Plan Review Details - Permit 03041167
Plan Review Stops For Permit 03041167
Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2004-06-04 Cont ID  
Sent By shill Date 2004-06-04 Time 12:12 Rev Time 0.50
Received By shill Date 2004-06-04 Time 12:12 Sent To  
Notes
2004-06-04 00:00:00WINDOW SHOP DRAWINGS, PRODUCT APPROVALS
 AND SITE SPECIFIC
  
  
 ****PROVISO****
  
 SUBMIT HURRICANE INSTALLATION SCHEDULE
 AS PER PROVISO WHEN THE PERMIT WAS
 ISSUED.PROVIDE INFORMATION IN REGARDS
 TO WHERE THE SHUTTERS WILL BE STORED.
 SHOW THAT THE AREA CAN ACCOMODATE THE
 SHUTTERS AND PROVIDE A DETAIL IF THEY
 ARE BEING STORED ON A RACK.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-05-28 Time 15:24 Rev Time 1.00
Received By shill Date 2004-04-14 Time 11:54 Sent To  
Notes
2004-04-14 00:00:00REVISION - 8 1/2 X 11 STRUCTURAL FIELD
 CHANGES - PANEL ATTACHMENT, REPAIR,
 NEW DOOR LOCATION, MISSED EMBEDS
 PREPARED BY CAL DATED 4/2/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2004-04-01 Cont ID  
Sent By shill Date 2004-04-01 Time 13:52 Rev Time 0.50
Received By shill Date 2004-04-01 Time 13:52 Sent To  
Notes
2004-04-01 00:00:00****CORRECTIONS****
 GARAGE DOOR SHOPS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE NOA FOR THE STEEL OVERHEAD
 GARAGE DOOR IS A PART OF THE ORIGINAL
 PERMIT PACKAGE.HOWEVER, SHOP
 DRAWINGS AND SUBMITTALS ARE TO BE
 REVIEWED BY THE DESIGNER OF RECORD.
 RENKER-EICH-PARKS IS NOT THE DESIGNER
 OF RECORD.
  
 CC:HAROLD PISKURA

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status F Date 2004-04-01 Cont ID  
Sent By shill Date 2004-04-01 Time 10:47 Rev Time 2.00
Received By shill Date 2004-04-01 Time 10:47 Sent To  
Notes
2004-04-01 00:00:00****CORRECTIONS****
 WINDOW/STOREFRONT SHOP DRAWINGS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE DRAWINGS ARE TO BE REVIEWED BY
 THE DESIGNER OF RECORD.THE ARCHITECT
 WHO SPECIFIED THE WIND PRESSURES IS
 HENRY TRIMM ON SHEET A4.HE ALSO REFERS
 TO WIND PRESSURES ON THE STRUCTURALS,
 WHICH WAS DONE BY CAL ENGINEERING.
  
 2.)PRODUCT APPROVALS FOR IMPACT GLASS
 WERE ALREADY APPROVED AND DO NOT NEED
 A SECOND APPROVAL.HOWEVER THE PERMIT
 WAS ISSUED WITH A PROVISO TO SUBMIT
 LEGIBLE COPIES OF THE NOAS.THE
 COPIES SUBMITTED ARE NOT LEGIBLE.
 THE NON-IMPACT PRODUCT APPROVALS ARE A
 A CHANGE FROM THE ORIGINAL PERMIT PLAN.
 SUBMIT AS A REVISION FOR REVIEW.
  
 3.)PROVIDE INFORMATION IN REGARDS TO
 WHERE THE SHUTTERS WILL BE STORED.
 SHOW THAT THE AREA CAN
 ACCOMODATE THE SHUTTERS AND INDICATE
 HOW THEY WILL BE STORED (FLAT OR
 VERTICALLY).IF THEY ARE STORED
 VERTICALLY, A RACK DETAIL MUST BE
 PROVIDED.THIS PERMIT WAS ISSUED WITH
 A PROVISO TO SUBMIT AN INSTALLATION
 SCHEDULE.PROVIDE AT THIS TIME.
  
 4.)THE REVIEW NOTE FROM DON COLEMAN,
 AUTO BUILDERS STATES THAT SHOP DRAWINGS
 ARE NOT REQUIRED FOR THE INTERIOR
 WINDOWS.THE PLAN, A1 NOTES A 2HR
 OCCUPANCY SEPARATION.DOES THIS APPLY
 TO THESE WINDOWS?
  
 5.)THE PRODUCT APPROVALS SUBMITTED
 ARE ILLEGIBLE.LEGIBLE COPIES MAY BE
 AVAILABLE AT WWW.MIAMIDADE.GOV (FIND
 A DEPARTMENT, BUILDING CODE COMPLIANCE,
 PRODUCT CONTROL, PRODUCT APPROVAL
 SEARCH).
  
