
 IS TO COMPLY WITH 1608.2.1.
  
 2.)INCLUDE A TITLE BLOCK ON SHEETS
 FS1,FS2,FS3 AND SEAL THE CONCRETE FLOOR
 SYSTEM SHEETS, FS61G15-23.002.
  
 3.)SEE THE PREVIOUS LIST, HOW WILL
 THE #4@12" OC TERMINATE IN THE B1 BEAM
 FOR THE BALCONY SHOWN ON SHEET S1.1?
 NOT ADDRESSED.
  
 4.)SEE THE PREVIOUS LIST IN REGARDS
 TO THE BALUSTRADE DETAIL.EMBEDMENT AT
 THE TOP WAS GIVEN BUT NOT EMBEDMENT AT
 THE BOTTOM.SEE 1608.2.2 FOR MINIMUM
 DESIGN LOADING AND PROVIDE SUPPORTING
 CALUCLATIONS TO DEMONSTRATE COMPLIANCE
 WITH SAME.SEE ALSO FBC1015 FOR MINIMUM
 GUARDRAIL DIMENSIONS AND NOTE SAME IN
 THE DESIGN CRITERIA.
  
 5.)THE ENERGY CALC TOTAL SQUARE
 FOOTAGE DOES NOT APPEAR TO BE THE SAME
 AS THE A/C AREA ON THE PLAN.ADDRESS.
  
 6.)WHEN MAKING CHANGES, IN ORDER TO
 EXPEDITE PLAN REVIEW, CLEARLY CLOUD AND
 NUMBER ALL REVISIONS.SUBMIT OLD SHEETS
 (APPROVED ZONING AND IMPACT FEE STAMP
 ARE NOT ON THIS SET AND ARE REQUIRED
 BEFORE THE PERMIT CAN BE ISSUED).
  
 7.)SUBMIT THE FOLLOWING PRODUCT
 APPROVALS:
 MULLIONS
 FIXED GLASS
 GLASS BLOCK
  
 8.)NOTICE OF COMMENCEMENT IS EXPIRED
 (90 DAYS WITHOUT COMMENCING WORK),
 FS713.13.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-09-30 Cont ID  
Sent By hpiskura Date 2003-09-30 Time 13:28 Rev Time 0.00
Received By hpiskura Date 2003-09-30 Time 13:28 Sent To  
Notes
2003-09-30 00:00:00SHEET A1.0 NOW DECLARES UL DESIGN U 906
 FOR THE FIRE RATED STAIRS.U 906
 INVOKES 6" PROPRIETARY BLOCK FOR THE
 DESIGN.
 THE PLANS INDICATE 8" BLOCK FOR THE
 STRUCTURAL.PLEASE REVISE AS NECESSARY.
  
 SHEET A1.0 CALLS FOR HANDRAILS TO BE
 DESIGNED FOR 50 PLF IN ANY DIRECTION.
 THIS DOES NOT COMPLY WITH FBC 1608.2.1.
  
 THE 90# LIVE LOAD SHOWN FOR THE STORAGE
 AREA ON SHEET A2.0 IS LESS THAN THE
 MINIMUM 125# LIVE LOAD FOR LIGHT
 STORAGE IN FBC TABLE 1604.1.
 PLEASE REVISE AS NECESSARY.
  
 SHEET A1.1 MAKES NOTE OF FIRE
 SPRINKLERSIF THE BUILDING IS TO HAVE
 FIRE
 SPRINKLERS, THE DESIGN IS REQUIRED TO
 BE ON THE PERMIT PLANS.SEE FBC
 104.3.1.1 #4.
  
 AS PREVIOUSLY NOTED, SEE FBC 104.2.1.1
 FOR THE ROOF COVERING DESIGN
 INFORMATION NECESSARY ON THE PLANS.
  
 THE PREVIOUS CHECK LIST REQUESTED THE
 DESIGN INFORMATION FOR THE PRE-CAST
 CONCRETE FLOOR SYSTEM.SEE CHAPTER
 61G15-30 RESPONSIBILITY RULES COMMON TO
 ALL ENGINEERS, OF THE FL ADMINISTRATIVE
 CODE AS PERTAINS TO DELEGATING
 ENGINEERING REQUIREMENTS.
  
 HOW WILL THE #4@12" OC TERMINATE IN
 THE B1 BEAM FOR THE BALCONY SHOWN ON
 SHEET S1.1?
  
 THE BALUSTRADE CONNECTION DETAIL ON
 SHEET A1.1 IS SOMEWHAT VAGUE WITH ITS
 >>1/2" DOWEL TOP AND BOTTOM <<.WHAT
 ISTHE EMBEDMENT DEPTH OF THE DOWEL(S)?
 WILL THEY BE CAST IN PLACE?SEE FBC
 1608.2.2 FOR MINIMUM DESIGN LOADING AND
 PROVIDE SUPPORTING CALCULATIONS TO
 DEMONSTRATE COMPLIANCE WITH SAME.
 SEE ALSO, FBC 1015 FOR MINIMUM GUARD
 RAIL DIMENSIONS AND NOTE SAME IN THE
 DESIGN CRITERIA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-09 Cont ID  
Sent By hpiskura Date 2003-06-09 Time 14:15 Rev Time 0.00
Received By hpiskura Date 2003-06-06 Time 15:08 Sent To  
Notes
2003-06-09 00:00:00PLEASE PROVIDE A COPY OF THE PAID
 IMPACT FEE RECEIPT FROM PALM BEACH
 COUNTY.
  
 THE BUILDING WILL BE LOCATED IN AN A8
 FLOOD ZONE WITH AN 15.0' BASE FLOOD
 ELEVATION RELATIVE TO NGVD.
  
 THE BUILDING WILL BE A TWO STORY MIXED
 OCCUPANCY OF B/M/S.
  
 PLEASE SHOW A LAYOUT OF THE PROPOSED
 RACK STORAGE CALLED OUT ON SHEET A1.0
 SO THA EGRESS REQUIREMENTS MAY BE
 DETERMINED. ALSO, INDICATE THE
 QUANTITIES AND NATURE OF THE
 COMMODITIES TO BE STORED.SEE FBC
 104.2.
  
 WHAT WILL THE ROOM SHOWN AS
 "CONSTRUCTION" BE USED FOR?WHERE IS
 THE EXIT DOOR?
  
