Plan Review Details - Permit 03040961
Plan Review Stops For Permit 03040961
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-30 Cont ID  
Sent By lsmith Date 2003-04-30 Time 11:40 Rev Time 0.50
Received By lsmith Date 2003-04-30 Time 11:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-18 Cont ID  
Sent By kstevens Date 2003-04-23 Time 11:46 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2003-04-18 00:00:001. FAILED PLUMBING
 2. NO ANCHORINGDETAIL SHOWN FOR
 EQUIPMENT.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-04-17 Cont ID  
Sent By kstevens Date 2003-04-16 Time 17:47 Rev Time 0.33
Received By btrobaug Date 2003-04-17 Time 12:41 Sent To B
Notes
2003-04-17 00:00:00PLEASE NOTE THAT AN ELECTRICAL PERMIT
 IS REQUIRED.SUBMIT AN ELECTRICAL
 SCHEMATIC FOR REVIEW AT TIME OF
 APPLICATION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-21 Time 16:45 Rev Time 0.00
Received By shernand Date 2003-04-21 Time 16:45 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 15:32 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 15:32 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-04-30 Cont ID  
Sent By kstevens Date 2003-04-30 Time 11:15 Rev Time 0.50
Received By kstevens Date 2003-04-30 Time 11:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-23 Cont ID  
Sent By kstevens Date 2003-04-23 Time 11:33 Rev Time 0.50
Received By kstevens Date 2003-04-23 Time 11:33 Sent To B
Notes
2003-04-23 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) FROM PREVIOUS REVIEW:
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 **(SEE ATTACHED SHEET FOR SAMPLE OF DE-
 TAIL FOR ADDRESSING COMMENTS #'S 1 & 2)
 3) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 ***(SEE ATTACHED SHEET FOR EXAMPLE OF
 POOL EQUIP. ANCHORING SLAB.)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) ALL SHEETS OF A SIGNED AND SEALED
 ENGINEERED SET OF PLANS SHALL BE SIGNED
 AND SEALED BY THE ENGINEER OF RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-21 Time 16:45 Rev Time 0.75
Received By kstevens Date 2003-04-16 Time 17:39 Sent To E
Notes
2003-04-16 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)- PIPING SCHEMATIC ON SHT #1
 OF 5 SHOWS TWO WALL DRAINS. POOL PIPING
 LAYOUT SHOW ONE FLOOR MAIN DRAIN AND ONE
 WALL MAIN DRAIN. PLEASE CLAIRFY.
 4) SHT 1 0F 5 - NO SPA PIPING SHOWN ON
 SCHEMATIC. PLEASE REVISE AND RESUBMIT
 SCHEMATIC. ALSO SHOW BLOWER, SPA JET RE-
 TURN ECT.
 5) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 6) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 7) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 8) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 9) ALL SHEETS OF A SIGNED AND SEALED
 ENGINEERED SET OF PLANS SHALL BE SIGNED
 AND SEALED BY THE ENGINEER OF RECORD.
 MANUF. INFO. NOT INCLUDED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 2 Status P Date 2003-04-16 Cont ID  
Sent By sgraham Date 2003-04-16 Time 15:43 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-04-11 Time 15:32 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-04-14 00:00:00DENIED, SIDE SETBACK MUST BE 10'