Plan Review Details - Permit 03050237
Plan Review Stops For Permit 03050237
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-11-04 Time 09:12 Rev Time 0.00
Received By hpiskura Date 2003-09-17 Time 11:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-22 Cont ID  
Sent By hpiskura Date 2003-07-22 Time 13:59 Rev Time 0.00
Received By hpiskura Date 2003-07-22 Time 13:59 Sent To  
Notes
2003-07-22 00:00:00SEVERAL ITEMS ON THE 6/18/03 COMMENT
 LIST HAVE NOT BEEN ADDRESSED.
  
 SEE FBC 104.3.1.1 AND FBC 1606.1.7 FOR
 MINIMUM INFORMATION REQUIRED FOR PLAN
 REVIEW.INCLUDE THE IMPORTANCE FACTOR.
  
 PLEASE PROVIDE A DETAIL FOR THE
 INSTALLATION OF THE DOORS AND WINDOWS.
  
 THE SPECIFICATIONS AS PREVIOUSLY NOTED
 STILL PROVIDE FOR UNFORMED FOOTINGS AND
 MISSILE IMPACT TESTING TO 12-97.
  
 THE EMERGENCY ESCAPE WINDOW INFORMATION
 HAS NOT BEEN PROVIDED.FBC 1005.4
  
 INFORMATION ON THE INSULATION IS NOT
 CLEAR.THE SPECIFICATIONS CITE SEVERAL
 MATERIALS BUT NO R VALUE.SEE FBC
 13-400.
  
 IMPACT FEES MUST BE PAID TO THE COUNTY B
 EFORE A PERMIT MAY BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-18 Cont ID  
Sent By hpiskura Date 2003-06-18 Time 16:21 Rev Time 0.00
Received By hpiskura Date 2003-06-18 Time 15:20 Sent To  
Notes
2003-06-18 00:00:00PLEASE PROVIDE A SURVEY/SITE PLAN
 LOCATING THE PROPOSED BUILDING ON THE
 PROPERTY.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 PROVIDE A CONSTRUCTION DETAIL FOR THE
 ATTACHMENT OF THE WINDOWS AND DOORS TO
 THE BUILDING.FBC 104.2.
  
 SPECIFY THE TYPE OF INSULATION IN THE
 WALLS AND CEILING.FBC 13-400.
  
 NOTE THE EMERGENCY ESCAPE WINDOW IN THE
 SLEEPING ROOM.FBC 1005.4.
  
 THE SPECIFICATIONS SECTION 03100-2 OMITS
 FOOTING FORMS.FORMS ARE REQUIRED BY
 CITY AMENDMENT TO FBC 1804.1.1.PLEASE
 REVISE AS NECESSARY.
  
 SECTION 08163-2 OF THE SPECIFICATIONS
 CITES SSTD 12-97, THE FBC INVOKES SSTD
 12-99.
  
 THE LANDING AT THE ENTRANCE IS REQUIRED
 TO BE LEVEL FOR HC ACCESSIBILITY AND
 EGRESS REQUIREMENTS.SEE FBC 1012.1.3
 AND 11-4.8.4.
  
 IT WOULD BE HELPFUL TO COLLATE THE
 PLANS TOGETHER AND PROVIDE A BINDING
 FOR THE SPECIFICATIONS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-06 Cont ID  
Sent By dpalmer Date 2003-11-06 Time 13:22 Rev Time 0.50
Received By dpalmer Date 2003-11-06 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-23 Cont ID  
Sent By csiegber Date 2003-11-04 Time 09:09 Rev Time 0.50
Received By dpalmer Date 2003-07-23 Time 09:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-12 Cont ID  
Sent By dpalmer Date 2003-05-12 Time 10:07 Rev Time 0.50
Received By dpalmer Date 2003-05-12 Time 10:07 Sent To  
Notes
2003-05-12 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR COMMERCIAL USE. 220-3,220-11,220-11,
 220-13 ETC AND ALL CONTINUOUS LOADS AT
 125%. 215-3/230-42
  