 IS THE AREA SHOWN AS "CONCRETE LID" ON
 SHEET A2.0 INTENDED FOR STORAGE OR
 ANOTHER OCCUPANCY/USE?IF SO INDICATE
 THE MINIMUM DESIGN LOADS AND
 ACCESS/EGRESS.
  
 PLEASE PROVIDE DETAILS FOR THE STAIRS
 INCLUDING RISE, RUN, HANDRAILS, FIRE
 RATED ENCLOSURE PROTECTION,DESIGN
 LOADS AND CONNECTION DETAILS.
  
 SHEET S1.1.SHOW THE DIMENSIONS FOR
 THESECOND FLOOR BALCONY AND THE GUARD
 RAIL DETAILS.
  
 SHOW HOW HURRICANE MISSILE IMPACT
 RESISTANCE WILL BE ACCOMPLISHED FOR THE
 EXTERIOR GAZED PORTIONS OF THE
 BUILDINGS.SEEFBC 1606.1.4.
  
 PROVIDE THE STRUCTURAL INFORMATION ON
 THE PLANS CALLED FOR IN FBC 1606.1.7.
  
 PLEASE PROVIDE THE ROOF COVERING DETAILS
 IN ACCORDANCE WITH FBC 104.2.1.1.
  
 SHOW THE END BEARING DETAIL AND
 CONNECTION FOR THE BAR JOISTS.
  
 SHEET S1.1.HOW IS THE TS COLUMN
 ATTACHED TO THE WF BEAM?
  
 SHOW THE DESIGN SPECIFICATIONS FOR THE
 PRECAST CONCRETE AND THE CONNECTION
 BEARING DETAILS.
  
 SHOW A REINFORCEMENT DETAIL FOR THE
 CANTILEVERED 6" SLAB AND THE BALCONY.
  
 SHOW THE FIRE RATED DOORS FOR THE STAIR
 SHAFTS.SEE FBC TABLE 705.1.2.
  
 SHOW THE FIRE DESIGN NUMBER(S) FOR THE
 STAIR AND ELEVATOR SHAFTS.
  
 SHOW THE FIRE SEPARATION, AND FIRE
 DESIGN NUMBER FOR THE MIXED OCCUPANCY
 SEPARATION.SEE FBC 704.1.1.
  
 SHOW THE INSTALLATION INFORMATION FOR
 THE GLASS BLOCK.SEE FBC 2112.5.
  
 PLEASE PROVIDE SPECIFIC DESIGN
 INFORMATION FOR THE "UNISTRUT WITH 5/8
 GYP BOARD" SHOWN ON SHEET A2.0.
  
 S1.1 AND S1.2.HOW IS THE TOP OF THE
 PARAPET WALL FINISHED?LATERAL
 REINFORCEMENT?

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-08-17 Cont ID  
Sent By dpalmer Date 2005-08-17 Time 12:42 Rev Time 0.50
Received By dpalmer Date 2005-08-17 Time 12:42 Sent To  
Notes
2005-08-17 00:00:00ADDED REVISED SHEETS INTO SETS.
  
 SEE MECH COMMENTS,
 COMPUTER TO BE REVISED TO INCLUDE TENANT
 BLD-OUT UNDER THIS PERMIT AND ANY
 VALUATION ADJUSTMENT FOR TENANT BLD-OUT.
 THIS WAS OK'D PER LUIS MARTINEZ

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-08-04 Cont ID  
Sent By dpalmer Date 2005-08-04 Time 17:50 Rev Time 1.00
Received By dpalmer Date 2005-08-04 Time 17:50 Sent To  
Notes
2005-08-04 00:00:00********** UNSAT **********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEWS AND SEE NEW NOTES DUE TO CHNAGES
 IN PLANS.
 **PLEASE SEE PLANS ARE FOR FINAL/ CO AND
 ALL ON PLANS MUST BE CORRECTED AT 100%.
  
 1)NOTE: PLEASE SEE NO "EQUIPMENT
 GROUNDING CONDUCTORS" ARE INSTALLED
 UNTIL AFTER THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE 250.6,250.24, SEE
 RISER DIAGRAM.
  
 2)NOTE: PLEASE SEE SEC'S SHOWN FROM FPL
 TO GUTTER?? PLEASE SEE 2-SETS OF 3/0'S
 ARE ONLY RATED FOR 400AS' AND SERVICE
 SHOWS MIN LOADS AFTER ALL DERATINGS OVER
 400A'S.
 PLEASE SEE 240.4,310.16 FOR MIN SEC'S
 REQUIRED.
  
 3)NOTE: PLEASESEE 250.66 FOR ANY
 ADJUSTMENT IN GROUNDINGELECTRODE
 CONDUCTOR? PLEASE SEE ORIGINAL SET WAS
 REDLINED DUE TO INCORRECT SIZE SHOWN.
  
 4)NOTE: PLEASE SEE MISSING AIC RATING
 FOR MAIN DISCONNECT FEEDING PANEL "D".
 110.9, 215.5
  
 5)NOTE: PLEASE CORRELATE PANEL "C" WITH
 RISER DIAGRAM. PLEASESEE A MCB IS
 REQUIRED FOR GROUPING OF MAINS ETC.
 230.72,215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-04-04 Cont ID  
Sent By dpalmer Date 2005-04-04 Time 11:41 Rev Time 1.50
Received By dpalmer Date 2005-04-04 Time 09:26 Sent To  
Notes
2005-04-04 00:00:00******* UNSAT *********
  
 1)NOTE: PLEASE SEE REVISION TO SPACE IS
 TO BE SUBMITTED UNDER A SEPARATE PERMIT
 AS NOTED ON ORIGINAL BLDG PLANS.
  
 2)NOTE: PLEASE ALSO SUBMIT REVISED
 PLANS/RISER FOR BASE BLDGS.
  
 3)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT. 250.6,250.24
  
 4)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR PER 250.66.
 THIS WAS ON ORIG THREE REVIEWS AND
 REDLINED ON PERMITTED PLANS.
 250.66 MIN 1/0 (MISPRINT)?
  
 5)NOTE: PLEASE VERIFY LOCATION OF NEW
 TRANSFER SWITCH. PLEASE SHOW AS EITHER
 MANUAL?AUTO? PLEASE SUBMIT SPECS
 SHEETS FOR TRANSFER SWITCH, SHOWONG IF
 IT IS "SERVICE ENT RATED"
 PLEASE VERIFY IF TRANSFER SWITCH IS
 INDEED ON LOAD SIDE OF SERVICE DISC?
  