 6.)THE SITE SPECIFIC PRODUCT APPROVAL
 FOR THE 181X120 WINDOW MUST BE REVIEWD,
 SIGNED AND SEALED BY THE DESIGNER OF
 RECORD IN BOX 10.THE PRINTED NAME,
 LICENSE NUMBER, FIRM NAME AND AUTH # IF
 APPLICABLE, ADDRESS IS INFORMATION
 REQUIRED TO BE ON THIS SHEET FAC61G15-
 23.002 (ENGINEERS), FAC61G1-16.003, 004.
  
 CC:HAROLD PISKURA

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2004-04-02 Cont ID  
Sent By alange Date 2004-03-31 Time 15:21 Rev Time 0.50
Received By shill Date 2004-03-30 Time 11:36 Sent To  
Notes
2004-04-02 00:00:00RE: FIREDOOR SUBMITTAL; RECEIVED LETTER
 FROM CONTRACTOR THAT FIREDOOR NOAS
 SUBMITTED IN ERROR.
  
 OVERHEAD DOOR SPECS SUBMITTED AND
 REVIEWED SEPARATELY.
2004-03-30 00:00:00****CORRECTIONS****
 SUBMITTALS - OVERHEAD DOORS, FIREDOORS
  
 PRODUCT APPROVALS NOT SUBMITTED WITH
 THE ORIGINAL PLAN REQUIRE SEPARATE
 PERMITS WITH SEPARATE FEES AND REVIEW.
  
 PLEASE CLARIFY AS TO WHY THE FIREDOOR
 NOAS ARE BEING SUBMITTED AT THIS TIME.
 SOME ARE STAMPED; IF THEY HAVE BEEN
 REVIEWED AND APPROVED, WHY ARE THEY
 BEING SUBMITTED NOW?
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2004-03-30 Cont ID  
Sent By shill Date 2004-03-30 Time 11:36 Rev Time 0.50
Received By shill Date 2004-03-30 Time 11:36 Sent To  
Notes
2004-03-30 00:00:00STRUCTURAL CAULKING SUBMITTAL
 BRUNSWICK DOOR SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2004-03-24 Cont ID  
Sent By shill Date 2004-03-24 Time 17:06 Rev Time 0.50
Received By shill Date 2004-03-24 Time 17:06 Sent To  
Notes
2004-03-24 00:00:00STEEL SHOP DRAWINGS (SEMBCO STEEL)

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2004-03-24 Cont ID  
Sent By hpiskura Date 2004-03-24 Time 07:12 Rev Time 0.00
Received By hpiskura Date 2004-03-24 Time 07:12 Sent To  
Notes
2004-03-24 00:00:00SHEETS RECEIVED IN THE CONSTRUCTION
 SERVICES DEPARTMENT HAVING A CAL
 ENGINEERING SHOP DRAWING REVIEW STAMP
 DATED 3/6/04 WITH AN INDISCERNIBLE
 INITIAL ARE NOT SATISFACTORY.
  
 THE SHEETS PROPOSE STRUCTURAL CHANGES
 AND OR REPAIRS AND ARE NOT SIGNED,
 SEALED AND DATED BY A FLORIDA
 PROFESSIONAL ENGINEER.
  
 ONE SET PROPOSES CUTTING PANEL P-20 FOR
 A DOOR.ANOTHER PROPOSES A SOLUTION FOR
 MISSED EMBED PLATES AND A THIRD
 DESCRIBES A METHOD FOR INSTALLING
 MISSED REBAR AT THE PANEL FLOOR SLAB
 CONNECTION.
  
 THE ARDAMAN & ASSOCIATES REPAIR METHOD
 FOR THE UNDERMINED SLABS WAS NOT
 EMPLOYED.PLEASE ADVISED ACCEPTANCE OF
 THE UNCOMPACTED FILL IN THESE AREAS.
 SEE ATTACHED PHOTOS.
  
 PROVIDE PLANS AND SKETCHES IN ACCORDANCE
 WITH GOOD ENGINEERING PRACTICE SUITABLE
 FOR PUBLIC RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2004-02-23 Cont ID  
Sent By csiegber Date 2004-03-19 Time 12:31 Rev Time 0.50
Received By shill Date 2004-02-23 Time 17:27 Sent To  
Notes
2004-02-23 00:00:00TILT PANEL REBAR, PANELS 63 - 70,
 76 - 80 (GULFSTREAM LUMBER, 11/17/3)
  
 TILT PANEL LAYOUT, CASTING BED LAYOUT
 PREPARED BY CAD SOLUTIONS 10/28/3

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-19 Time 14:39 Rev Time 1.00
Received By shill Date 2004-02-05 Time 09:45 Sent To  
Notes
2004-02-05 00:00:00****CORRECTIONS*****
  
 TILT PANEL SHOPS & LAYOUT
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)THE THIRD SET SUBMITTED HAS REDLINE
 MARKS NOT ON THE OTHER TWO SETS. PROVIDE
 THREE IDENTICAL SETS OF SHOP DRAWINGS,
 REVIEWED BY THE DESIGNER OF RECORD.
  