 PLEASE SEE FIRE PLAN REVIEW, FOR ANY
 COMMENTS THAT MAY AFFECT ELECTRICAL
 PLANS. IE, EM LT AND EX LTS? 700-12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE TAKE OUT OLD/VOIDED SHEETS AND
 INSERT NEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-07-21 Cont ID  
Sent By mamini Date 2003-07-21 Time 09:17 Rev Time 1.00
Received By mamini Date 2003-07-21 Time 09:16 Sent To  
Notes
2003-07-21 00:00:00PASSED WITH PROVISOS:
 1. PLEASE NOTE THAT SEPTIC TANK AS
 PROPOSED IS NOT ALLOWED, INSTEAD INSTALL
 HOLDING TANK. PERMIT FROM HEALTH DEPT.
 IS REQUIRED.
 2. ALL PARKING STALLS MUST BE PAINTED
 WITH DOUBLE 4" WIDE STRIPES.
 3. A G.V. ON PROPOSED 1" WATER LINE IS
 RECOMMENDED.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-06-18 Cont ID  
Sent By hpiskura Date 2003-06-18 Time 16:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-17 Cont ID  
Sent By mcarsill Date 2003-09-17 Time 17:28 Rev Time 0.00
Received By mcarsill Date 2003-09-17 Time 17:28 Sent To  
Notes
2003-09-17 00:00:001) EXIT SIGNS AND EMERGENCY LIGHTS
 ARE REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-23 Cont ID  
Sent By mcarsill Date 2003-07-23 Time 17:40 Rev Time 0.00
Received By mcarsill Date 2003-07-23 Time 17:40 Sent To  
Notes
2003-07-23 00:00:001) PLEASE INDICATE IN WRITING HOW
 LONG THE SALES TRAILER WILL BE
 LOCATED AT THE SITE.
  
 2) PLEASE INDICATE LOCATION OF THE
 NEAREST FIRE HYDRANT TO THE TRAILER.
  
 3) PLEASE INDICATE EXIT SIGN(S) OR
 EMERGENCY LIGHTING.
  
 4) ANY FIRE EXTINGUISHERS PLANNED. AT
 LEAST ONE WILL BE REQUIRED.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 6) BEDROOM? SMOKE DETECTORS?
  
 7) IN THE EVENT OF AN EMERGENCY OR
 PARAMEDICAL RESPONSE, HOW WILL THE
 BUILDING BE IDENTIFIED FROM THE OTHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-11-04 Time 09:12 Rev Time 0.00
Received By csiegber Date 2003-11-04 Time 09:12 Sent To B
Notes
2003-11-04 00:00:00TO HP DESK/SUBMITTAL-13C-02-13125

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-11-04 Time 09:09 Rev Time 0.00
Received By csiegber Date 2003-11-04 Time 09:09 Sent To E
Notes
2003-11-04 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 13:59 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 13:59 Sent To B
Notes
2003-10-03 00:00:00TO HP DESK/SUB DOOR & FRAME/WINDOW & SLI
 DER DATA/CALCS/DOOR HARDWARE DATA/

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-09-12 Cont ID  
Sent By mmclean Date 2003-09-19 Time 11:47 Rev Time 0.00
Received By csiegber Date 2003-09-12 Time 14:36 Sent To  
Notes
2003-09-12 00:00:00COMM BD #40

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-02 Cont ID  
Sent By csiegber Date 2003-09-12 Time 10:15 Rev Time 0.00
Received By csiegber Date 2003-09-02 Time 16:09 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-18 Cont ID  
Sent By shernand Date 2003-07-18 Time 08:30 Rev Time 0.00
Received By shernand Date 2003-07-18 Time 08:30 Sent To  
Notes
2003-07-18 00:00:00COMM BOARD #54

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-16 Cont ID  
Sent By shernand Date 2003-05-16 Time 11:51 Rev Time 0.00
Received By shernand Date 2003-05-16 Time 11:51 Sent To  
Notes
2003-05-16 00:00:00ADDED A SUBMITTAL TO BOX #60, SAYS SHEET
 A-201 WAS OMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 15:35 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 15:35 Sent To  
Notes
2003-05-05 00:00:00COMM BOARD #60

