Plan Review Details - Permit 03042053
Plan Review Stops For Permit 03042053
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-05-07 Cont ID  
Sent By sgraham Date 2003-05-07 Time 11:19 Rev Time 0.85
Received By jwitmer Date 2003-05-07 Time 12:55 Sent To  
Notes
2003-05-07 00:00:00MASTER PLAN 02081325 MODEL "D"
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 RE-EVALUATE TRUSS ANCHOR SCHEDULE BEFORE
 ROOF FRAMING INSPECTION.
 JIM WITMER
 (561)805-6715

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-05-07 Cont ID  
Sent By jwitmer Date 2003-05-07 Time 12:56 Rev Time 0.00
Received By jwitmer Date 2003-05-07 Time 12:55 Sent To  
Notes
2003-05-07 00:00:00MASTER PLAN 02081325 MODEL"D"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2003-05-07 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-28 Cont ID  
Sent By sthyng Date 2003-04-28 Time 10:14 Rev Time 0.00
Received By sthyng Date 2003-04-28 Time 10:14 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-23 Cont ID  
Sent By pkrauss Date 2003-05-23 Time 09:12 Rev Time 0.20
Received By pkrauss Date 2003-05-23 Time 09:12 Sent To  
Notes
2003-05-23 00:00:00MECH PERMIT 03042057
 REVISED ENERGY CALCS SEER INCREASED FROM
 10.5 TO 12 SEER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-05-07 Cont ID  
Sent By jwitmer Date 2003-05-07 Time 12:55 Rev Time 0.00
Received By jwitmer Date 2003-05-07 Time 12:55 Sent To  
Notes
2003-05-07 00:00:00MASTER PLAN 02081325 MODEL "D"

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-05-07 Cont ID  
Sent By jwitmer Date 2003-05-07 Time 12:55 Rev Time 0.00
Received By jwitmer Date 2003-05-07 Time 12:55 Sent To  
Notes
2003-05-07 00:00:00MSTER PLAN 02081325 MODEL "D"

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-07 Cont ID  
Sent By sthyng Date 2003-04-28 Time 10:14 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***