Plan Review Details - Permit 03042304
Plan Review Stops For Permit 03042304
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By jgomez Date 2003-07-17 Time 18:11 Rev Time 2.50
Received By jgomez Date 2003-07-17 Time 18:11 Sent To PC
Notes
2003-07-17 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-NEED TO AMEND DECLARATION OF COVENANTS
 TO SPECIFICALLY INCLUDE THE WORDS
 "EGRESS EASEMENT" AT ZERO LOT SIDE AS
 REQUIRED BY THE BUILDING OFFICIAL.
 PROVIDE SUCH DOCUMENT PRIOR TO FIRST
 ROUGH INSPECTION TO AVOID ANY DELAYS
 IN CONSTRUCTION AND C.O.
 2-PROVIDE ORIGINAL LETTER WITH ORIGINAL
 SEAL, SIGNATURE AND ENGINEER'S INFO.
 FOR GLASS BLOCK LETTER AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITING DOCUMENTS FOR PUBLIC RECORDS
 3-STORM PANELS:A)SOME PANELS EXCEED
 THE MAXIMUM SPAN ALLOWED IN ENGINEERED
 DRAWINGS. REVISE INSTALLATION SCHEDULE
 AS REQUIRED.
 B)STORM PANELS ENGINEER IS LIMITING THE
 DRAWINGS TO BE FOR ONE PERMIT ONLY.
 NEED ORIGINAL DRAWINGS AS REQUIRED BY
 THE ENGINEER.
 4-UPDATE THE TRUSS ANCHOR SCHEDULE.
 SEE SIMPSON HIGH WIND-RESISTANT
 CONSTRUCTION CALTALOGUE WHICH IS THE
 ONLY SIMPSON CATALOGUE REVISED TO MEET
 SEC. 1609.4.3 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-03 Cont ID  
Sent By pkrauss Date 2003-07-15 Time 08:49 Rev Time 3.50
Received By jgomez Date 2003-06-03 Time 11:05 Sent To  
Notes
2003-06-03 00:00:00BULDING REVIEW CHECKLIST:
 1-REVISE ENERGY CALCULATIONS: A)A/C AREA
 DON'T MATCH ARCHITECT'S DRAWINGS.
 B)INSULATION SPECIFIED ON EXTERIOR CONC.
 BLOCK WALL DOESN'T MATCH ARCHITECT'S
 PLANS. REVISE EITHER ONE AS REQUIRED.
 C)COMPLETE ALL INFORMATION ON TOP OF
 FORM. EG: OWNER, ETC.
 D)PROVIDE ORIGINAL SIGNATURES ON BOTTOM
 OF FORM. SEC. 103.0 CHAPTER 13 FBC/01.
  
 2-SOIL TEST REPORT PROVIDED IS FOR LOT
 21. THIS IS LOT 4. REVISE AS REQ'D.
 3-IF EGRESS FROM BEDROOM IS THRU ZERO
 LOT WALL, THEN NEED RECORDED PLAT
 SHOWING EASEMENT TO ALLOW FOR EGRESS
 THRU NEIGHBOR'S PROPERTY AS REQUIRED
 BY THE BUILDING OFFICIAL.
 4-PROVIDE SPECS FOR WWM SUPPORTS IN CONC
 SLAB. SEE SEC. 1909.3 FBC 2001.
 5-GLASS BLOCK BY TUB AREA TO BE SAFETY
 GLASS IF FACE THICKNESS IS LESS THAN
 0.25". SEE SEC. 2405.2 FBC 2001.
 6-ENERGY CALCULATIONS TAKE THE CEILING
 FAN CREDIT, THEN, SPECIFY SIZE AND #
 OF CEILING FANS IN ALL ROOMS AS REQ'D
 BY TABLE 6-6 CHAPTER 13 FBC 2001.
 **NOTE: WHEN TAKING THIS CREDIT, CEILING
 FANS SHALL BE INSTALLED. THEY ARE NOT
 OPTIONAL AS CALLED FOR DEN ROOM.
 7-STORM PANELS EXCEED THE MAXIMUM PANEL
 SPAN ALLOWED BY TABLE 1 OF ENGINEERED
 DRAWINGS ACCORDING TO THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER
 OF RECORD. REVISE INSTALLATION SCHED.
 AS REQUIRED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 8-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 ENTRY DOORS AS REQUIRED BY THE PRODUCT
 APPROVAL SUBMITTED.
 9-OWES $38.46 FOR UPDATED VALUATION AND
 RADON FEES.
 10-UPDATE THE TRUSS ANCHOR SCHEDULE AND
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC 2001, WHICH DOES NOT
 ALLOW THE 33% INCREASE IN THE ALLOWA-
 BLE STRESS OF THE STEEL.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-16 Cont ID  
Sent By mmclean Date 2003-05-14 Time 15:19 Rev Time 0.25
Received By dpalmer Date 2003-05-16 Time 17:48 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 11:07 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 11:07 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-29 Cont ID  
Sent By shernand Date 2003-04-29 Time 08:45 Rev Time 0.00
Received By shernand Date 2003-04-29 Time 08:45 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-15 Cont ID  
Sent By pkrauss Date 2003-07-15 Time 08:49 Rev Time 0.25
Received By pkrauss Date 2003-07-15 Time 08:49 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-07-11 Time 11:07 Rev Time 0.25
Received By pkrauss Date 2003-05-28 Time 14:48 Sent To  
Notes
2003-05-28 00:00:00DENIED:MECHANICAL PERMIT 03042346
  
 PLEASE PROVIDE MANUAL J CALCULATIONS AS
 PER 2001 FBC CHAPTER 13 SECTION 607
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-17 Cont ID  
Sent By dpalmer Date 2003-05-16 Time 17:48 Rev Time 0.33
Received By kstevens Date 2003-05-17 Time 09:19 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-04-29 Time 08:45 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved