Plan Review Details - Permit 03040845
Plan Review Stops For Permit 03040845
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-01-08 Cont ID  
Sent By rbrown Date 2004-01-08 Time 12:27 Rev Time 0.00
Received By rbrown Date 2004-01-08 Time 12:27 Sent To  
Notes
2004-01-08 00:00:00SUBMITTAL ON 1/7/04 FOR MECHANICAL SHAFT
 DAMPER AND WALL DETAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-12-16 Cont ID  
Sent By csiegber Date 2004-01-07 Time 10:46 Rev Time 0.00
Received By rbrown Date 2003-12-16 Time 07:50 Sent To FIRE
Notes
2003-12-16 00:00:00REVISION SUBMITTED 11/17/03 FOR BLDG/
 MECH/ELEC

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-11-13 Cont ID  
Sent By rbrown Date 2003-11-13 Time 14:53 Rev Time 0.00
Received By rbrown Date 2003-11-13 Time 14:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-08 Cont ID  
Sent By rbrown Date 2003-05-08 Time 13:06 Rev Time 0.00
Received By rbrown Date 2003-05-08 Time 13:06 Sent To FIRE
Notes
2003-05-08 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FBC 11-4.22TOILET ROOM #106.THE
 PLUMBING PLAN REVIEW COMMENTS, REQUIRING
 THE PLANS TO SHOW ACCESSIBILTY, SHALL BE
 ADDRESSED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-02-09 Cont ID  
Sent By dpalmer Date 2004-02-09 Time 08:15 Rev Time 0.50
Received By dpalmer Date 2004-02-09 Time 08:15 Sent To  
Notes
2004-02-09 00:00:00REV FOR E3,E4,E6

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-09 Cont ID  
Sent By dpalmer Date 2003-12-09 Time 10:33 Rev Time 0.50
Received By dpalmer Date 2003-12-09 Time 10:33 Sent To  
Notes
2003-12-09 00:00:00REV E-3

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-12-02 Time 13:57 Rev Time 0.45
Received By jleahy Date 2003-11-26 Time 08:55 Sent To  
Notes
2003-11-26 00:00:00APLLICATION SAYS E0--E6 BUT ONLY HAD E3,
 E5

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-23 Cont ID  
Sent By dpalmer Date 2003-04-23 Time 17:43 Rev Time 1.00
Received By dpalmer Date 2003-04-23 Time 17:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-02-09 Cont ID  
Sent By nmccray Date 2004-02-09 Time 10:48 Rev Time 0.00
Received By nmccray Date 2004-02-09 Time 10:48 Sent To  
Notes
2004-02-09 00:00:00REVISION DATED AND SEALED 02-03-04 FOR
 SHEET E-3

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-12-16 Cont ID  
Sent By rbrown Date 2003-12-16 Time 15:28 Rev Time 0.00
Received By nmccray Date 2003-12-16 Time 14:26 Sent To B
Notes
2003-12-16 00:00:00REVISION DATED AND SEALED ON 11-14-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-05-13 Cont ID  
Sent By rbrown Date 2003-12-16 Time 08:36 Rev Time 0.00
Received By nmccray Date 2003-05-13 Time 14:30 Sent To  
Notes
2003-05-13 00:00:00*************PROVISO********************
 SEPARATE SHOP DRAWING AND PERMIT APP IS
 REQUIRED FOR FIRE SPRINKLER SYSTEM AND
 FIRE ALARM SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 08:16 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 08:16 Sent To  
Notes
2004-02-05 00:00:00TO COMM BD#16

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-07 Cont ID  
Sent By csiegber Date 2004-01-07 Time 10:46 Rev Time 0.00
Received By csiegber Date 2004-01-07 Time 10:46 Sent To B
Notes
2004-01-07 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-02 Cont ID  
Sent By csiegber Date 2003-12-02 Time 13:57 Rev Time 0.00
Received By csiegber Date 2003-12-02 Time 13:57 Sent To E
Notes
2003-12-02 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-11-17 Time 12:10 Rev Time 0.00
Received By csiegber Date 2003-11-17 Time 12:10 Sent To  
Notes
2003-11-17 00:00:00TO COMM BD#57

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-07 Cont ID  
Sent By csiegber Date 2003-11-07 Time 11:11 Rev Time 0.00
Received By csiegber Date 2003-11-07 Time 11:11 Sent To P
Notes
2003-11-07 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-04-11 Time 10:02 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 10:02 Sent To  
Notes
2003-04-11 00:00:00COMM BOARD #48

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-02-19 Cont ID  
Sent By pkrauss Date 2004-02-19 Time 07:50 Rev Time 0.40
Received By pkrauss Date 2004-02-19 Time 07:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-01-08 Cont ID  
Sent By pkrauss Date 2004-01-08 Time 09:11 Rev Time 0.40
Received By pkrauss Date 2004-01-08 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-12-15 Cont ID  
Sent By pkrauss Date 2003-12-15 Time 13:43 Rev Time 0.15
Received By pkrauss Date 2003-12-15 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-12-05 Cont ID  
Sent By pkrauss Date 2003-12-05 Time 09:39 Rev Time 0.55
Received By pkrauss Date 2003-12-05 Time 08:47 Sent To  
Notes
2003-12-05 00:00:00DENIED:
 PLAN SHEET M-202 STAIR 5 INDICATES DUCT
 PENETRATING STAIRWELL AREA.PLEASE
 CLARIFY, PLAN SHEET A-2.1 INDICATES THE
 STAIRWELL HAS A 2 HR FIRE SEPARATION.
 AS PER 2001 FBC 1006.1.3.1 PENETRATIONS
 THROUGH A STARIWAY ENCLOSURE ARE
 PROHIBITED UNLESS IT IS FOR STAIRWELL
 PRESSURIZATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-03 Cont ID  
Sent By pkrauss Date 2003-05-03 Time 10:45 Rev Time 0.45
Received By pkrauss Date 2003-05-03 Time 10:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-02-06 Cont ID  
Sent By kstevens Date 2004-02-06 Time 17:50 Rev Time 0.50
Received By kstevens Date 2004-02-06 Time 17:50 Sent To  
Notes
2004-02-06 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATION CODE
 FLORIDA STATUTES
  
  
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-11-13 Cont ID  
Sent By kstevens Date 2003-11-13 Time 14:19 Rev Time 2.00
Received By kstevens Date 2003-11-13 Time 14:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-29 Cont ID  
Sent By csiegber Date 2003-11-07 Time 11:11 Rev Time 1.50
Received By kstevens Date 2003-04-29 Time 15:17 Sent To  
Notes
2003-04-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE ROUTE PLANS TO DEPT OF BUSIN-
 ESS REGULATION HOTEL AND RESTAURANT DIV.
 (954) 958-5520 PRIOR TO RESUBMITTING.
 PLANS TO BE STAMPED AND WORK SHEETS
 ATTACHED.
 2) NEW TOILET ROOM #106, PLEASE PROVIDE
 DETAIL SHOWING COMPLIANCE WITH 11-4.22
 AND ALL SUBSECTIONS.
 3) NEW TOILET ROOM #106, DOOR SHALL NOT
 OPEN INTO THE CLEAR FLOOR SPACE OF ANY
 FIXTURE. PLEASE SHOW CLEAR FLOOR SPACE
 FOR LAV.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692