 6)NOTE: PLEASE INCLUDE ALL CONDUCTORS
 FROM GUTTER TO MAINS ETC.
 215.5,310.16
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-02-19 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 11:34 Rev Time 0.50
Received By dpalmer Date 2004-02-19 Time 11:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-11-05 Cont ID  
Sent By dpalmer Date 2003-11-05 Time 15:13 Rev Time 2.00
Received By dpalmer Date 2003-11-05 Time 15:13 Sent To  
Notes
2003-11-05 00:00:00************** UNSAT ***********
  
 PLEASE NOTE: OWES RESUB FEE, DID NOT
 GET ACCESSED WHEN RESUBMITTED.
  
 PLEASE NOTE: PER FS 713, IF WORK HAS
 NOT COMMENCED W/IN 90 DAYS OF RECORDING
 NOC, A NEW RECORDED NOC IS REQ'D BEFORE
 PICKING UP PERMIT.
  
 1)NOTE: PLEASE SEE RISER DIAGRAM WHICH
 HAS NOW BEEN REVISED TO ADDRESS PREVIOUS
 COMMENTS.
 RISER NOW SHOWS EQUIPMENT GROUNDING
 CONDUCTORS BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOW PARALLELING THE
 NEUTRAL? PLEASE SEE ORIG COMMENT, ASK
 FOR MISSING EQUIPMENT GROUNDING FROM
 MAIN DISC'S TO PANELS.250.110,250.122.
 PER 250.24
  
 2)NOTE: PLEASE SEE RISER, NOW SHOWS A
 #3 ALONG WITH THE 4 500MCM CONDUCTORS
 FROM GUTTER TO METER AND THEN TO GUTTER
 ON LOAD SIDE OF K-7? PLEASE CLARIFY
 WHAT THIS #3 CONDUCTOR IS???
 PLEASE ALSO SEE 250.24
  
 3)NOTE: PLEASE SEE PLANS AND SHOW
 LOCATION OF SIGN CIRCUIT. IT IS NOTED
 THAT PANEL SCHEDULE SHOWS CIRCUIT
 HOWEVER THIS COULD NOT BE LOCATED ON
 PLANS.
  
 4)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS. PLEASE ALSO SEE 700.12E
 PLEASE SEE ONE SET OF PLANS HAS A FEW
 OF THESE ITEMS HIGHLIGHTED.
  
 5)NOTE: PLEASE CORRELATE SYMBOLS ON
 PLANS AND SYMBOL LIST.
  
 SOME OF THE ABOVE NOTES ARE FROM FIRST
 TWO REVIEW. A NOTICE WAS GIVEN ON PREVI-
 -OUS REVIEW IN REF TO FS 553.80(2)(B)
 PLEASE SEE AS PER FS A 4X FEE MUST NOW
 BE ASSESSED AND MUST BE PAID BEFORE
 RESUBMITTING FOR NEXT REVIEW.
 PLEASE SEE BZ ATTACHED $11,924.42, THIS
 FEE MAY BE ADJUSTED DUE TO VALUATION
 ADJUSTMENT ON PERMIT FEE.
 NEW COMMENT:
 1)NOTE: PLEASE KNOW THAT PER FS 471.025
 AND FAC 61G15-23.002, A NOTICE FROM THE
 FBPE'S HAS BEEN GIVEN TO THIS OFFICE
 AND REQUIRE'S ENGINEER TO SIGN PLANS
 WITH A SIGNATURE AND INITIALS ARE NOT
 ACCEPTABLE. MUST SIGN A MIN OF FIRST
 AND LAST NAME AS RECORDED ON SAID SEAL.
  
 PLEASE TAKE ALL OLD /VOIDED SHEETS OUT
 AND INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-29 Cont ID  
Sent By dpalmer Date 2003-09-29 Time 16:19 Rev Time 2.00
Received By dpalmer Date 2003-09-29 Time 16:19 Sent To  
Notes
2003-09-29 00:00:00************* UNSAT *******************
  
 PLEASE SEE THAT SOME NOTES FROM FIRST
 REVIEW NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 IE, ACCU-1 ON ROOF SHOWN ON GFI RECEPT
 CIRCUIT. PLEASE GO THROUGH OTHERS.
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
 PLEASE ALSO SEE 700.16 STAIRWAY?
  
 3)NOTE: PLEASE SEE SERVICE LOCATION
 OUTSIDE, APPEARS TO ONLY SHOW ONE METER
 AND THREE PANELS/ORDISCS.
  
 4)NOTE: PLEASE SEE /CLARIFY MEANS OF
 EEQUIPMENT GROUNDING FROM MAIN DISC'S TO
 PANELS. 250.24/250.110/250.122
  
 5)NOTE: PLEASE CLARIFY LOCATION OF REQ'D
 SIGN CIRCUIT 600.5
  
 6)NOTE: PLEASE SEE FIRE PLAN REVIEW
 NOTES THAT WILL HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 7)NOTE: CIRCUIT FOR OUTSIDE WALLPACKS
 IS NOW SHOWN ,HOWEVER HOW ARE THESE
 CONTROLLED? PC/TC? ARE THEY ON 24/7?
  
 8)NOTE: PLEASE CLARIFY WHAT APPEARS TO
 BE A FAN OUTSIDE NEXT TO SERVICE?
  
 9)NOTE: PLEASE CORRELATE SYMBOLS FOR
 EXIT LTS AND ANY OTHERS.
 PLEASE CLARIFY MEANS OF LIGHTING STAIR-
 WAY. LS 101 5-8
  
 10)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE NOTE, MAX FUTURE TENANT TO BE
 100A'S.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-13 Cont ID  
Sent By dpalmer Date 2003-05-13 Time 06:46 Rev Time 2.00
Received By dpalmer Date 2003-05-13 Time 06:46 Sent To  
Notes
2003-05-13 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE INCLUDE LICENSE # IN
 TITLE BLOCK FOR ARCH OF RECORD AS REQ`D
 IN FS/ FAC 61G1-16.004/ 481
  
 2)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 ON ALL SHEETS. PERMIT APPLICATION
 MENTIONS A SHOWROOM?
  
 3)NOTE: PLEASE CLARIFY HEIGHTS OF GFI`S
 IN GARAGE.
  