 2.)TILT PANEL LAYOUT REQUIRES THREE
 COPIES, REVIEWED BY THE DESIGNER OF
 RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2004-01-27 Cont ID  
Sent By shill Date 2004-01-27 Time 16:28 Rev Time 0.50
Received By shill Date 2004-01-27 Time 16:28 Sent To  
Notes
2004-01-27 00:00:00*****CORRECTIONS*****
 TILT PANEL REBAR, GULFSTREAM LUMBER
 PANEL LAYOUT, CAD SOLUTIONS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THREE COPIES OF ALL PLANS/SHOP
 DRAWINGS ARE REQUIRED FOR JOBS WITH A
 RESIDENT INSPECTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2004-01-27 Cont ID  
Sent By hpiskura Date 2004-01-27 Time 12:57 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2004-01-27 00:00:00TILT PANEL SHOP DWG CAD SOLUTIONS INC.
 DATED 10/16/03.
  
 SHOP DRAWINGS ARE REQUIRED TO BE
 REVIEWED BY THE ENGINEER OF RECORD
 BEFORE SUBNMITTING TO THE CITY.
  
 ALSO, THREE SETS OF INFORMATION ARE
 REQUIRED FOR PROJECTS WITH A RESIDENT
 INSPECTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2004-01-17 Cont ID  
Sent By csiegber Date 2004-01-23 Time 15:23 Rev Time 0.50
Received By shill Date 2004-01-17 Time 18:54 Sent To  
Notes
2004-01-17 00:00:00****CORRECTIONS****
  
 STEEL SHOP DRAWINGS PREPARED BY SEMBCO
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SHOP DRAWINGS ARE TO BE REVIEWED
 BY THE DESIGNER OF RECORD.
  
 2.)THREE SETS SHOULD BE SUBMITTED;
 THE ADDITIONAL SET IS FOR THE RESIDENT
 INSPECTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-13 Time 09:47 Rev Time 0.50
Received By shill Date 2004-01-12 Time 16:15 Sent To  
Notes
2004-01-12 00:00:00*****CORRECTIONS*****
  
 TILT PANEL REBAR SHOP DRAWINGS
 PREPARED BY GULFSTREAM LUMBER 11/17/03
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SHOP DRAWINGS ARE TO BE REVIEWED
 BY THE DESIGNER OF RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-08-19 Cont ID  
Sent By csiegber Date 2004-01-07 Time 16:50 Rev Time 0.00
Received By hpiskura Date 2003-08-19 Time 10:05 Sent To  
Notes
2003-08-19 00:00:00REVISIONS DATED 8/11/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-07-31 Cont ID  
Sent By hpiskura Date 2003-07-31 Time 07:53 Rev Time 0.00
Received By hpiskura Date 2003-07-31 Time 07:53 Sent To  
Notes
2003-07-31 00:00:00PROVIDE NOA'S AND/OR TEST REPORTS FOR
 THE ADDED SKYLIGHTS RESISTANCE TO
 HURRICANE MISSILE IMPACT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-01 Cont ID  
Sent By alange Date 2003-07-30 Time 14:31 Rev Time 0.00
Received By hpiskura Date 2003-07-01 Time 14:26 Sent To  
Notes
2003-07-01 00:00:00PROVISO:
  
 1IMPACT FEES MUST BE PAID, PLANS
 STAMPED AND RECEIPT ATTACHED TO PERMIT
 APPLICATION.
  
 2PROVIDE A THIRD SET OF PLANS FOR THE
 RESIDENT INSPECTOR.
  
 3PROVIDE AN INSTALLATION SCHEDULE FOR
 THE HURRICANE SHUTTERS, INCLUDE SELECTED
 COMPONENTS ON THE NOA, SPANS, FASTENERS
 AND LOCATIONS. BEFORE INSTALLATION.
  
 4NOA 01-0227.03 HAS ILLEGIBLE
 DRAWINGS, PROVIDE CLEAR COPIES BEFORE
 INSTALLATION.
  
 5THIS IS AN ENCLOSED BUILDING, NOT AN
 OPEN BUILDING.80% OPENINGS ARE FOR
 OPEN BUILDINGS.SEE THE ATTACHED CODE
 EXCERPT.PROVIDE THE METHOD OF WIND
 RESISTANCE FOR THE LOUVERS AS
 PREVIOUSLY REQUESTED.
  
 6THE DECLARED PERMIT VALUATION OF
 $2060750.00 IS TOO LOW.THE CITY
 ESTIMATE FOR THIS WORK IS $3604149.00.
 PLEASE PAY AN ADDITIONAL $39408.77
 PERMIT FEES TO THE CITY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-10 Cont ID  
Sent By hpiskura Date 2003-06-10 Time 14:49 Rev Time 0.00
Received By hpiskura Date 2003-06-10 Time 14:07 Sent To  
Notes
2003-06-10 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 A RESIDENT INSPECTOR WILL BE REQUIRED
 FOR THIS PROJECT.CONTACT DON NEELY AT
 561-805-6665 FOR MORE INFORMATION.
  
