Plan Review Details - Permit 03041038
Plan Review Stops For Permit 03041038
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-15 Cont ID  
Sent By jwitmer Date 2003-07-15 Time 08:04 Rev Time 0.33
Received By jwitmer Date 2003-07-15 Time 08:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-03 Cont ID  
Sent By jwitmer Date 2003-06-03 Time 10:44 Rev Time 0.75
Received By jwitmer Date 2003-06-03 Time 10:44 Sent To  
Notes
2003-06-03 00:00:00BUILDING PROVISO:
 COMMENT# 4 NOT ADDRESSED:
 PROVIDE INFORMATION ON RAISED FLOOR,
 NO DETAILS, NO MATERIALS OR MANUFAC-
 TURERS SPECIFICATION, NOR HEIGTH OF THE
 RAISED FLOOR FROM FINISH FLOOR.
 THIS INFORMATION TO REQUIRED BEFORE THE
 FRAMING INSPECTION.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)805-6715

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-28 Cont ID  
Sent By jwitmer Date 2003-04-28 Time 08:53 Rev Time 1.33
Received By jwitmer Date 2003-04-28 Time 08:35 Sent To  
Notes
2003-04-28 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03041038
 ADD: 250 AUSTRALIAN AVENUE / 8TH FL
 CONT: CATALFUMO CONSTRUCTION
 TEL: (561)694-8818
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION : DENIED
  
 1) SHEET, A-1 PROJECT INFORMATION :
 TYPE OF CONSTRUCTION TYPE IV
 TABLE 500 ONLY ALLOWS TYPE IV BUILDINGS
 A MAXIMUM OF 5 STORIES FOR BUSINESS
 OCCUPANCY.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PLANS DO NOT INDICATEAS TO WHAT
 CODE THIS PLAN CONFORMS TO?
  
 3) SECTION 609.2.1 PARTITIONS SHALL BE
 CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS.
 THIS INCLUDES BACKING IN WALLS.
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-4:
 A) DETAIL # 1, INDICATES A RAISED
 FLOOR BUT DOES NOT GIVE ANY INFORMATION
 ON THE TYPE OF MATERIALS, INSTALLATION
 NOR MANUFACTURERS SPECIFICATION.
 B) DETAIL # 3, THE DROPPED SOFFIT
 DETAIL DOESN'T INDICATE THETYPE OF FAST-
 ENER NOR THE SPACING?
  
 5)THE MINIMUM INTERIOR FINISH CLASSIFI-
 CATION NOT LISTED, SEE TABLE 803.3.
 PLANS DO NOT STATE IF THE SPACE IS
 FIRE SPRINKLERED.
  
 6) WILL THERE BE CABLE TRAYS ABOVE THE
 CEILING FASTENED TO THE DECK ABOVE?
 IF SO PROVIDE ADDITIONAL INFO. TYPE OF
 MATERIALS, FASTENING DEVICE & SPACING?
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-09 Cont ID  
Sent By dpalmer Date 2003-07-09 Time 09:31 Rev Time 0.33
Received By dpalmer Date 2003-07-09 Time 09:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-28 Cont ID  
Sent By dpalmer Date 2003-04-28 Time 15:35 Rev Time 0.50
Received By dpalmer Date 2003-04-28 Time 15:35 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-05-02 Cont ID  
Sent By drunnels Date 2003-05-02 Time 15:38 Rev Time 0.00
Received By drunnels Date 2003-05-02 Time 15:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-07-15 Cont ID  
Sent By nmccray Date 2003-07-15 Time 15:26 Rev Time 0.00
Received By nmccray Date 2003-07-15 Time 15:26 Sent To  
Notes
2003-07-15 00:00:00REVISION 6-27-03 NAM

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-06-03 Cont ID  
Sent By nmccray Date 2003-06-03 Time 14:42 Rev Time 0.00
Received By nmccray Date 2003-06-03 Time 14:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-05-02 Cont ID  
Sent By mcarsill Date 2003-05-02 Time 10:43 Rev Time 0.00
Received By mcarsill Date 2003-05-02 Time 10:43 Sent To  
Notes
2003-05-02 00:00:001) IS THERE ANY FIRE ALARM EQUIPMENT
 CONTAINED WITHIN THE COMPUTER ROOM.
  
 2) NO METION OF ANY FIRE SUPPRESSION
 SYSTEMS CONTAINED WITHIN ROOM.
  
 3) PLEASE DETAIL INTERIOR FINISH
 INFORMATION.
  
 4) NO EXIT SIGN SHOWN IN COMPUTER ROOM.
 IS THERE AN EXISTING ONE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-22 Cont ID  
Sent By alange Date 2003-07-22 Time 16:06 Rev Time 0.00
Received By alange Date 2003-07-22 Time 16:06 Sent To FS
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-30 Cont ID  
Sent By shernand Date 2003-06-30 Time 09:49 Rev Time 0.00
Received By shernand Date 2003-06-30 Time 09:49 Sent To  
Notes
2003-06-30 00:00:00COMM BOARD #29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-05-30 Time 16:14 Rev Time 0.00
Received By shernand Date 2003-05-30 Time 16:15 Sent To  
Notes
2003-05-30 00:00:00COMM BOARD #6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-04-14 Time 14:21 Rev Time 0.00
Received By shernand Date 2003-04-14 Time 14:21 Sent To  
Notes
2003-04-14 00:00:00COMM BOARD #7

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-08 Cont ID  
Sent By pkrauss Date 2003-07-08 Time 08:14 Rev Time 0.40
Received By pkrauss Date 2003-07-08 Time 07:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-01 Cont ID  
Sent By pkrauss Date 2003-05-01 Time 13:06 Rev Time 0.55
Received By pkrauss Date 2003-05-01 Time 13:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-05-02 Cont ID  
Sent By drunnels Date 2003-05-02 Time 15:38 Rev Time 0.00
Received By drunnels Date 2003-05-02 Time 15:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2003-05-02 Cont ID  
Sent By drunnels Date 2003-05-02 Time 15:38 Rev Time 0.00
Received By drunnels Date 2003-05-02 Time 15:38 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy