Plan Review Details - Permit 03042078
Plan Review Stops For Permit 03042078
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2003-07-01 Cont ID  
Sent By sthyng Date 2003-07-01 Time 10:44 Rev Time 1.50
Received By sthyng Date 2003-07-01 Time 10:44 Sent To  
Notes
2003-07-01 00:00:00********CORRECTIONS********
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE THE PREVIOUS CORRECTIONS
 REGARDING THE ATTACHMENT OF THE NEW SLAB
 TO THE EXISTING.THE EMBEDMENT LENGTH
 IS STILL NOT ON THE PLAN.AGAIN, I
 HAVE CIRCLED THE DETAIL SO THAT YOU
 CORRECT THE RIGHT ONE.
  
 2.)SEE THE CORRECTION NOTE #5 DATED
 6/12/3.I HAD A CONVERSATION WITH THE
 DESIGNER EXPLAINING THIS CORRECTION.HE
 INDICATED THAT HE UNDERSTOOD THE
 CORRECTION.IT IS NOT CHANGED ON THE
 PLAN.THE R VALUE SPECIFIED ON THE
 PLAN IN NOT CONSISTENT WITH THE
 MINIMUMS SPECIFIED ON THE ENERGY CALC.
 I HAVE CIRCLED THE INCORRECT RVALUE ON
 THE PLAN.
  
 3.)THE PRODUCT APPROVALS FOR THE
 HURRICANE SHUTTERS ARE ILLEGIBLE.
  
 4.)PROVIDE A HURRICANE SHUTTER
 ANCHORING SCHEDULE, SEE ATTACHED.
  
 5.)SHOW THE DIMENSIONS ABOVE & BELOW
 GRADE FOR THE FOOTER, CBS WALL SECTION.
  
 6.)THE WINDOW PRODUCT APPROVALS ARE
 INCOMPLETE.SUBMIT TWO COMPLETE COPIES.
  
 7.)ADDITIONS OVER 25% MUST COMPLY
 WITH FBC3401.7.1.2.SHOW, FOR THE
 EXISTING HOUSE, THE FOLLOWING:
 EMERGENCY EGRESS FOR BEDROOMS,FBC1005.4
 SMOKE DETECTORS FOR BEDROOMS,FBC905.2.2
 BATHROOM TO COMPLY WITH FBC11-11(1)
 FRONT DOOR TO COMPLY WITH 1004
  
 8.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status   Date 2003-07-01 Cont ID  
Sent By sthyng Date 2003-07-01 Time 09:57 Rev Time 1.00
Received By sthyng Date 2003-07-01 Time 09:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-06-23 Cont ID  
Sent By shernand Date 2003-07-01 Time 09:36 Rev Time 0.50
Received By sthyng Date 2003-06-23 Time 12:51 Sent To  
Notes
2003-06-23 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ONLY ENERGY CALCS WERE SUBMITTED.
 THE PLANS MUST BE SUBMITTED WITH THE
 ENERGY CALCS, WITH ALL CORRECTIONS
 FROM THE PREVIOUS CORRECTION LIST
 MADE TO THE PLAN.
  
 2.)ALL PREVIOUS CORRECTIONS MUST
 BE MADE TO THE PLAN, OR A 4X FEE WILL
 BE ASSESSED.SEE ATTACHED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-20 Time 15:13 Rev Time 1.00
Received By sthyng Date 2003-06-12 Time 19:17 Sent To  
Notes
2003-06-12 00:00:00*******CORRECTIONS********
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE #2 ON FIRST CORRECTION LIST,
 #1 ON 2ND CORRECTION LIST.THIS IS
 THE THIRD REQUEST FOR ENERGY CALCS.A
 PERMIT CANNOT BE ISSUED UNTIL ENERGY
 CALCS ARE SUBMITTED.
  
 2.)SEPARATE PERMITS REQUIRED.
  
 3.)SEE PREVIOUS CORRECTION #3,
 FOR THE ATTACHMENTS OF THE NEW SLAB TO
 THE EXISTING, SHOW THE LENGTH OF THE
 DOWELS AND THE EMBEDMENT.THIS IS
 FOUND ON THE WALL SECTION; I HAVE
 CIRCLED IT SO THAT YOU CHANGE THE
 CORRECT DETAIL.
  
 4.)SEE PREVIOUS CORRECTION #5; STILL
 SHOWS BOTH A 6" AND 8" EMBEDMENT.I
 HAVE MARKED THIS AS WELL.
  
 5.)YOU HAVE SPECIFIED 4.2 FOIL
 INSULATION ON THE WALL.THIS MUST BE
 CONSISTENT WITH THE ENERGY CALCS.IF
 THEY SUBMIT A SHORT FOR ENERGY CALC,
 THE MINIMUM R VALUE FOR A BLOCK WALL
 IS R5.DO NOT RESUBMIT UNTIL YOU HAVE
 SEEN THE ENERGY CALC AND HAVE CONFIRMED
 THAT THE R VALUES STATED ON THE ENERGY
 CALC ARE CONSISTENT WITH OR LESS THAN
 SPECIFIED BY YOUR PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-06-12 Time 16:03 Rev Time 2.00
Received By sthyng Date 2003-06-04 Time 11:13 Sent To  
Notes
2003-06-04 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE #2 ON PREVIOUS CORRECTION
 LIST; ENERGY CALCS REQUIRED.
  
 2.)SEPARATE PERMITS REQUIRED.
  
 3.)FOR THE ATTACHMENTS OF THE NEW
 SLAB TO THE EXISTING, SHOW THE LENGTH
 OF THE DOWELS AND EMBEDMENT.
  
 4.)THE CEILING INSULATION IS TO BE
 R19 MINIMUM (FBC 13-404.1.C).IT WAS
 CORRECT ON THE ORIGINAL PLAN, THEN WAS
 CHANGED TO R11.CORRECTION #5
 REFERRED TO THE WALL INSULATION.
 SPECIFY THE INSULATION R-VALUE FOR THE
 WALLS.
  
 5.)THE NOTE ABOVE THE BEAM PLAN ON THE
 ROOF PLAN SHOWS 6" AND 8" EMBEDMENT.
 CLARIFY.ALSO SAYS "INTO EX. CONC FTG".
 ISN'T THIS FOR THE BEAM, NOT THE
 FOOTING?IT IS ON THE ROOF PLAN.
  
 6.)SEE PREVIOUS CORR. NOTE #7.THE
 SHEATHING SCHEDULE STILL DOES NOT
 COMPLY.
  
 7.)THE ATTACHMENT OF THE NEW FOOTING
 TO EXISTING SHOWS BOTH 6" AND 8"
 EMBEDMENT.CLARIFY.
  
 8.)TWO COPIES OF ALL PRODUCT APPROVALS
 MUST BE SUBMITTED.
  
 9.)THE ROOF PRODUCT APPROVAL IS TO
 RE-COVER AN EXISTING DECK WITH AN
 EXISTING ROOF.YOU MAY SUBMIT THE
 CORRECT PRODUCT APPROVAL NOW OR SUBMIT
 IT WITH THE ROOF PERMIT APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-06-03 Time 13:10 Rev Time 2.50
Received By sthyng Date 2003-05-20 Time 10:50 Sent To  
Notes
2003-05-20 00:00:00*******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IMPACT FEES ARE TO BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025.
  
 2.)ENERGY CALCS REQUIRED FBC13-101.2.
  
 3.)SEPARATE PERMITS REQUIRED (ELECTRIC
 ROOF, MECHANICAL).
  
 4.)IS THE 18 X 16 FOOTER ON THE PLAN
 PROPOSED OR EXISTING?IF IT IS A NEW
 FOOTER, HOW WILL IT TIE INTO THE
 EXISTING SLAB?
  
 5.)SPECIFY INSULATION ON THE PLAN (NOT
 "SEE ENERGY CALC"; ENERGY CALCS NOT
 SUBMITTED).
  