 4)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE W/ SUBMITTE PANEL
 SCHEDULES. PLEASE CIRCUIT ALL EM/ EXT LT
 -S PER 700-16E
  
  
 5)NOTE: PLEASE SHOW CONTROL AND CIRCUIT-
 ING OF OUTSIDE LIGHTING.
  
 6)NOTE: PLEASE SEE PLANS, THERE SEEMS
 TO BE CIRCUITING SHOWN IN AREAS THAT DO
 NOT GO TO ANYTHING?
  
 7)NOTE: PLEASE COMPLETE LOAD CALCULATION
 -S. SHOWN BLANK?
  
 8)NOTE: PLEASE SHOW MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN DISC`S TO
 PANELS. 250-110/250-122
  
 9)NOTE: PLEASE CLARIFY SIZE ALLOWED FOR
 FUTURE TENANT/METER AND MAIN DISC?
 PLEASE BE SURE TO SIZE SEC`S FOR FUTURE
 LOADS ALSO. SERVICE IS 400A`S AT PRESENT
 TIME.
  
 10)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66. BASED ON SEC`S
 310-16
  
 11)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 TO FOOTER STEEL AND COLD WATER ETC
 AS PER 250-50 AND ALSO ANY BLDG STEEL.
  
 12)NOTE: PLEASE VERIFY OCP SHOWN FOR
 COND UNITS/ A/C.
  
 MIN 125%.
 PLEASE ALSO SIZE WIRE PER 310-16 (75~)
  
 13)NOTE: PLEASE SEE LOADING OF TRACK
 LIGHTING CIRCUIT.
  
 14)NOTE: PLEASE SHOW ALL CONTINUOUS AND
 MOTOR LOADS @125%. (EXT LTS).(ELEV)
 215-3/230-42
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEWING AND STAMPING.(MUST BE DONE
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-10-21 Cont ID  
Sent By mamini Date 2003-10-21 Time 14:28 Rev Time 0.50
Received By mamini Date 2003-10-21 Time 14:28 Sent To  
Notes
2003-10-21 00:00:00PASSED:
 1. SEE PERMIT # 03101164 FOR UNDERGROUND
 UTILITIES AND SITE WORK .
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-09-11 Cont ID  
Sent By mamini Date 2003-09-11 Time 08:29 Rev Time 1.00
Received By mamini Date 2003-09-11 Time 08:29 Sent To  
Notes
2003-09-11 00:00:00FAILED:
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS STISFACTORY EXCEPT COMMENT NO.
 6 THAT HAS NOT BEEN ADDRESSED.
 A) SUBMIT THREE SETS OF CIVIL PLANS ONLY
 (SHEET SP1.0, SP1.1,SP1.2,) TO THE
 PUBLIC UTILITIES & ENGINEERING AT 1000
 45TH STREET ATT: MANNY GONZALEZ
 B)SUBMIT TWO SETS OF THE SAME WITH
 APPROVED STAMP TO US WITH A SEPARATE
 APPLICATION AND APPROPRIATE FEES FOR
 "UNDERGROUND UTILITIES AND SITE WORK
 PERMIT".
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-05-06 Cont ID  
Sent By mamini Date 2003-05-06 Time 14:59 Rev Time 1.00
Received By mamini Date 2003-05-06 Time 14:59 Sent To  
Notes
2003-05-06 00:00:00FAILED :
 1. PLEASE PROVIDE STORM WATER
 CALCULATION (WATER QUALITIES) FOR OUR
 REVIEW.
 2. DRIVEWAY APPROACHES MUST BE
 CONSTRUCTED PER CITY STANDARD, FROM CURB
 CUT TO PROPERTY LINE SHOULD BE 6"
 CONCRETE.
 2. ALL PARKING STALLS MUST PAINTED WITH
 DOUBLE 4" STRIPES, PER CITY REQUIREMENT.
 3. A BACKFLOW PREVENTER IN 1" WATER
 SERVICE IS REQUIRED.
 3. A CLEAN OUT WILL NEED TO BE INSTALLED
 IN THE SANITARY SEWER LATERAL, ON THE
 PROPERTY AT BACK OF SIDEWALK, IF NOT
 ALREADY INSTALLED.
 4. 6" SEWER LATERAL SHOULD BE CONNECTED
 TO MANHOLE? AS SHOWN DIRECTLY WITHOUT
 USE OF 8X6 REDUCER, PLEASE VERIFY.
 5. POLLUTION/EROSION PLANS MUST BE ADDED
 TO CIVIL/SITE PLAN, DETAILS, SILT FENCE,
 NOTE TO GC, ECT.PLANS MUST BE
 INSTALLED IN FIELD PRIOR TO ANY EARTH/
 CONSTRUCTION.
 6. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK IS REQUIRED.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2005-08-24 Cont ID  
Sent By mwennerg Date 2005-08-24 Time 09:40 Rev Time 0.00
Received By mwennerg Date 2005-08-24 Time 09:40 Sent To  
Notes
2005-08-24 00:00:00******DENIED******
  
  
  
 PASSED ON PREVIOUS REVIEW. IT CAN'T BE
 DETERMINED IF REVISIONS HAVE IMPACT ON
 FIRE REVIEW AND LIFE SAFETY. PLEASE
 CLEARLY IDENTIFY CHANGES FOR FUTURE
 REVIEW PROCESS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-04-11 Cont ID  
Sent By mwennerg Date 2005-04-11 Time 16:00 Rev Time 0.00
Received By mwennerg Date 2005-04-11 Time 16:00 Sent To  
Notes
2005-04-11 00:00:00PASSED PROVISO
  
 1) ALL REVIEW NOTES FROM 12/24/03 THAT
 HAVE NOT BEEN ADDRESSED, SHALL BE
 COMPLIED WITH PRIOR TO ANY FIELD
 INSPECTIONS.
  
 2) SEPARATE PERMIT AND DRAWINGS ARE
 REQUIRED FOR AREAS NOT INCLUDED AND
 WITHIN THE SCOPE OF THIS PERMIT AND
 DRAWINGS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-12-24 Cont ID  
Sent By mcarsill Date 2003-12-24 Time 15:53 Rev Time 0.00
Received By mcarsill Date 2003-12-24 Time 15:53 Sent To  
Notes
2003-12-24 00:00:001) THE FIRE DEPARTMENT CONNECTION SHALL
 BE PROVIDED WITH 7'- 6" CLEARANCE.
  
