Plan Review Details - Permit 03041291
Plan Review Stops For Permit 03041291
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-24 Cont ID  
Sent By jgomez Date 2003-06-24 Time 17:45 Rev Time 0.50
Received By jgomez Date 2003-06-24 Time 17:38 Sent To  
Notes
2003-06-24 00:00:00PROVISO SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-05-07 Cont ID  
Sent By pkrauss Date 2003-05-05 Time 08:13 Rev Time 2.00
Received By jgomez Date 2003-05-07 Time 16:35 Sent To  
Notes
2003-05-07 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE/CLARIFY DETAIL S21 FOR COLUMN
 LOCATED BETWEEN GARAGE AND STAIRWAY TO
 MATCH CONDITIONS SHOWN ON SECOND FLOOR
 FRAMING PLAN. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 2-ROOF FRAMING PLAN: REVISE CONNECTOR
 TC-1 FOR FRAMED WALL. NEED WOOD TO
 WOOD CONNECTOR. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-34SH WINDOW DOESN'T PROVIDE THE 24"
 CLEAR HEIGHT REQUIRED BY SEC. 1005.4
 FBC 2001. REVISE AS REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-25 Cont ID  
Sent By btrobaug Date 2003-09-25 Time 16:56 Rev Time 0.33
Received By btrobaug Date 2003-09-25 Time 16:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-24 Cont ID  
Sent By csiegber Date 2003-09-19 Time 12:22 Rev Time 0.50
Received By btrobaug Date 2003-04-24 Time 08:50 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-29 Time 11:15 Rev Time 0.00
Received By csiegber Date 2003-09-29 Time 11:15 Sent To M
Notes
2003-09-29 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-19 Time 12:22 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 12:22 Sent To E
Notes
2003-09-19 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 13:46 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 13:46 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-01 Cont ID  
Sent By pkrauss Date 2003-10-01 Time 08:30 Rev Time 0.20
Received By pkrauss Date 2003-10-01 Time 08:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-05 Cont ID  
Sent By csiegber Date 2003-09-29 Time 11:15 Rev Time 0.15
Received By pkrauss Date 2003-05-05 Time 08:12 Sent To B
Notes
2003-05-05 00:00:00MECHANICAL PERMIT 03041328

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-23 Cont ID  
Sent By jleech Date 2003-04-23 Time 18:33 Rev Time 0.33
Received By jleech Date 2003-04-23 Time 18:33 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-24 Cont ID  
Sent By shernand Date 2003-04-17 Time 13:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***