 PLEASE PROVIDE THE STRUCTURAL
 INFORMATION IN ACCORDANCE WITH FBC
 1606.1.7.
  
 SHOW HOW HURRICANE MISSLE IMPACT
 RESISTANCE WILL BE ACCOMPLISHED FOR THE
 GLAZED AREAS IN THE EXTERIOR BUILDING
 ENVELOPE, INCLUDING SKYLIGHTS.SEE FBC
 1606.1.4.(NOTE:INCLUDE THE 17 8X2.5
 LOUVERS FOR INTERNAL PRESSURE ANALYSIS)
  
 IF NOTICE OF ACCEPTANCE AND/OR TEST
 REPORTS FOR THE DOORS, WINDOWS AND ROOF
 COVERING ARE NOT INCLUDED WITH THE
 PERMIT APPLICATION, SEPARATE PERMITS
 AND FEES AND WILL BE REQUIRED.
  
 A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT IS REQUIRED BEFORE PERMIT
 ISSUE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-15 Cont ID  
Sent By hpiskura Date 2003-05-15 Time 09:29 Rev Time 0.00
Received By hpiskura Date 2003-05-13 Time 16:05 Sent To  
Notes
2003-05-15 00:00:00THIS BUILDING WILL BE AN H3 OCCUPANCY AS
 DEFINED IN FBC 308.2.1.THE STORAGE OF
 TIRES CONSTITUTES A "FLAMMABLE SOLID"
 AS CALLED OUT IN FBC 308.2.1 AND
 DEFINED IN FBC 202.
  
 THEREFORE THE 100,000 + SQUARE FEET
 BUILDING PROPOSED FAR EXCEEDS THE AREA
 FOR A GROUP H BUILDING IN FBC TABLE
 500.FURTHER, FOOTNOTE C TO TABLE 500
 PROHIBITS AREA AND/OR HEIGHT INCREASES.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-08-26 Cont ID  
Sent By dpalmer Date 2004-08-26 Time 09:44 Rev Time 1.00
Received By dpalmer Date 2004-08-26 Time 09:30 Sent To  
Notes
2004-08-26 00:00:00**** NOTE ******
 FIRE PUMP DECREASED FROM 150HP TO 100HP
 THIS IS FOR ELECTRICAL REVISION OF RISER
 ONLY. FIRE PLANS WILL ALSO NEED TO BE
 REVISED, REVIEWED BY FIRE PLAN REVIEW
 FOR CODE COMPLIANCE.
  
 ***PLANS NOW MISSING NOTE FOR SIGNAGE
 AS ON PREVIOUS PLANS.
 230.2E
  
 *** PLANS ALSO NOTED FOR FIRE PUMP CONT.
 TO MEET 230.76,230.79 AND 110.27
 MUST HAVE MANUAL MEANS OF DISCONNECT.
 230.76
 THIS MANUAL MEANS OF DISCONNECT MUST BE
 RATED FOR THE LOAD SERVED. 230.79
 THIS MEANS OF DISCONNECT MAY NOT EXPOSE
 LIVE PARTS. 110.27
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-08-20 Time 15:39 Rev Time 0.25
Received By dpalmer Date 2004-07-16 Time 08:21 Sent To  
Notes
2004-07-16 00:00:00*** N**
 SHEET E-4 SUBMITTED, THIS IS FOR FIRE
 ALARM AND NOT FOR ELECTRICAL REVIEW.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-07-16 Cont ID  
Sent By dpalmer Date 2004-07-16 Time 08:11 Rev Time 0.50
Received By dpalmer Date 2004-07-16 Time 08:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-07-12 Time 15:23 Rev Time 0.33
Received By dpalmer Date 2004-05-14 Time 08:02 Sent To FIRE
Notes
2004-05-14 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002,
 FS 471.023. PLEASE PROVIDE LICENSE #
 AS REQ'D FOR CERTIFICATE OF AUTHORIZAT-
 -ION.
 REQUIRED TO BE PRINTED IN TITLE BLOCK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 16:51 Rev Time 0.33
Received By dpalmer Date 2003-08-12 Time 06:12 Sent To  
Notes
2003-08-12 00:00:00FENCING/GATES SHOULD BE UNDER SEPARATE
 PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-06-12 Cont ID  
Sent By dpalmer Date 2003-06-12 Time 09:48 Rev Time 1.00
Received By dpalmer Date 2003-06-12 Time 09:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-07 Cont ID  
Sent By dpalmer Date 2003-05-07 Time 07:22 Rev Time 3.00
Received By dpalmer Date 2003-05-06 Time 18:59 Sent To  
Notes
2003-05-07 00:00:00************* UNSAT*************
  
 1)NOTE: PLEASE VERIFY CODE LETTER
 OF FIRE PUMP MOTOR/OR PLEASE NOTE AS
 "LISTED W/OCP SET FOR LOCKED ROTOR".
 695-4-B1
  
 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 CONTRACTOR TO PROVIDE SIGNAGE FOR MEANS
 OF DISC OF MAINS 1 AND FIRE PUMP/ LOCAT-
 -IONS ETC.230-2E
  
 3)NOTE: PLEASE SEE THAT THERE IS A PANEL
 -BOARD "M" SHOWN ON SCHEDULES, BUT NOTH-
 ING SHOWN ON RISER DIAGRAM? SHOWN ON
 FLOOR PLAN ALSO?
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS
 AT 125%. 220-3,220-10,220-11,220-13,
 215-3,230-42 ETC.
  
