2003-05-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-PROVIDE IMPACT FEES PAID RECEIPT. |
| 2-OWNER AND CONTRACTOR INFORMATION DON'T |
| MATCH. PERMIT APPLICATION, ENERGY |
| CALCULATIONS AND INFORMATION FROM PAPA |
| IS DIFFERENT. CORRECT AS REQUIRED. |
| 3-SECTION/DETAIL AT GARAGE INTERIOR |
| BEARING WALL IS MISSING INFORMATION. |
| SEE COMMENTS ON REVIEWED SET. |
| 4-PROVIDE SOIL TEST REPORT. |
| 5-REVISE/CLARIFY NOTE #1 ON SHEET A-4. |
| HANDRAIL & GUARDRAIL ARE NOT THE SAME. |
| SEE SEC. 1007.5.1 FOR HANDRAIL HEIGHT. |
| 6-REVISE DETAIL 4/S-2 TO MATCH FLOOR |
| FRAMING PLAN. COLUMN IS RECEIVING TWO |
| GIRDERS, BUT DETAIL ONLY SHOW SUPPORT |
| FOR ONE GIRDER. SECTION 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 7-ENERGY CALCULATIONS: A)REVISE OWNER & |
| CONTRACTOR INFORMATION. B)COMPLETE |
| TOP OF FORM INCLUDING ADDRESS OF HOUSE |
| 8-SPECIFY CONNECTOR FOR TRUSS ON DETAIL |
| 1/S-2. SEC. 104.2.1.2 CITY AMENDMENTS. |
| 9-CLARIFY DETAIL C/S-2. HOW IS THIS |
| BUCKET ATTACHED TO THE CORNER OF NOOK |
| AREA WALL. PROVIDE DETAIL SHOWING THE |
| EDGE OF THE WALL AND THE CLEARANCES. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 10-REVISE DETAIL E/S-3 SPECIFIED ON ROOF |
| PLAN ABOVE MASTER BEDROOM. THIS IS |
| MASONRY CONSTRUCTION NOT WOOD FRAME. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 11-SHEET A-4: CLARIFY EXTERIOR STUCCO |
| SOFFIT SPECIFICATIONS NOTES. SOME ARE |
| REPETITIVE AND SOME ARE MISSING INFO. |
| SEE ASTM C-1063 AND PROVIDE CLEAR |
| SPECIFICATIONS WITH SIZE OF FASTENER |
| AND SPACING. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 12-SHEET A-5. WOOD FRAME TO CONCRETE |
| WALL CONNECTION DETAIL: A)MISSING HOW |
| MUCH EMBEDMENT FOR ANCHORS.B)UPDATE |
| SEMCO CONNECTOR. SECTION 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 13-2ND FLOOR FRAMING PLAN & ROOF FRAMING |
| PLAN ARE MISSING SOME CONNECTORS. SEE |
| PLANS FOR COMMENTS. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |