Plan Review Details - Permit 03042700
Plan Review Stops For Permit 03042700
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-18 Cont ID  
Sent By sthyng Date 2003-07-18 Time 11:28 Rev Time 1.50
Received By sthyng Date 2003-07-18 Time 11:28 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-11 Cont ID  
Sent By kstevens Date 2003-07-17 Time 15:33 Rev Time 3.00
Received By sthyng Date 2003-06-11 Time 15:54 Sent To  
Notes
2003-06-11 00:00:00******CORRECTIONS********
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURT BEFORE
 A PERMIT CAN BE ISSUED.
  
 2.)DESIGN INFORMATION IS REQUIRED TO
 BE ON THE PLAN, FBC 1606.1.7, NOT ON
 WIND LOAD CERTIFICATION FORM.
  
 3.)BEDROOMS ARE REQUIRED TO HAVE
 EMERGENCY EGRESS FBC 1005.4.A 24 S/H
 WINDOW DOES NOT MEET THE HEIGHT
 REQUIREMENT.
  
 4.)SAFETY GLASS REQUIRED FOR THE
 WINDOWS AT THE TUB AND SHOWER,FBC2405.2.
 NOTE ON FLOOR PLAN.
  
 5.)SPECIFY MATERIAL AND ATTACHMENTS
 FOR PORCH CEILING.
  
 6.)WALL SECTON SHOWS R3 INSULATION
 ON WALLS, ENERGY CALC SHOWS 4.2.
  
 7.)UPLIFT SPECIFIED FOR ATTACHMENTS
 EXCEED PRODUCT LIMITATIONS, SEE
 ATTACHED.REVISE; DO NOT INCLUDE
 STRESS INCREASE FOR STEEL; USE 2003
 CATALOGS.
  
 8.)ADDITIONAL FEES REQUIRED.
  
 9.)SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE DOUBLE FRENCH DOORS
 AND THE WINDOW MULLIONS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-14 Cont ID  
Sent By csiegber Date 2003-10-09 Time 16:26 Rev Time 0.50
Received By btrobaug Date 2003-07-14 Time 09:43 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-07-11 Time 11:08 Rev Time 0.50
Received By btrobaug Date 2003-05-14 Time 09:58 Sent To P
Notes
2003-05-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE SHOW THE GROUNDING ELECTRODE
 SYSTEM IN COMPLIANCE WITH 250-50(A,B &
 C)
  
 3} THE CALCULATION FOR THE A/C SYSTEM ON
 THE PANEL SCHEDULE AND THE LOAD CALC'S
 DO NOT CORRELATE.
  
 4} THE SMALL APPLIANCE CIRCUITS MUST BE
 CALCULATED @ 1500 VA.EA PER 220-16(A).
  
 5} THERE IS ONLY ONE GENERAL LIGHTING
 CIRCUIT ON THE PANEL SCHEDULE.THERE
 MUST BE A MINIMUM OF THREE @ 15AMPS.
  
 6} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PER 8-1.4.2,NFPA-72.
  
 8} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 16:25 Rev Time 0.00
Received By csiegber Date 2003-10-09 Time 16:25 Sent To E
Notes
2003-10-09 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 11:08 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 11:08 Sent To E
Notes
2003-07-11 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-29 Cont ID  
Sent By shernand Date 2003-04-29 Time 14:45 Rev Time 0.00
Received By shernand Date 2003-04-29 Time 14:45 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-10-16 Cont ID  
Sent By pkrauss Date 2003-10-16 Time 08:01 Rev Time 0.20
Received By pkrauss Date 2003-10-16 Time 07:58 Sent To  
Notes
2003-10-16 00:00:00SEE COMMENTS DATED 7-18-03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-16 Cont ID  
Sent By pkrauss Date 2003-07-18 Time 15:27 Rev Time 0.25
Received By pkrauss Date 2003-07-18 Time 15:21 Sent To  
Notes
2003-10-16 00:00:00PROVISO:
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 PLEASE SIZE RETURN AIR AS TO THE
 BEDROOM AREAS AS FOLLOWS:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By sthyng Date 2003-07-18 Time 11:29 Rev Time 0.25
Received By pkrauss Date 2003-06-04 Time 08:04 Sent To B
Notes
2003-06-04 00:00:00MECHANICAL PERMIT 03042711
 PLANS APPROVED ON 5-24-03

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By kstevens Date 2003-07-17 Time 15:32 Rev Time 0.25
Received By kstevens Date 2003-07-17 Time 15:32 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-17 Cont ID  
Sent By btrobaug Date 2003-07-14 Time 10:22 Rev Time 0.25
Received By kstevens Date 2003-05-17 Time 09:36 Sent To M
Notes
2003-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. KITCHEN SINK NOT
 VENTED. - SHOWER & TUB IS NOT VENTED,
 (SEE RED LINE CORRECTIONS), PLEASE SHOW
 ALL PIPE SIZES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-29 Time 14:45 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***