 5)NOTE: PLEASE CORRELATE PANEL "A" AND
 RISER, SHOWS FEED TO PANEL "T" W/ #2`S
 AND RISER SHOWS # 1`S?
  
 6)NOTE: PLEASE SEEPANEL"A" ALSO SHOWS
 FEEDING PANEL "M".
  
 7)NOTE: PLEASE SEE PANEL "L", BOXES
 CHECKED FOR MLO& MCB. RISER, SHOWS AS
 MLO. (MISPRINT)
  
 8)NOTE: PLEASE SEE 700-16 FOR FIXTURES
 LOCATED IN SOME AREAS THAT ARE SHOWN
 W/ SINLGE BALLAST(ELEC RMS).
  
 9)NOTE: PLEASE CLARIFY LIGHTING IN AREAS
 /HALLWAYS NEARS PANELS, B>L>M.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-06-02 Cont ID  
Sent By mamini Date 2003-06-02 Time 15:53 Rev Time 1.00
Received By mamini Date 2003-06-02 Time 15:53 Sent To  
Notes
2003-06-02 00:00:00PASSED :
 1. SEE PERMIT # 03060010 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-04-18 Cont ID  
Sent By mamini Date 2003-04-18 Time 08:26 Rev Time 1.00
Received By mamini Date 2003-04-18 Time 08:26 Sent To  
Notes
2003-04-18 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK IS REQUIRED.
 2. PLEASE SUBMIT TWO SETS OF CIVIL/SITE
 PLANS (SIGNED & SEALED) FOR OUR REVIEW
 AND APPROVAL, SUBMITALL MUST INCLUDE
 STORM WATER CALCULATION, PERVIOUS &
 IMPERVIOUS CALC. FOR THE PROPOSED SITE.
 3. PLANS MUST BE APPROVED FOR ALL THE
 CONNECTIONS TO SERVICES AND BACKFLOWS
 BY THE PUBLIC UTILITIES PRIOR TO BEING
 SUBMITTED TO THE BUILDING DEPARTMENT.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2004-10-14 Cont ID  
Sent By nmccray Date 2004-10-14 Time 10:38 Rev Time 0.00
Received By nmccray Date 2004-10-14 Time 10:38 Sent To  
Notes
2004-10-14 00:00:00REVISION DATED 9-22-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-10-07 Time 15:22 Rev Time 0.00
Received By mcarsill Date 2004-07-29 Time 09:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2004-07-27 Cont ID  
Sent By mcarsill Date 2004-07-27 Time 13:06 Rev Time 0.00
Received By mcarsill Date 2004-07-27 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2004-05-17 Cont ID  
Sent By nmccray Date 2004-05-17 Time 16:21 Rev Time 0.00
Received By nmccray Date 2004-05-17 Time 16:21 Sent To  
Notes
2004-05-17 00:00:00************DENIED**********************
 1) SEPARATE PERMIT AND SHOP DRAWING ARE
 REQUIRED FOR SECURITY ENTRY GATE AND
 SECURITY CONTROLLED DOORS.
  
 2) THE VEHICLE ENTRY GATE SHALL BE A
 MINIMUM WIDTH OF 20 FEET.
  
 3) HOW DOES FIRE DEPARTMENT VEHICLES ARE
 TO GAIN ACCESS TO THE PROPERTY AFTER
 HOURS. DO THIS GATE HAVE KNOX-KEY
 CONTROL.
  
 4) ALL SPECIAL LOCKING AND CONTROLLED
 DEVICES ON DOORS SHALL COMPLY WITH CH.7
 OF NFPA 101 LIFE SAFETY CODE 2000
 EDITION.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-08-06 Cont ID  
Sent By dpalmer Date 2004-05-14 Time 08:03 Rev Time 0.00
Received By nmccray Date 2003-08-06 Time 11:11 Sent To  
Notes
2003-08-06 00:00:00REVISION DATED FOR 8-04-03 OK & REVISION
 DATED FOR 7-21-03 OK

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-06-18 Cont ID  
Sent By nmccray Date 2003-06-18 Time 11:23 Rev Time 0.00
Received By nmccray Date 2003-06-18 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-05-20 Cont ID  
Sent By nmccray Date 2003-05-20 Time 14:56 Rev Time 0.00
Received By nmccray Date 2003-05-20 Time 14:56 Sent To  
Notes
2003-05-20 00:00:001) PLEASE REF NFPA 1,CH.8-15 & CH 32;
 NFPA 231D.
  