 2) THE FIRE DEPARTMENT CONNECTION SHALL
 BE WITHIN 150 FEET OF A FIRE HYDRANT.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL. THE
 FIRE SPRINKLER SYSTEM AND ANY FIRE
 ALARM SYSTEM EQUIPMENT MUST BE UL
 LISTED FOR CENTRAL STATION SERVICE SINCE
 THIS BECAME EFFECTIVE AUGUST 1, 2003.
  
 4) THE DESIGN TEAM AND OWNER RED-LINED
 THE DRAWINGS ON 12-24-03 AND MADE
 CORRECTIONS TO THE DRAWINGS.
  
 5) THE BACKFLOW DEVICE FOR THE FIRE
 SPRINKLER SYSTEM IS REQUIRED TO HAVE
 TAMPER SWITCHES AND A CHAIN AND LOCK.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-11-24 Cont ID  
Sent By mcarsill Date 2003-11-24 Time 16:27 Rev Time 0.00
Received By mcarsill Date 2003-11-24 Time 16:27 Sent To  
Notes
2003-11-24 00:00:001) ONE HOUR DOORS STILL SHOWN AT THE
 GARAGE. THESE DOORS SHALL BE AT LEAST
 1 1/2 HOURS SINCE THE WALLS ARE
 REQUIRED TO BE AT LEAST TWO HOUR
 FIRE RATED.
  
 2) DOORS # 13 AND 17 SHALL BE 45 MINUTE
 FIRE RATED. STORAGE IS NOT PERMITTED
 UNDER STAIRS UNLESS THE STORAGE AREA
 IS RATED THE SAME AS THE REQUIRED
 RATING FOR THE STAIRS.
  
 3) DOOR HARDWARE ON DOORS # 23 AND 26
 SHALL NOT REQUIRE THE USE OF A KEY,
 TOOL, SPECIAL KNOWLEDGE OR EFFORT.
 DOOR # 23 CANNOT BE LOCKABLE FROM
 WITHIN THE OFFICE.
  
 4) KNOX-BOX SHOULD BE INSTALLED ON
 ELEVATION WHERE THE ADDRESS IS LOCATED.
  
 5) FIRE SPRINKLER PLANS ARE REQUIRED
 AT TIME OF PERMIT. SHOP DRAWINGS
 ARE REQUIRED LATER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-09-12 Cont ID  
Sent By mcarsill Date 2003-09-12 Time 16:06 Rev Time 0.00
Received By mcarsill Date 2003-09-12 Time 16:06 Sent To  
Notes
2003-09-12 00:00:001) PLEASE PROVIDE A LIFE SAFETY PLAN.
 SOME PORTIONS OR AREAS HAVE A SINGLE
 MEANS OF EGRESS. PLEASE EXPLAIN
 RATIONALE. SOME AREAS HAVE A SINGLE
 MEANS OF EGRESS THAT INCLUDE THE RACK
 STORAGE, GARAGE AND FLOOR COVERING
 SHOWROOM.
  
 2) NO EMERGENCY LIGHTS IN OFFICE, FIRST
 FLOOR.
  
 3) NO FIRE SPRINKLER PLANS PROVIDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-05 Cont ID  
Sent By mcarsill Date 2003-06-05 Time 15:30 Rev Time 0.00
Received By mcarsill Date 2003-06-05 Time 15:30 Sent To  
Notes
2003-06-05 00:00:001) DOOR SCHEDULE INDICATES NO RATED
 FIRE DOORS. PLEASE EXPLAIN RATIONALE.
  
 2) DOORS 19 AND 20 OPPOSE ONE ANOTHER.
  
 3) A KNOX-BOX WILL BE REQUIRED FOR THE
 BUILDING.
  
 4) IN SOME OTHER LOCALES DOORS OPPOSE
 ONE ANOTHER.
  
 5) PLEASE CLEARLY ILLUSTRATE ALL
 EMERGENCY LIGHTS.
  
 6) PLEASE SHOW HANDRAILS ON BOTH SIDES
 OF ALL STAIRS.
  
 7) PLEASE SHOW PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS.
  
 8) NO FIRE SPRINKLER PLANS PROVIDED WITH
 PLANS. DRAWINGS ILLUSTRATE A FIRE LINE
 ENTERING THE BUILDING. PLEASE PROVIDE
 REQUIRED INFORMATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8097,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 14:43 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 14:43 Sent To M
Notes
2005-09-12 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 08:13 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 08:13 Sent To  
Notes
2005-08-16 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-08-02 Cont ID  
Sent By adarroug Date 2005-08-02 Time 13:28 Rev Time 0.00
Received By adarroug Date 2005-08-02 Time 13:28 Sent To  
Notes
2005-08-02 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 12:57 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 12:57 Sent To  
Notes
2005-03-31 00:00:00TO "COMM" BD#36

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 15:53 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 15:53 Sent To  
Notes
2004-02-11 00:00:00TO COMM BD#33

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-01-14 Cont ID  
Sent By shill Date 2004-01-14 Time 15:15 Rev Time 0.00
Received By shill Date 2004-01-14 Time 15:15 Sent To  
Notes
2004-01-14 00:00:00SUBMITTALS PUT WITH PLANS WHICH HAVE
 NOT BEEN PICKED UP BY CONTRACTOR

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-14 Time 14:35 Rev Time 0.00
Received By csiegber Date 2004-01-14 Time 14:35 Sent To B
Notes
2004-01-14 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-11-04 Time 10:47 Rev Time 0.00
Received By csiegber Date 2003-11-04 Time 10:47 Sent To  
Notes
2003-11-04 00:00:00TO COMM BD#36

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-09 Cont ID  
Sent By csiegber Date 2003-09-09 Time 11:24 Rev Time 0.00
Received By csiegber Date 2003-09-09 Time 11:24 Sent To  
Notes
2003-09-09 00:00:00ON COMM BD#48

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-09-03 Time 12:22 Rev Time 0.00
Received By csiegber Date 2003-09-03 Time 12:22 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-06 Time 10:29 Rev Time 0.00
Received By shernand Date 2003-05-06 Time 10:29 Sent To  
Notes
2003-05-06 00:00:00COMM BOARD #35

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2005-09-19 Cont ID  
Sent By pkrauss Date 2005-09-19 Time 12:42 Rev Time 0.45
Received By pkrauss Date 2005-09-19 Time 10:22 Sent To  
Notes
2005-09-19 00:00:00PROVISO:
 1.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IS
 REQUIRED PER 2001 FBC(M)606.2.1.
  
