Plan Review Details - Permit 03042840
Plan Review Stops For Permit 03042840
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-22 Cont ID  
Sent By lsmith Date 2003-05-22 Time 07:47 Rev Time 0.50
Received By lsmith Date   Time   Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 16:57 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2003-05-21 00:00:00NEED ANCHORING DETAIL FOR EQUIPMENT,
 NEED ORIGINAL SIGNATURE ON ENGINEER
 RAISED SEAL. SEE ELEC & PLUMBING
 COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-22 Cont ID  
Sent By btrobaug Date 2003-05-22 Time 10:21 Rev Time 0.33
Received By btrobaug Date 2003-05-22 Time 10:16 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-08 Cont ID  
Sent By lsmith Date 2003-05-22 Time 07:48 Rev Time 0.25
Received By dpalmer Date 2003-05-08 Time 07:36 Sent To P
Notes
2003-05-08 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE WIRING DIAGRAM
 WITH POOL/EQUIPMENT DATA LISTINGS.
 PLEASE SHOW ALL WIRING TO ALL EQUIPMENT,
 INCLUDING PUMPS/ HEATERS ETC.
  
 2)NOTE: PLEASE SUBMIT POOL HEATER SPECS
 SEE PLUMB REVIEW COMMENTS.
  
 PLEASE SUBMIIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 16:57 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 16:57 Sent To B
Notes
2003-05-21 00:00:00LSMITH DESK, RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-30 Time 14:51 Rev Time 0.00
Received By shernand Date 2003-04-30 Time 14:51 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-24 Cont ID  
Sent By kstevens Date 2003-05-24 Time 18:28 Rev Time 0.75
Received By kstevens Date 2003-05-24 Time 18:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-19 Cont ID  
Sent By btrobaug Date 2003-05-22 Time 10:22 Rev Time 0.50
Received By kstevens Date 2003-05-19 Time 05:43 Sent To B
Notes
2003-05-19 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FLA. STATUTES
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 2) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 3) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 4) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 5) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 6) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 7) PIPING SCHEMATIC DOES NOT REFLECT THE
 POOL LAYOUT. SPA PIPING NOT SHOWN, SPA
 PUMP NOT SHOWN, ONLY ONE SKIMMER SHOWN,
 NO VACUUM LINE SHOWN, NO HEATER SHOWN.
 PLEASE REVISE SCHEMATIC SHOWING ALL
 MISSING EQUIPMENT, PIPING, VALVES, PIPE
 SIZES ECT.
 8) 61G15-23.002(1) THE DATE SEAL AND
 SIGNATURE SHALL BE AFFIXED TO PLANS. NO
 DATE ON SEAL/SIGNATURE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-04-30 Time 14:51 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***