 2) WET FIRE HYDRANTS SHALL BE INSTALLED
 AND IN OPERATION PRIOR TO AND DOING
 CONSTRUCTION. ACCESS TO THESE FIRE
 HYDRANTS MUST BE MAINTAINED THROUGHOUT
 THE CONSTRUCTION.
  
 3) SEPARATE PLAN AND PERMIT APPLICATION
 WILL BE REQUIRED FOR FIRE PUMP.
  
 4) SEPARATE PLAN AND PERMIT APPLICATION
 WILL BE REQUIRED FOR FIRE ALARM SYSTEM.
  
 5) SEPARATE PLAN AND PERMIT APPLICATION
 WILL BE REQUIRED FOR ACCESS CONTROLLED
 DOORS AND SECURITY GATES.
  
 6) SEPARATE PLAN AND PERMIT APPLICATION
 WILL BE REQUIRED FOR FIRE SPRINKLER
 SYSTEM.
  
 7) BUILDING SHALL HAVE APPROVED ADDRESS
 NUMBERS PLACED IN A POSITION TO BE
 PLAINLY LEGIBLE AND VISIBLE FROM THE
 STREET AND ROAD FRONTING THE PROPERTY.
  
 8) FIRE DEPT CONNECTION SHALL BE 150 FT
 OR LESS TO FIRE HYDRANT.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-07 Time 15:22 Rev Time 0.00
Received By csiegber Date 2004-10-07 Time 15:22 Sent To FIRE
Notes
2004-10-07 00:00:00REV

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-08-20 Time 15:39 Rev Time 0.00
Received By csiegber Date 2004-08-20 Time 15:39 Sent To E
Notes
2004-08-20 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2004-07-15 Cont ID  
Sent By csiegber Date 2004-07-15 Time 09:10 Rev Time 0.00
Received By csiegber Date 2004-07-15 Time 09:10 Sent To  
Notes
2004-07-15 00:00:00TO COMM BD#4/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-12 Time 15:23 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 14:50 Sent To  
Notes
2004-07-12 00:00:00TO COMM BD#35

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2004-05-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 15:24 Rev Time 0.00
Received By csiegber Date 2004-05-28 Time 15:24 Sent To B
Notes
2004-05-28 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 16:51 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 16:51 Sent To E
Notes
2004-05-12 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2004-03-31 Cont ID  
Sent By alange Date 2004-03-31 Time 15:21 Rev Time 0.00
Received By alange Date 2004-03-31 Time 15:21 Sent To B
Notes
2004-03-31 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 12:31 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 12:31 Sent To B
Notes
2004-03-19 00:00:00TO SH DESK/STRUCTURAL STEEL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 12:25 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 12:25 Sent To B
Notes
2004-03-19 00:00:00TO SH DESK/STRUCTURAL CAULKING/OVERHEAD
 ROLL UP DOORS/HOLLOW METAL DOORS

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 14:39 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 14:39 Sent To B
Notes
2004-02-19 00:00:00TO SH DESK/SUBMITTAL/TILT PANEL & REBAR

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-01-23 Time 15:23 Rev Time 0.00
Received By csiegber Date 2004-01-23 Time 15:23 Sent To B
Notes
2004-01-23 00:00:00TO SH DESK/TILT PANELS REBAR

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-13 Time 09:47 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 09:47 Sent To B
Notes
2004-01-13 00:00:00TO SH DESK/STRUCTURAL SHOP DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-01-07 Cont ID  
Sent By csiegber Date 2004-01-07 Time 16:50 Rev Time 0.00
Received By csiegber Date 2004-01-07 Time 16:50 Sent To B
Notes
2004-01-07 00:00:00TO HP DESK/TILT PANEL S/D

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-01-06 Cont ID  
Sent By csiegber Date 2004-01-06 Time 14:37 Rev Time 0.00
Received By csiegber Date 2004-01-06 Time 14:37 Sent To B
Notes
2004-01-06 00:00:00TO SH DESK/TILT PANEL REBAR SHOP DRAW

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-08-15 Cont ID  
Sent By alange Date 2003-08-15 Time 15:04 Rev Time 0.00
Received By alange Date 2003-08-15 Time 15:04 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 15:05 Rev Time 0.00
Received By alange Date 2003-08-04 Time 15:05 Sent To  
Notes
2003-08-04 00:00:00TO COMM BOX # 13

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 14:31 Rev Time 0.00
Received By alange Date 2003-07-30 Time 14:31 Sent To B
Notes
2003-07-30 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-25 Cont ID  
Sent By csiegber Date 2004-05-05 Time 14:17 Rev Time 0.00
Received By csiegber Date 2003-07-25 Time 10:05 Sent To  
Notes
2003-07-25 00:00:00TO COMM BD # 18

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 08:02 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 08:02 Sent To  
Notes
2003-06-26 00:00:00COMM BOARD #45