 2.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM - 2001
 FBC(M)602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2005-08-17 Cont ID  
Sent By pkrauss Date 2005-08-17 Time 07:36 Rev Time 0.55
Received By pkrauss Date 2005-08-17 Time 07:14 Sent To E
Notes
2005-08-17 00:00:00DENIED:
 1.PLAN SHEET A-3 , IN THE REVISIONS
 SUBMITTED APPEARS TO BE A NEW SHEET.
 THE ORIGINAL SUBMITTAL A-3.0 IS AN
 ELEVATION PLAN NOT A MECHANICAL HVAC
 PLAN.PLEASE CLARIFY IF THIS IS
 ADDITIONAL WORK THAT WAS NOT COVERED
 UNDER THE ORIGINAL SCOPE OF WORK.
  
 REVISIONS FOR PLAN SHEET MEP2.1, MEP2.2,
 & MEP3.0 ARE APPROVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2005-04-11 Cont ID  
Sent By pkrauss Date 2005-04-11 Time 14:52 Rev Time 0.45
Received By pkrauss Date 2005-04-11 Time 14:44 Sent To  
Notes
2005-04-11 00:00:00DENIED:
 PLANS SUBMITTED AS A REVISION.THIS
 SECTION OF THE BUILDING WAS NEVER
 REVIEWED UNDER THE REFERENCED PERMIT
 NUMBER.PLAN SHEET MEP1.1 INDICATES
 "THIS SPACE TO BE BUILT UNDER SEPARATE
 PERMIT".
  
 1.PLEASE INDICATE LOCATION OF THE
 CONDENSING UNIT.PROVIDE INFORMATION
 FOR THE STAND IF LOCATED ON THE ROOF.
 SHOW COMPLIANCE WITH 2001 FBC 1511.7.
  
 2.INDICATE ACCESS TO THE ROOF.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 2001 FBC/M606.2.1 AND
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS 606.4.1 #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-12-11 Cont ID  
Sent By pkrauss Date 2003-12-11 Time 16:32 Rev Time 0.20
Received By pkrauss Date 2003-12-11 Time 16:32 Sent To  
Notes
2003-12-11 00:00:00PER CONVERSATION WITH PETE RUSSO,
 O.A. CALCS FOR ALL AREAS & EQUIPMENT
 SCHEDULE ON PLAN SHEET MEP-3.0.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-12-09 Cont ID  
Sent By pkrauss Date 2003-12-09 Time 06:39 Rev Time 0.45
Received By pkrauss Date 2003-12-09 Time 06:38 Sent To  
Notes
2003-12-09 00:00:00DENIED:
 PLEASE NOTE COMMENTS 1 AND 2 FROM 1ST
 REVIEW NOT ADDRESSED.
  
 1.PROVIDE O.A. CALCULATIONS PER 2001
 FBC(M) 403.3.
  
 2.PROVIDE CALCULATIONS FOR THE GARAGE
 PER 2001 FBC 411.4.2 MINIMUM OF 6 AIR
 CHANGES PER HOUR OR 403.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-09-24 Cont ID  
Sent By pkrauss Date 2003-09-24 Time 07:13 Rev Time 0.55
Received By pkrauss Date 2003-09-24 Time 07:13 Sent To  
Notes
2003-09-24 00:00:00DENIED:
 1. PLEASE CLARIFY OUTSIDE AIR TO AHU-1.
 NOTE ON PLAN SHEET MEP 2.1 INDICATES
 O.A. AT CEILING OF THE FIRE PUMP ROOM.
 OUTSIDE AIR NEEDS TO COME FROM OUTSIDE
 THE BUILDING. INTAKE OPENING SHALL BE
 LOCATED A MINIMUM OF 10 FT FROM LOT LINE
 OR BUILDINGS ON THE SAME LOT (2001 FBC/M
 401.5.)
  
 CLARIFY RETURN AIR FOR AHU-1. WILL THE
 MECHANICAL ROOM BE USED AS A PLENUM?
 MECHANICAL CLOSETS/ROOMS TO COMPLY WITH
 2001 FBC CHAPTER 13 SUB-SECTION 410.1.AB
 410.1.ABCD.3.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-19 Cont ID  
Sent By pkrauss Date 2003-05-19 Time 15:28 Rev Time 0.55
Received By pkrauss Date 2003-05-19 Time 14:55 Sent To  
Notes
2003-05-19 00:00:00DENIED:MECHANICAL PERMIT 03050253
  
 1.PLEASE PROVIDE OUTSIDE AIR CALCS
 AS PER 2001 FBC(M) TABLE 403.3.
  
 2.PROVIDE CALCULATIONS FOR AIR CHANGES
 IN GARAGE AREA AS PER TABLE 403.3.
  
 3.PLAN SHEET MEP3.0 INDICATES EF-1
 TO RUN 15 MINUTES PER HOUR.AS PER 2001
 FBC(M) 403.4 MECHANICAL VENTILATION NOT
 REQUIRED TO RUN CONTINUOUSLY WHERE THE
 SYSTEM IS ARRANGED TO OPERATE AUTO-
 MATICALLY UPON DETECTION OF A CONCENTRA-
 TIONOF CARBON MONOXIDE OF 25 (PPM) BY
 APPROVED AUTOMATIC DETECTION DEVICES.
  
 4.CONDENSER UNIT STANDS ON ROOF SHALL
 COMPLY WITH 2001 FBC 1511.7 FOR THE
 DISTANCE BETWEEN THE ROOF FINISHED
 SURFACE AND THE BOTTOM OF THE SUPPORT
 RAIL.
  
