Plan Review Details - Permit 03041791
Plan Review Stops For Permit 03041791
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-15 Cont ID  
Sent By jgomez Date 2003-07-15 Time 15:14 Rev Time 3.00
Received By jgomez Date 2003-07-15 Time 15:14 Sent To PC
Notes
2003-07-15 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE ENERGY CALCULATIONS. UNDER
 ATTIC AREA IS INCORRECT. SEE SECTION
 602.1.ABC.1.2 CHAPTER 13 FBC 2001.
 2-PROVIDE SOIL TEST REPORT PRIOR TO
 CONSTRUCTION.
 3-REVISE ROOF NAILING ZONE DIAPHRAGM.
 GABLE ENDS TO BE NAILED AS ZONE 3.
 SEE CHAPTER 23 CITY AMENDMENTS TO FBC.
 4-WHERE IS DETAIL 1/A6 KEYED ON ROOF
 FRAMING PLAN SHEET A-6.
 5-CLARIFY DETAIL 7/A5. CONNECTOR IS
 DESIGNED AS WOOD TO WOOD CONNECTOR.
 CLARIFY WHERE IT SAYS THAT DIFFERENT
 FASTENERS MAY BE USED IF NOT EXCEEDING
 25% OF THE ULTIMATE CAPACITY. ALSO,
 HOW ARE CONNECTORS ADAPTED TO RECEIVE
 DIFFERENT NAILS THAN DESIGNED FOR?.
 6-REVISE/UPDATE DETAIL 2/A5 TO COMPLY
 WITH SEC. 1609.4.3 FBC 2001. SPECIFY
 HOW WERE THE VALUES DETERMINED FOR
 THE SPECIFIED LOADS ON THIS TABLE.
 7-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE. B)ENTRY DOORS WITH LEGIBLE
 DRAWINGS WITH RENEWAL STAMP AND DADE
 COUNTY LOGO ON BOTTOM FORM OF PRODUCT
 APPROVAL REPORT. C)GARAGE DOORS WITH
 LEGIBLE DRAWINGS. D)NEED SITE SPECIFIC
 FORM FILLED FOR STRUCTURAL MULLIONS TO
 BE USED. CLEARLY INDICATE MULLIONS AND
 FASTENERS TO BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-07-11 Time 14:46 Rev Time 4.00
Received By jgomez Date 2003-06-04 Time 15:57 Sent To  
Notes
2003-06-04 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ENERGY CALCULATIONS: REVISE THE UNDER
 ATTIC AREA TO COMPLY WITH SECTION
 602.1ABC.1.2 CHAPTER 13 FBC 2001.
 2-PROVIDE SOIL TEST REPORT PRIOR TO
 CONSTRUCTION.
 3-PROVIDE SPECIFICATIONS FOR FIREBLOCK'G
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305 FBC 2001.
 4-REVISE COLS. SPECIFIED AT ENTRY DOORS.
 IT'S NOT A C1. SEE SIZE SHOWN ON FOUN-
 DATION PLAN.
 5-DETAIL 5/A5 NEED TO BE REVISED. NEED
 2X STRUCTURAL BUCK TO SUPPORT WINDOW.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-PROVIDE COMPLETE SPECS FOR GARAGE DOOR
 STRUCTURAL BUCK DETAIL. NEED ANCHOR
 EMBEDMENT AND WASHER. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 7-ENTRY TOWER: PROVIDE COMPLETE DETAIL
 AND SPECIFICATIONS FOR ATTACHMENT OF
 WINDOWS TO ROPE COLUMN SHOWN ON THE
 FRONT ELEVATION.SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 8-REVISE ROOF NAILING ZONE DIAPHRAGM.
 SEE FIGURE 1606.2(C) FBC 2001 FOR
 ZONE 3 AREA NOT SHOWN IN DRAWINGS.
 9-WHERE ARE DETAILS 1/A6 AND 1/A8 THAT
 WERE KEYED ON ROOF FRAMING PLANS?
 10-DETAIL 7/A5: CLARIFY WHERE ARE
 CONNECTORS HUC48,410,412,414 TAKEN
 FROM. SIMPSON 2003 CATALOGUE DON'T
 SHOW THEM. ALSO, NEED MASONRY HANGER.
 WHY USING A WOOD TO WOOD HANGER?.
 11-DETAIL 2/A5: UNABLE TO FIND RT22 IN
 USP CATALOGUE. IS THIS A CUSTOM MADE
 CONNECTOR?. CLARIFY. ALSO, UPDATE
 VALUES TO COMPLY WITH SEC. 1609.4.3
 FBC 2001.
 12-MISSING TRUSS ANCHOR SCHEDULE.
 13-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE.
 B)ENTRY DOORS WITH LEGIBLE DRAWINGS.
 C)GARAGE DOORS WITH LEGIBLE DRAWINGS.
 D)AS PER THE BUILDING OFFICIAL ALL SITE
 SPECIFIC PRODUCT APPROVALS TO HAVE THE
 SEAL AND SIGNATURE OF THE ARCHITECT/
 ENGINEER OF RECORD OR TO PROVIDE A
 SIGNED & SEALED LETTER CLEARLY IDENTI-
 FYING ALL SITE SPECIFIC WINDOWS AND
 ASSEMBLIES THAT WHERE REVIEWED AND
 APPROVED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-01-30 Cont ID  
Sent By dpalmer Date 2004-01-30 Time 10:09 Rev Time 0.33
Received By dpalmer Date 2004-01-30 Time 10:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-29 Time 10:17 Rev Time 0.33
Received By dpalmer Date 2004-01-27 Time 07:46 Sent To  
Notes
2004-01-27 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED WITH
 A COMPLETE SIGNATURE AND/OR SIGNATURE
 AS SIGNED ON ARCH LICENESE AND/OR
 DRIVERS LICENSE. FS 481.221
 WE ARE IN POSSESSION OF MORE THAN ONE
 SIGNATURE FOR SAME ARCH.
 PLEASE NOTE, PER BLDG OFFICAL WE ARE
 RETAINING ONE COPY OF EACH SET FOR FILE.
 IF LICENSES ARE COMPLETE AND FULL
 SIGNATURE , THEN PLANS MUST ALSO BE
 SIGNED THE SAME WAY.
  