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-06-04 Time 13:58 Rev Time 0.00
Received By shernand Date 2003-06-04 Time 13:58 Sent To  
Notes
2003-06-04 00:00:00COMM BOARD #13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-15 Cont ID  
Sent By sgraham Date 2003-04-16 Time 14:52 Rev Time 0.00
Received By shernand Date 2003-04-15 Time 16:42 Sent To  
Notes
2003-04-15 00:00:00COMM BOARD #59

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-08-19 Cont ID  
Sent By pkrauss Date 2003-08-19 Time 08:28 Rev Time 0.40
Received By pkrauss Date 2003-08-19 Time 08:28 Sent To  
Notes
2003-08-19 00:00:00PROVISO:
  
 MISSING ONE COPY OF M-3, ONLY 2 COPIES
 SUBMITTED 3 COPIES SHOULD HAVE BEEN
 SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-13 Cont ID  
Sent By pkrauss Date 2003-08-13 Time 10:19 Rev Time 0.45
Received By pkrauss Date 2003-08-13 Time 10:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-13 Cont ID  
Sent By pkrauss Date 2003-05-13 Time 13:20 Rev Time 2.15
Received By pkrauss Date 2003-05-13 Time 12:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2003-08-18 Cont ID  
Sent By kstevens Date 2003-08-16 Time 14:23 Rev Time 2.00
Received By kstevens Date 2003-08-16 Time 14:23 Sent To  
Notes
2003-08-16 00:00:00REVISION OK - DELETED THEN ADD MEZZINENE
 TOILET ROOM - DELETED GAS/SAND OIL SEP--
 ARATOR. SUBMITTED ROOF DRAIN CALCULATION
 AND LOCATED SCUPPER DRAINS DOWNSPOUTS.
 PENDING APPROVAL BY RODNEY COMPO.

Review Stop P PLUMBING
Rev No 5 Status F Date 2003-08-09 Cont ID  
Sent By alange Date 2003-08-15 Time 15:04 Rev Time 3.50
Received By kstevens Date 2003-08-08 Time 18:51 Sent To  
Notes
2003-08-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BLDG.
 FBC-2001 AMENDMENTS, ADMIN.
 CODE, CHAPTER 1
  
 1) SHT A.1 PER TABLE 1003.1 (BLDG) AND
 TABLE 403.1 (PLMBG) PLUS SQUARE FOOTAGE
 SUPPLIED BY ARCHITECT, 110726 (WHSE)
 MINUS OFFICE AREA OF 7,081 SQUARE FEET,
 6 WATER CLOSETS ARE REQUIRED. 8 WERE
 PROVIDED BUT 3 DELETED, (TWO URNALS AND
 1 WATER CLOSET), SO ONLY 5 ARE PROVIDED.
 2) SHTS A.7 & A.13 DETAILS AND NOTE ON
 SHT A.13 INDICATE 7 DOWNSPOUTS & SCUPPER
 AREAS, BUT SHT P6 WITH THE ROOF DRAIN
 CALCULATIONS SHOW 11 SCUPPERS AND DOWN
 SPOUTS. PLEASE CLAIRFY.
 3) SHT A.13 SHOWS 12" X 6" GUTTER, BUT
 SHT P6 SHOWS THE GUTTER TO BE 16"WX6"D
 PLEASE CLAIRFY.
 4) PROVIDE ELEVATION FOR GUTTER SHOWING
 PITCH TO DOWNSPOUTS, (SLOPE), ON SOUTH
 SIDE OF BLDG.
 5) SHTS A.13 & P6. A.13 SHOWS 9 DOWN-
 SPOUTS ON SOUTH SIDE AND SHT P6 SHOWS
 11 DOWNSPOUTS. PLEASE CLAIRFY
 6) SHT P6 STILL SHOWS URNALS IN MEN'S
 TOILET ROOMS.
 7) SHT P4 REVISION DELETED GASOLINE, OIL
 SANT INTECEPTOR WITH CALCULATIONS AND
 THE SUMP PUMP DETAIL. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-07-02 Cont ID  
Sent By kstevens Date 2003-07-02 Time 08:48 Rev Time 1.00
Received By kstevens Date 2003-07-02 Time 08:48 Sent To  
Notes
2003-07-02 00:00:00PASSED/PROVISO
  
  
 EYE WASH AND EMERGENCY SHOWER REQUIRED
 WITH FLOOR DRAIN. - REVISION REQUIRED
 FOR FLOOR PLAN, PLUMBING FLOOR PLAN,
 WATER RISER DIAGRAM, AND SANITARY RISER
 DIAGRAM.