 5.FIRE DAMPERS ARE NOT INDICATED ON
 PLAN.PLEASE NOTE, FIRE DAMPERS ARE
 REQUIRED WHERE DUCTS PENETRATE A FIRE
 RATED WALL PARTITION OR FLOOR.PLEASE
 SHOW LOCATIONS OF ALL FIRE DAMPERS THAT
 ARE REQUIRED.2001 FBC(M) 607.6
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.
 E

Review Stop P PLUMBING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-02-20 Cont ID  
Sent By kstevens Date 2004-02-20 Time 15:03 Rev Time 1.50
Received By kstevens Date 2004-02-20 Time 15:03 Sent To  
Notes
2004-02-20 00:00:00PASSED/PROVISO
  
 REVISIONS REQUIRED FOR THE FOLLOWING
 - SHOW STARTING POINT FOR GUTTERS SLOP-
 ING TO DOWNSPOUTS.
 - SUBMIT DETAIL FOR BATHROOM ON SECOND
 FLOOR SHOWING SIZE OF OPENING FOR W/C,
 CLEAR FLOOR SPACE FOR LAV AND W/C, GRAB
 BARS FOR W/C, IF PARALLEL APPROACH FOR
 LAV., LAV TO BE 2' OFF WALL.
 - SUBMIT DETAIL FOR BAR SINK SHOWING
 CLEAR FLOOR SPACE AND IF PARALLEL APPRO-
 ACH SINK SHALL BE 2' OFF WALL TO CENTER
 OF 48" CFS.

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-02-19 Cont ID  
Sent By kstevens Date 2004-02-19 Time 16:19 Rev Time 5.00
Received By kstevens Date 2004-02-19 Time 16:19 Sent To  
Notes
2004-02-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) FROM PREVIOUS REVIEWS.
 DISPLAY BATHROOM SHOWER DETAILS NOT
 SUBMITTED. SECTION 11-4.21 AND ALL SUB-
 SECTIONS. (COMMENT #2 FROM PREVIOUS RE-
 VIEWS).
 2) FROM PREVIOUS REVIEWS.
 SUBMIT DETAIL FOR GRAB BARS FOR W/C,
 SHOW LAV HEIGHT AND CLEAR FLOOR SPACE
 FOR LAV AND WATER CLOSET.
 3) FROM PREVIOUS REVIEWS.
 SUBMIT CALCULATIONS FOR ROOF GUTTERS AND
 DOWNSPOUTS. SHOW TOTAL SQUARE FOOTAGE
 FOR EACH ROOF AREA. AREA OF UPPER ROOF
 THAT DRAINS TO LOWER ROOF SHALL BE ADDED
 WHEN SIZING GUTTERS AND DOWN SPOUTS.
 SHOW IN CALCULATIONS. ALSO SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS
 ADDED TO CALCULATIONS. TABLE 1106.2 AND
 TABLE 1106.6. INDICATE PITCH (SLOPE) OF
 GUTTER AND SHOW WHERE THE PITCH TO EACH
 DOWNSPOUT STARTS. (HIGH POINT)
 4) NEW COMMENT. BAR SINK SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. PROVI-
 DE A DETAIL SHOWING HEIGHT, CLEAR FLOOR
 SPACE, KNEE CLEARANCE, DEPTH, EXPOSED
 PIPES, FAUCETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-12-06 Cont ID  
Sent By kstevens Date 2003-12-06 Time 04:45 Rev Time 1.00
Received By kstevens Date 2003-12-06 Time 04:45 Sent To  
Notes
2003-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BLDG.
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED. THE NUMBER SHALL STAY THE
 SAME FOR CLAIRITY.
 2) IF BATHING ROOMS ARE PROVIDED, THEN
 EACH PUBLIC AND COMMON USE BATHING FAC-
 ILITY SHALL COMPLY WITH 11-4.23. SECTION
 11-4.1.2(6) - SHOW ALL REQUIREMENTS FOR
 CLEAR FLOOR SPACE 11-4.23.3, SHOWER
 STALLS 11-4.21, SHOWER SEAT 11-4.21.3,
 SHOWER GRAB BARS 11-4.21.4, SHOWER CON-
 TROLS 11-4.21.5, SHOWER UNIT 11-4.21.6,
 CURBS 11-4.21.7, WATER CLOSETS 11-4.23.4
 3) SHT A1.0 LOUNGE AND KITCHEN SINKS
 SHALL COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS. PROVIDE DETAIL. (THE ONLY DE-
 TAIL SHOWN IS COUNTER HEIGHT. PROVIDE
 DETAIL FOR ALL SUBSECTIONS).
 4) SHT A1.0 ALL TOILET ROOMS SHALL
 COMPLY WITH 11-4.24, 11-4.16, 11-4.19
 AND ALL SUBSECTIONS. PROVIDE DETAILS.
 (CLEAR FLOOR SPACE AND TURNING AREAS NOT
 SHOWN FOR ALL TOILET ROOMS).
 5) SHT A1.1 SEE COMMENT #4.
 6) SHTA1.2 SUBMIT CALCULATIONS FOR ROOF
 GUTTER AND DOWNSPOUTS. SHOW TOTAL SQUARE
 FOOTAGE FOR EACH ROOF AREA. AREA OF UP-
 PER ROOF THAT DRAINS TO LOWER ROOF SHALL
 BE ADDED WHEN SIZING GUTTERS AND DOWN-
 SPOUTS. SHOW IN CALCULATIONS. ALSO SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED TO CALCULATIONS. TABLE
 1106.2 AND TABLE 1106.6. INDICATE PITCH
 (SLOPE) OF GUTTER AND SHOW WHERE THE
 PITCH TO EACH DOWNSPOUT STARTS.
 ---NEW COMMENTS
 1B) SIGNATURE REQUIRED ON SEAL PER
 61G15-23.002(1) - FS471.025
 2B) IRRIGATION PERMIT REQUIRED.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION. (THIS WAS NOT ADDRESSED)
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-01 Cont ID  
Sent By kstevens Date 2003-10-01 Time 07:54 Rev Time 1.00
Received By kstevens Date 2003-09-30 Time 18:51 Sent To  
Notes
2003-10-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMIN. CODE
 A) FOLLOWING COMMENTS HAVE NOT BEEN
 ADDRESSED FROM PREVIOUS REVIEW. THE
 NUMBER SHALL STAY THE SAME FOR CLAIRITY.
 1) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FACILITIES. TABLE 403.1 - INDICATE
 TOTAL AREA FOR EACH OCCUPANCY AND TOTAL
 FIXTURES REQUIRED FOR EACH OCCUPANCY.
 2) IF BATHING ROOMS ARE PROVIDED, THEN
 EACH PUBLIC AND COMMON USE BATHING FAC-
 ILITY SHALL COMPLY WITH 11-4.23. SECTION
 11-4.1.2(6).
 3) SHT A1.0 LOUNGE AND KITCHEN SINKS
 SHALL COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS. PLEASE PROVIDE DETAILS.
 4) SHT A1.0 ALL TOILET ROOMS SHALL
 COMPLY WITH 11-4.24, 11-4.16, 11-4.19
 AND ALL SUBSECTIONS. PLEASE PROVIDE DE-
 TAILS.
 5) SHT A1.1 SEE COMMENT #4.
 6) SHT A1.2 SUBMIT CALCULATIONS FOR ROOF
 GUTTER AND SOWNSPOUTS. SHOW TOTAL SQUARE
 FOOTAGE FOR EACH ROOF AREA. AREA OF UP-
 PER ROOF THAT DRAINS TO LOWER ROOF SHALL
 BE ADDED WHEN SIZING GUTTERS AND DOWN-
 SPOUTS. SHOW IN CALCULATIONS. ALSO SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADD TO CALCULATIONS. TABLE
 1106.2 AND TABLE 1106.6. INDICATE PITCH
 (SLOPE) OF GUTTER, AND SHOW WHERE THE
 PITCH TO EACH DOWNSPOUT STARTS.
 7) DOWNSPOUTS SHALL TERMINATE A MINIMUM
 OF 1' FROM THE STRUCTURE SIDEWALL. SEC
 1503.4.4. PROVIDE A DETAIL.
 11) SHT MEP3.0 SANT RISER DIAGRAM, ONLY
 FIXTURES FROM THE BATHROOM GROUP SHALL
 DRAIN THROUGH THE HORIZONTAL WET VENT.
 SEC 909.1. 1ST FLOOR KITCHEN SINK SHALL
 CONNECT DOWNSTREAM OF THE TOILET ROOM
 FIXTURES. SEPARATE STACK FOR KITCHEN
 SINK REQUIRED.
 12) SUPPLY TO HOSE BIBB IN ELECTRICAL
 ROOM IS NOT SHOWN ON SHT MEP2.3 NOR SHT
 MEP3.0 RISER.104.2.1
 NEW COMMENTS:
 13) SECTION 606.2(2) SHUTOFF VALVE RE-
 QUIRED FOR HOSE BIBB.
 14) PLEASE BE AWARE OF FF 553.80(2)(B)
 CONCERNING DESIGN PROFESSIONALS AND PLAN
 REVIEWS.
  
