Plan Review Details - Permit 03050231
Plan Review Stops For Permit 03050231
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-06-17 Cont ID  
Sent By shill Date 2004-06-17 Time 10:57 Rev Time 0.25
Received By shill Date 2004-06-17 Time 10:57 Sent To  
Notes
2004-06-17 00:00:00CONCRETE SPECS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-06-11 Time 09:07 Rev Time 2.00
Received By shill Date 2004-03-26 Time 12:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-03-17 Time 16:15 Rev Time 2.00
Received By shill Date 2004-02-06 Time 15:17 Sent To  
Notes
2004-02-06 00:00:00*****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE THE ENGINEERING FOR THE
 METAL BUILDING.
  
 2.)ANY PRODUCT APPROVALS REQUIRED BUT
 NOT SUBMITTED BEFORE ISSUANCE WILL
 REQUIRE SEPARATE PERMITS WITH ADDITIONAL
 FEES.
  
 3.)THE PRINTED NAME AND LICENSE NUMBER
 OF THE PERSON SEALING THE DOCUMENT IS
 REQUIRED TO BE ON THE PLAN (ARCHITECT),
 FAC61G1-16.004.
  
 4.)THE PRINTED NAME AND LICENSE NUMBER
 OF THE PERSON SEALING THE DOCUMENT IS
 REQUIRED TO BE ON THE PLAN (ENGINEER),
 FAC61G15-23.002.
  
 5.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATON.233-5025
  
 6.)ADDITIONAL PERMITS REQUIRED.
  
 7.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 **NO RESUB FEE PER LM/SMH**

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-18 Cont ID  
Sent By hpiskura Date 2003-06-18 Time 15:00 Rev Time 0.00
Received By hpiskura Date 2003-06-18 Time 12:54 Sent To  
Notes
2003-06-18 00:00:00PLEASE PROVIDE A SITE/PLAN SURVEY WITH
 DIMENSIONS LOCATING THE PROPOSED
 BUILDING ON THE SITE.FBC 104.2.
  
 SPECIFY THE INSULATION TO BE USED IN
 WALLS AND CEILING.SEE FBC 13-400.
  
 DESCRIBE THE NATURE AND QUANTITIES OF
 THE COMMODITIES TO BE STORED IN THE
 BUILDING.SEE FBC 312.2.
  
 PLEASE INDICATE THE DESIGN PRESSURES FOR
 THE COMPONENTS AND CLADDINGS, (ROOF
 COVERING, DOORS AND WINDOWS) SEE FBC
 1606.1.7.
  
 THIS BUILDING MAY BE SUBJECT TO IMPACT
 FEES COLLECTED BY PALM BEACH COUNTY.
 THE PERMIT PLANS MUST BE STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-253-5025 FOR
 MORE INFORMATION.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-22 Cont ID  
Sent By dpalmer Date 2004-04-22 Time 11:12 Rev Time 0.33
Received By dpalmer Date 2004-04-22 Time 11:12 Sent To  
Notes
2004-04-22 00:00:00REV ELEC SITE PLAN ONLY

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-04-16 Time 14:39 Rev Time 0.50
Received By dpalmer Date 2004-01-27 Time 16:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-12 Cont ID  
Sent By dpalmer Date 2003-05-12 Time 11:52 Rev Time 0.50
Received By dpalmer Date 2003-05-12 Time 11:51 Sent To  
Notes
2003-05-12 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215-3/230-42 ETC
  
 2)NOTE: PLEASE SHOW/ INCLUDE BLDG FOOTER
 STEEL AND ANY COLD WATER AS PART OF THE
 GROUNDING AT DEATCHED BLDG. 250-31 AND
 250-50
  
 PLEASE ALSO SEE ANY FIRE REVIEW COMMENTS
 THAT MAY AFFECT ELECTRICAL PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-05-07 Cont ID  
Sent By mamini Date 2003-05-07 Time 11:06 Rev Time 1.00
Received By mamini Date 2003-05-07 Time 11:06 Sent To  
Notes
2003-05-07 00:00:00PASSED WITH PROVISOS:
 1. A BACKFLOW PREVENTER INTALLATION IN
 WATER SERVICE WILL BE REQUIRED.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By mcarsill Date 2004-01-22 Time 16:21 Rev Time 0.00
Received By mcarsill Date 2004-01-22 Time 16:21 Sent To  
Notes
2004-01-22 00:00:001) RESPONSE MEMORANDUM FROM OWNER
 IS NOT CORRECT. ACCORDING TO STORAGE
 LIST, COMBUSTIBLES WILL BE PRESENT
 IN THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-10 Cont ID  
Sent By nmccray Date 2003-06-10 Time 10:54 Rev Time 0.00
Received By nmccray Date 2003-06-10 Time 10:54 Sent To  
Notes
2003-06-10 00:00:001) THIS MUST COMPLY WITH NFPA 101 LIFE
 SAFETY CODE 2000 EDITION CHAPTER 42.
  