 2)NOTE: PLEASE MOVE SD INTO MASTER BED-
 -ROOM. PER NFPA-72
  
 3)NOTE: PLEASE SEE RECEPT SPACING IN
 DINING RM. PER 210.52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-18 Cont ID  
Sent By btrobaug Date 2003-11-18 Time 11:58 Rev Time 0.50
Received By btrobaug Date 2003-11-18 Time 11:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-12 Cont ID  
Sent By sgraham Date 2003-04-30 Time 12:14 Rev Time 0.50
Received By btrobaug Date 2003-05-12 Time 11:46 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-29 Cont ID  
Sent By csiegber Date 2004-01-29 Time 10:17 Rev Time 0.00
Received By csiegber Date 2004-01-29 Time 10:17 Sent To E
Notes
2004-01-29 00:00:00TO DP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 14:46 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 14:46 Sent To B
Notes
2003-07-11 00:00:00JGOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-24 Cont ID  
Sent By shernand Date 2003-04-24 Time 11:50 Rev Time 0.00
Received By shernand Date 2003-04-24 Time 11:50 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-20 Cont ID  
Sent By kstevens Date 2003-05-17 Time 05:44 Rev Time 0.25
Received By pkrauss Date 2003-05-20 Time 08:54 Sent To B
Notes
2003-05-20 00:00:00MECHANICAL PERMIT 03041872

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-05-17 Cont ID  
Sent By btrobaug Date 2003-05-12 Time 13:09 Rev Time 0.33
Received By kstevens Date 2003-05-17 Time 05:44 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-24 Time 11:51 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***