 ---------WHEN RESUBMITTING PLANS--------
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-04 Cont ID  
Sent By kstevens Date 2003-06-04 Time 14:13 Rev Time 2.75
Received By kstevens Date 2003-06-04 Time 12:56 Sent To  
Notes
2003-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FACILITIES. TABLE 403.1 - INDICATE
 TOTAL AREA FOR EACH OCCUPANCY AND TOTAL
 FIXTURES REQUIRED FOR EACH OCCUPANCE.
 (ALSO SEE TABLE 1003.1 BLDG CODE)
 2) IF BATHING ROOMS ARE PROVIDED, THEN
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH 11-4.23
 3) SHT A1.0 LOUNGE AND KITCHEN SINKS
 SHALL COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS. PLEASE PROVIDE DETAILS.
 4) SHT A1.0 ALL TOILET ROOMS SHALL SHOW
 LENGTH AND WIDTH ON PLANS. ALL TOILET
 ROOMS SHALL COMPLY WITH 11-4.22 AND ALL
 SUBSECTIONS. PLEASE PROVIDE DETAILS.
 5) SHT A1.1 - SEE COMMENT #4.
 6) SHT A1.2 SUBMIT CALCULATIONS FOR ROOF
 GUTTER AND DOWNSPOUTS. SHOW SQUARE FOOT-
 AGE FOR EACH ROOF AREA. AREA OF UPPER
 ROOF THAT DRAINS TO LOWER ROOF SHALL BE
 ADDED WHEN SIZING GUTTERS AND DOWNSPOUTS
 OF LOWER ROOF. BE SURE TO SHOW THIS IN
 THE CALCULATIONS. TABLE 106.2 & TABLE
 1106.6. INDICATE PITCH OF GUTTER, AND
 SHOW WHERE THE PITCH TO EACH DOWNSPOUT
 STARTS.
 7) DOWNSPOUTS SHALL TERMINATE A MINIMUM
 OF 1' FROM BLDG WALL. SEC 1503.4.4
 8) SHT A1.2 SHOWS ROOF DRAIN ON RIGHT
 SIDE OF LOWER ROOF. IT STATES SEE MECH.
 DRAWINGS. UNABLE TO LOCATE ON MECH.
 DRAWINGS. PLEASE CLAIRFY.
 9) SHT MEP2.4 PLUMBING NOTES #16, SEPAR-
 ATE PERMIT/PLANS REQD. FOR GAS. 104.1.1
 10) SHT MEP3.0 WATER HEATER IN LOUNGE TO
 BE ACCESSIBLE. SEC 501.4 - SUBMIT DETAIL
 11) SHT MEP3.0 SANT RISER DIAGRAM, ONLY
 FIXTURES FROM THE BATHROOM GROUP SHALL
 DRAIN THROUGH THE HORIZONTAL WET VENT.
 SEC 909.1 - 1ST FLOOR KIT. SINK, SECOND
 FLOOR LOUNGE, & SECOND FLOOR BATHROOM
 SHALL ALL TIE IN DOWNSTREAM OF WET VENT.
 12) SHT MEP3.0 WATER RISER DIAGRAM, 1ST
 FLOOR W/C AND LAV NOT SHOWN ON RISER.
 HOSE BIBB IN ELECTRIC ROOM? PLEASE
 CLAIRFY. IF H.B. IS FOR GROUND A HARD
 CAP IS SUGGESTED. NO SUPPLY TO H.B. IS
 SHOWN ON RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 3 Status P Date 2003-09-09 Cont ID  
Sent By sgraham Date 2003-09-09 Time 09:38 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-09-09 00:00:00PROVISO: S/W EASEMENT MUST BE SUBMITTED
 BEFORE C/O ISSUED.

Review Stop Z ZONING
Rev No 2 Status F Date 2003-09-08 Cont ID  
Sent By sgraham Date 2003-09-08 Time 08:48 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-09-08 00:00:00DENIED, NEED INFORMAL SITE REVIEW
 CALLED 9-8-2003

Review Stop Z ZONING
Rev No 1 Status F Date 2003-05-16 Cont ID  
Sent By csiegber Date 2003-09-03 Time 12:22 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-05-16 00:00:005/16/03 DENIED NEED EASEMENT (1) INFO MM
2003-05-12 00:00:00DENIED, NEED EASEMENT INFORMATION