 2) WHAT WILL BE STORED IN THIS STRUCTURE
 WHAT WILL THE CONTENTS BE CLASSIFIED AS,
 LOW HAZARD, ORDINARY HAZARD, OR HIGH
 HAZARD.
  
 3) HOW MANY PERSONS WILL BE IN THIS
 STRUCTURE.
  
 4) STORAGE BAY # 1 HAVE A OVERHEAD DOOR,
 WILL THERE BE A VEHICLE STORED IN THIS
 BAY.
  
 5) WILL THIS STRUCTURE BE FIRE SPRINKLER
 PROTECTED.
  
 6) PLAN DOES NOT SHOW EXIT SIGNS.
  
 7) STORAGE OCCUPANCIES ARE REQUIRED TO
 HAVE AT LEAST TWO MEANS OF EGRESS UNLESS
 IT MEET EXCEPTION OF CHAPTER 42.
  
 8) WHAT IS THE INTERIOR WALL AND CEILING
 FINISH CLASSIFICATION. ( CLASS A, CLASS
 B, OR CLASS C ).
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 09:07 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 09:07 Sent To B
Notes
2004-06-11 00:00:00TO SH DESK/SUBMITTAL/STORAGE BLDG
 MIX DESIGN

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 14:39 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 14:39 Sent To E
Notes
2004-04-16 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-17 Cont ID  
Sent By csiegber Date 2004-03-17 Time 16:15 Rev Time 0.00
Received By csiegber Date 2004-03-17 Time 16:15 Sent To B
Notes
2004-03-17 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 16:48 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 16:48 Sent To  
Notes
2004-01-20 00:00:00TO COMM BD#45

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 16:00 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 15:54 Sent To  
Notes
2003-05-05 00:00:00COMM BOARD #60

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-30 Cont ID  
Sent By pkrauss Date 2004-01-30 Time 16:15 Rev Time 0.40
Received By pkrauss Date 2004-01-30 Time 16:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-06-06 Cont ID  
Sent By pkrauss Date 2003-06-06 Time 14:07 Rev Time 0.50
Received By pkrauss Date 2003-06-06 Time 14:00 Sent To  
Notes
2003-06-06 00:00:00DENIED:
 PLEASE NOTE 1 SET OF PLANS MISSING M-1,
 E-001 & E-201.
  
 1.PLEASE INDICATE WHAT TYPE OF
 MAINTENANCE WILL BE DONE. (REPAIR GARAGE
 FOR AUTOMOBILES, LAWN EQUIPMENT, ETC.)
  
 2.WHAT WILL BE STORED IN THE STORAGE
 AREAS?(COMBUSTIBLES?)
  
 3.LOAD CALCS INDICATE COOLING AIRFLOW
 OF 2,089 CFM WHEREAS PLAN INDICATES ONLY
 1435 CFM, WILL THE EQUIPMENT HAVE THE
 CAPACITY TO PRODUCE 2,089 CFM.ENERGY
 CALCS INDIATE A 57,300 TOTAL BTU SYSTEM
 WHICH CONFLICT WITH WHAT IS REFLECTED ON
 THE M-1 PLAN.PLEASE CLARIFY.
  
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-01-28 Cont ID  
Sent By kstevens Date 2004-01-28 Time 18:19 Rev Time 0.33
Received By kstevens Date 2004-01-28 Time 18:19 Sent To  
Notes
2004-01-28 00:00:00NO PLUMBING PLANS SUBMITTED - NO PLUMB-
 ING REQUIRED IN STORAGE FACILITY IF FAC-
 ILITY W/IN 500' OF TOILET FACILITIES PER
 EXCEPTION OF SECTION 403.4

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-06 Cont ID  
Sent By kstevens Date 2003-06-06 Time 09:17 Rev Time 0.25
Received By kstevens Date 2003-06-06 Time 09:17 Sent To  
Notes
2003-06-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) TABLE 403.1 REQUIRES 1 EACH - WATER
 CLOSET, LAV, DRINKING FOUNTAIN, & SERV-
 ICE SINK.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-16 Cont ID  
Sent By sgraham Date 2003-06-16 Time 15:34 Rev Time 1.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***