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-26 Cont ID  
Sent By pkrauss Date 2003-07-26 Time 10:02 Rev Time 0.55
Received By pkrauss Date 2003-07-26 Time 09:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-06-06 Cont ID  
Sent By pkrauss Date 2003-06-06 Time 14:45 Rev Time 0.40
Received By pkrauss Date 2003-06-06 Time 14:41 Sent To  
Notes
2003-06-06 00:00:00DENIED:
  
 1.THE "TRACE LOAD 700" CALCS DO NOT
 MATCH THE ENERGY CALCS OR THE EQUIPMENT
 SCHEDULE.PLEASE REVISE.
  
 2.RETURN OR TRANSFER AIR REQUIRED FROM
 THE DEN AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-10-01 Cont ID  
Sent By kstevens Date 2003-10-01 Time 11:41 Rev Time 0.33
Received By kstevens Date 2003-10-01 Time 11:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-07-26 Cont ID  
Sent By kstevens Date 2003-07-26 Time 07:52 Rev Time 0.75
Received By kstevens Date 2003-07-26 Time 07:52 Sent To  
Notes
2003-07-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 CITY WPB CODE
  
 1) SECTION 90-123(D) WHERE SEWERS ARE
 AVAILABLE IT IS REQUIRED TO CONNECT TO
 SANITARY SEWER. THE CITY COMMISION IS
 AUTHORIZED TO GRANT VARIANCES TO THIS
 REQUIREMENT. (SEE ATTACHED SHEET)
 2) GRAB BARS NOT LOCATED IN STALLS SHALL
 COMPLY WITH 11-4.26 AND FIGURE #29. THE
 GRAB BAR BEHIND THE WATER CLOSET SHALL
 BE 36" MINIMUM. 42" MINIMUM FOR SIDE
 GRAB BAR. SHEET 301
 3) SHT 301 DETAIL #3, HEIGHT FOR SINK
 SHALL BE 34" PER 11-4.24.2. SHOW ON DE-
 TAIL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-06 Cont ID  
Sent By kstevens Date 2003-06-06 Time 09:51 Rev Time 0.50
Received By kstevens Date 2003-06-06 Time 09:51 Sent To  
Notes
2003-06-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2.01 TOILET ROOM IN SALES OFF-
 ICE SHALL COMPLY WITH SECTION 11-4.22
 AND ALL SUBSECTIONS. PLEASE SUBMIT A
 DETAIL. 11-4.1.3(11)
 2) SHT A-2.01 KIT SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECIONS.
 PLEASE SUBMIT A DETAIL. SINK SHALL BE
 CENTERED ON THE 48" OF THE 30X48 CLEAR
 FLOOR SPACE FOR PARRALEL APPROACH.
 3) SHT A-2.01 A DRINKING FOUNTAIN IS RE-
 QUIRED PER TABLE 403.1. ALSO SEE SECTION
 410.1.
 4) SHT P-101 SANT. RISER DIAGRAM, KIT.
 SINK SHALL NOT DRAIN INTO THE WET VENT
 OF THE BATHROOM FIXTURES. SECTION 909.1
 SINK SHALL TIE IN DOWNSTREAM OF THE BATH
 ROOM FIXTURES.
 5) SHT P-101 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DE-
 LEATE FROM RISER. SECTION 604.9
 6) SHT A-2.01 IS MISLABLED AS STORAGE
 BLDG FLOOR PLAN/ELEVATIONS/REFLECTED
 CEILING PLANS ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 2 Status P Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-12 Time 10:15 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-09-19 00:00:009/19/03 OK PER JOSH LONG FORMAL SITE
 PLAN REVIEW PB# 1248G MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-06-16 Cont ID  
Sent By csiegber Date 2003-09-02 Time 16:09 Rev Time 1.00
Received By sgraham Date   Time   Sent To  
Notes
2003-06-16 00:00:006/13/03 WAITING FOR CITY COMMISSION
 APPROVAL MM