Plan Review Details - Permit 03041728
Plan Review Stops For Permit 03041728
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-13 Cont ID  
Sent By sthyng Date 2003-05-13 Time 07:39 Rev Time 0.50
Received By sthyng Date 2003-05-13 Time 07:39 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-12 Time 09:27 Rev Time 0.50
Received By sthyng Date 2003-05-08 Time 09:06 Sent To  
Notes
2003-05-08 00:00:00****CORRECTIONS****
  
 1.)INCLUDE STANDARD SAFETY ITEMS FOR
 POOLS ON PLAN.
  
 2.)SPECIFY POOL EQUIPMENT ATTACHMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-02 Cont ID  
Sent By kstevens Date 2003-04-30 Time 13:56 Rev Time 0.33
Received By btrobaug Date 2003-05-02 Time 10:31 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-12 Cont ID  
Sent By shernand Date 2003-05-12 Time 09:27 Rev Time 0.00
Received By shernand Date 2003-05-12 Time 09:27 Sent To B
Notes
2003-05-12 00:00:00STHYNG DESK, RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-23 Cont ID  
Sent By shernand Date 2003-04-23 Time 10:43 Rev Time 0.00
Received By shernand Date 2003-04-23 Time 10:43 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-21 Cont ID  
Sent By kstevens Date 2003-05-21 Time 16:01 Rev Time 1.00
Received By kstevens Date 2003-05-21 Time 16:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-30 Cont ID  
Sent By sthyng Date 2003-05-13 Time 07:43 Rev Time 0.33
Received By kstevens Date 2003-04-30 Time 13:56 Sent To E
Notes
2003-04-30 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.7.1 POOL CIRCULATING
 PUMPS SHALL BE EQUIPPED ON THE INLET
 SIDE WITH AN APPROVED TYPE HAIR AND LINT
 STRAINER WHEN USED WITH A PRESSURE FIL-
 TER. (DETAIL)
 2) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-23 Time 10:43 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***