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-06-27 Cont ID  
Sent By kstevens Date 2003-06-27 Time 14:45 Rev Time 1.50
Received By kstevens Date 2003-06-27 Time 14:44 Sent To  
Notes
2003-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) PER MSDS SHEETS AN EYEWASH/EMERGENGY
 SHOWER SHALL BE REQUIRED. SEC 411
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-19 Cont ID  
Sent By kstevens Date 2003-06-19 Time 17:09 Rev Time 2.50
Received By kstevens Date 2003-06-19 Time 17:06 Sent To  
Notes
2003-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHTS A-9,A-10,A-24. TRAINING ROOM
 UNISEX TOILET DETAIL AND MEZZANINE LOUN-
 GE. DOOR SHALL NOT OPEN INTO THE CLEAR
 FLOOR SPACE REQUIRED BY ANY FIXTURE.
 SEC 11-4.22.2, 11-4.17.5. 11-4.23.2
 2) ALL PLUMBING APPLIANCES SHALL BE BY
 AN APPROVED AGENCY. SECTION 303.4, AND
 303.4.1
 3) MSDS SHEETS NOT FOUND. NOTIFIED MR.
 HENRY O. TRIMM AND HE INDICATED HE WILL
 SEND SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-15 Cont ID  
Sent By kstevens Date 2003-05-15 Time 18:42 Rev Time 3.25
Received By kstevens Date 2003-05-15 Time 18:42 Sent To  
Notes
2003-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1) SHTS A.9, A.10, & A.24, IF TOILET
 FACILITIES ARE PROVIDED ON A SITE, THEN
 EACH SUCH PUBLIC OR COMMON USE TOILET
 FACILITY SHALL COMPLY WITH SECTION
 11-4.22.SECTION 11-4.1.3(11)
 2) SHTS A.9, A.10, & A.24, IF TOILET
 STALLS ARE PROVIDED, THEN AT LEAST ONE
 SHALL BE A STANDARD STALL COMPLYING WITH
 SEC 11-4.17.SECTION 11-4.22.4
 3) SHT A.14 RELIEF SCUPPER DETAIL,
 PLEASE INDICATE HEIGHT OF FLOW LINE OFF
 ROOF PER SECTION 1503.4.2
 4) SHT A.25 ALL LOUNGE SINKS SHALL COM-
 PLY WITH SECTION 11-4.24 AND ALL SUB-
 SECTIONS.
 5) SHTS P1 & P3 HOSE BIBB SHALL HAVE A
 SHUTOFF VALVE. SECTION 606.2(2)
 6) SHT P-3 PLEASE CONTACT RODNEY COMPO,
 INDUSTRIAL PRE-TREATMENT, ENVIRONMENTAL
 COMPLIANCE FOR SIZING THE OIL INTERCEPT-
 OR. WASTE ORD 2938-96. (561)837-4074.
 7) PLEASE PROVIDE MANUF INFO FOR MYERS
 GRINDER PUMP. PLEASE SHOW LISTING FOR
 PUMP.
 8) SJTS A.13, P4, & P6. SHT A.13 SHOWS
 8 - 8" ROOF DRAINS. 6 AT 14,000 SQ FT &
 2 AT 7,100 SQ FT.-SHTS P4 & P6 SHOWS
 8" ROOF DRAINS (TYPICAL OF 6) & 6" ROOF
 DRAINS (TYPICAL OF 4) ALL AT 7,100 SQ FT
 PLEASE CLAIRFY. - ALSO 14,000 SQ FT ON A
 HORIZONTAL DRAIN REQUIRES MIN. 10" PIPE,
 7,100 SQ FT REQUIRES 8" HORIZONTAL PIPE
 SIZE, & 4,500 SQ FT REQUIRES 6" HORIZON-
 TAL PIPE.
 9) PLEASE PROVIDE A LIST OF STORAGE
 MATERIALS AND MSDS SHEETS FOR ANY HAZ-
 ARDOUS MATERIALS. - AN EMERGENCY EYE
 WASH AND OR SHOWER MAY BE REQUIRED DE-
 PENDING ON MSDS INFORMATION RECIEVED.
 10) SEPARATE IRRIGATION PERMIT & PLANS
 SHALL BE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 3 Status P Date 2004-07-20 Cont ID  
Sent By mmclean Date 2004-07-20 Time 10:59 Rev Time 0.00
Received By mmclean Date 2004-07-20 Time 10:59 Sent To  
Notes
2004-07-20 00:00:00APPROVED BY JOSH LONG, PLANNER 659-8031

Review Stop Z ZONING
Rev No 2 Status F Date 2003-07-30 Cont ID  
Sent By mmclean Date 2003-07-30 Time Y1:13 Rev Time 0.00
Received By mmclean Date   Time   Sent To B
Notes
2003-07-30 00:00:007/30/03 SITE PLAN DENIED, SEVERAL CHANGE
 FROM SITE PLAN WHICH WAS APPROVED DURING
 THE FORMAL SITE PLAN REVIEW PB1239E
 PROCESS.ANY CHANGES TO THE APPROVAL
 PLAN REQUIRE ANTOHER FSPR.ANY QUESTION
 CALL JOSH, ASSOC PLANNER 659-8031 MM

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-16 Cont ID  
Sent By sgraham Date 2003-04-16 Time 14:52 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
2003-04-16 00:00:00APPROVED BY RGRANBERRY