Plan Review Stops For Permit 03040783 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2003-06-09 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-27 |
Time |
15:12 |
Rev Time |
1.00 |
Received By |
sthyng |
Date |
2003-06-09 |
Time |
18:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-05-15 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-06-09 |
Time |
13:18 |
Rev Time |
3.00 |
Received By |
sthyng |
Date |
2003-05-14 |
Time |
15:15 |
Sent To |
|
|
Notes |
2003-05-14 00:00:00 | *******CORRECTIONS********* | | | | 1.)PROVIDE PRODUCT APPROVALS FOR THE | | 2'0X6'8" EXTERIOR DOOR. | | | | 2.)THE PRODUCT APPROVAL SUBMITTED FOR | | THE FRONT ENTRY DOOR IS FOR SOLID DOORS, | | BUT THE HURRICANE SHUTTER SCHEDULE SHOWS | | HURRICANE SHUTTERS IN THAT LOCATION.IF | | THIS DOOR IS TO BE GLAZED, SUBMIT A | | PRODUCT APPROVAL FOR THE DOOR TO BE | | INSTALLED. | | | | 3.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 4.)THE ROOF SHEATHING ATTACHMENT | | SCHEDULE ON SHEET 9 IS ILLEGIBLE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2003-06-30 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-06-30 |
Time |
13:41 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-06-30 |
Time |
13:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-06-05 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-27 |
Time |
15:14 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-06-05 |
Time |
10:28 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-04-23 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-04 |
Time |
12:14 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-04-23 |
Time |
18:19 |
Sent To |
P |
|
Notes |
2003-04-23 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | HAND DRAWN CHANGES TO PLANS ARE NOT | | ACCEPTABLE.RETURN TO THE ENGINEER OF | | RECORD TO HAVE CHANGES MADE,AND | | RESUBMIT FOR REVIEW. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2003-06-27 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-27 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-27 |
Time |
15:12 |
Sent To |
E |
|
Notes |
2003-06-27 00:00:00 | BT DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-06-04 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-04 |
Time |
12:14 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-04 |
Time |
12:14 |
Sent To |
E |
|
Notes |
2003-06-04 00:00:00 | BT DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-04-10 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-10 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-10 |
Time |
12:04 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2003-06-09 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-06-09 |
Time |
13:18 |
Rev Time |
0.15 |
Received By |
pkrauss |
Date |
2003-06-09 |
Time |
13:09 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2003-05-15 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-06-05 |
Time |
10:48 |
Rev Time |
0.15 |
Received By |
pkrauss |
Date |
2003-05-05 |
Time |
08:55 |
Sent To |
B |
|
Notes |
2003-05-05 00:00:00 | DENIED:MECHANICAL PERMIT 03040793 | | | | 1.PROVIDE INFORMATION ON THE EXHAUST | | FANS INSTALLED IN THE BATHROOMS - | | (MAKE, MODEL, CFM & ELEC INFORMATION). | | | | 2.SHOULD GAS DRYER BE INSTALLED, | | PROVIDE INFORMATION FOR COMBUSTION AIR | | IF NEEDED. | | | | 3.PROVIDE OUTSIDE AIR CALCS AS PER | | 2001 FBC(M) 402.2 (NATURAL) OR TABLE | | 403.3 (MECHANICAL). | | | | 4.FAN SHUTDOWN REQUIRED AT FINAL | | INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2003-04-23 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-04-23 |
Time |
18:26 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2003-04-23 |
Time |
18:30 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-05-07 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-10 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-07 |
Time |
10:08 |
Sent To |
B |
|
Notes |
2003-05-07 00:00:00 | PLANS WERE PASSED AND STAMPED BY | | SHIRLEY GRAHAM. |
|
|