 6.)SOFFIT VENTS MUST COMPLY WITH FBC
 2309.7; CANNOT "MATCH EXISTING". SPECIFY
 SIZE AND SPACING.
  
 7.)ROOF SHEATHING ATTACHMENT DOES NOT
 COMPLY WITH CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC, REVISED TABLE
 2306.1 FOR ZONE 3.
  
 8.)SECTION A A-1 IS LABELED "MAIN
 FLOOR STAIR".REVISE.
  
 9.)PROVIDE WINDOW & DOOR BUCK
 ATTACHMENT DETAILS; REFER TO FBC
 1707.4.4.2.
  
 10.) THE ROOF FRAMING PLAN SPECIFIES
 2X8S, THE WALL SECTION SPECIFIES 2X10S.
  
 11.) TYPICAL INTERIOR PARTITION DETAIL
 REFERS TO AN ANCHOR SCHEDULE NOT ON THE
 PLAN.ALSO IT IS UNCLEAR AS TO WHERE
 THIS PARTITION IS TO BE INSTALLED.
  
 12.)THE BEAM TO ROOF JOIST CONNECTION
 IS INCORRECT.SPECIFY THE CORRECT
 ATTACHMENT WITH CORRECT LANGUAGE AS TO
 HOW IT WILL BE ATTACHED (SIZE AND
 NUMBER).REFER TO THE 2003 CATALOG.
  
 13.)WALL SECTION REFERS TO A3; NOT
 ON PLAN.
  
 14.)ON THE ROOF FRAMING PLAN AND
 FOUNDATION PLAN THERE IS A #5 DOWEL TO
 ATTACH TO EXISTING; HOW LONG?
  
 15.)THE WIND INFORMATION REFERS TO
 TRUSS LOADS; THIS JOB IS USING ROOF
 JOISTS.
  
 16.)CONFIRM THAT TRACO (SINGLE HUNG
 WINDOW PRODUCT APPROVAL SUBMITTED) MAKES
 A 345 SINGLE HUNG WINDOW WITH A CLEAR
 NET OPENING FOR EMERGENCY EGRESS.
  
 17.)IMPACT PROTECTION FOR WINDOWS
 REQUIRED; FBC 1606.1.4.
  
 18.)PROVIDE PRODUCT APPROVALS FOR THE
 IMPACT PROTECTION AND ROOF.
  
 19.)ADDITIONAL FEES REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-07 Cont ID  
Sent By shernand Date 2003-05-06 Time 11:13 Rev Time 0.33
Received By dpalmer Date 2003-05-07 Time 11:26 Sent To B
Notes
2003-05-07 00:00:00************ NOTES REDLINED *********
  
 MISSING SD`S INSIDE AND OUTSIDE BEDROOMS
 NFPA-72 8-1.4.3
  
 MISSING RECEPT PER 210-52
  
 MISSING ARC FAULT PROTECTIN REQ`D FOR
 NEW BEDROOM CIRCUIT.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-07-01 Time 09:36 Rev Time 0.00
Received By shernand Date 2003-07-01 Time 09:36 Sent To B
Notes
2003-07-01 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-20 Time 15:13 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 15:12 Sent To B
Notes
2003-06-20 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 16:03 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 16:03 Sent To B
Notes
2003-06-12 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-03 Cont ID  
Sent By shernand Date 2003-06-03 Time 13:10 Rev Time 0.00
Received By shernand Date 2003-06-03 Time 13:10 Sent To B
Notes
2003-06-03 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-06 Time 11:13 Rev Time 0.00
Received By shernand Date 2003-05-06 Time 11:13 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-30 Cont ID  
Sent By sgraham Date 2003-05-05 Time 09:26 Rev Time 0.00
Received By shernand Date 2003-04-30 Time 14:10 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-28 Cont ID  
Sent By sthyng Date 2003-04-28 Time 12:47 Rev Time 0.00
Received By sthyng Date 2003-04-28 Time 12:47 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-05-05 Cont ID  
Sent By sgraham Date 2003-05-05 Time 09:26 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-30 Time 14:10 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-04-30 00:00:00DENIED, NEED SURVEY