Plan Review Details - Permit 03040608
Plan Review Stops For Permit 03040608
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-27 Cont ID  
Sent By rmcdouga Date 2003-05-23 Time 13:31 Rev Time 3.00
Received By rmcdouga Date 2003-05-23 Time 13:31 Sent To  
Notes
2003-05-23 00:00:00BUILDING PROVISO
  
 1) PROVIDE A LETTER OR REVISED DRAWING
 FROM THE ARCHITECT ADDRESSING THE UPLIFT
 VALUE FOR THE HTA 16-18 CONNECTOR IN
 DETAIL B ON S2 AND CLARIFICATION OF THE
 CONNECTORS FOR THE TRUSSES OVER THE
 GARAGE BEFORE INSTALLING THE TRUSSES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-12 Cont ID  
Sent By shernand Date 2003-05-21 Time 12:42 Rev Time 4.00
Received By rmcdouga Date 2003-05-12 Time 13:07 Sent To  
Notes
2003-05-12 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT THE RECEIPT FOR THE COUNTY
 IMPACT FEES.
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMENDMENTS TO THE FBC
 1804.2.2.
  
 4) REVISE ITEM #7 UNDER STUCCO SPECS. ON
 A-3 TO REQUIRE FASTENING AT EVERY RIB
 (4"O.C.) AS REQUIRED BY ASTM C 1063.
 ITEMS #4 AND #5 ARE THE SAME NOTE.
  
 5) THE CONDITIONED AREA ON THE ENERGY
 CALCULATIONS IS 2292 SQFT AND THE PLANS
 LIST 2260 SQFT OF A/C SPACE. PLEASE
 CORRECT.
  
 6) REVISE THE TRUSS CONNECTOR UPLIFT
 VALUES TO VALUES THAT DO NOT INCLUDE THE
 STRESS INCREASE ON THE STEEL CALCS.
 WHICH ARE NO LONGER ALLOWED BY THE FBC.
  
 7) SUBMIT PRODUCT APPROVALS FOR A SINGLE
 OUTSWING DOOR WITH SIDELITE.
  
 8) THE OWNER OF RECORD INDICATED ON THE
 PERMIT APPLICATION IS INTELLI HOMES,
 HOWEVER THE COUNTY PROPERTY APPRAISER
 AND THE CITY RECORDS LIST TIDES PALM
 BEACH LTD PARTENERSHIP AS THE OWNER.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-02 Cont ID  
Sent By btrobaug Date 2003-09-02 Time 14:50 Rev Time 0.50
Received By btrobaug Date 2003-09-02 Time 14:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-23 Cont ID  
Sent By csiegber Date 2003-08-25 Time 08:29 Rev Time 0.50
Received By btrobaug Date 2003-04-23 Time 15:46 Sent To M
Notes
2003-04-23 00:00:00REDLINED 250-66 & 220-16 B./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 08:29 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 08:29 Sent To E
Notes
2003-08-25 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shernand Date 2003-05-21 Time 12:42 Sent To  
Notes
2003-05-21 00:00:00RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-15 Cont ID  
Sent By shernand Date 2003-04-15 Time 13:42 Rev Time 0.00
Received By shernand Date 2003-04-15 Time 13:42 Sent To Z
Notes
2003-04-15 00:00:00SUBMITTAL FOR SURVEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-09 Cont ID  
Sent By shernand Date 2003-04-09 Time 09:14 Rev Time 0.00
Received By shernand Date 2003-04-09 Time 09:14 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-23 Cont ID  
Sent By btrobaug Date 2003-04-23 Time 16:19 Rev Time 0.50
Received By hmoser Date 2003-04-23 Time 18:27 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-21 Cont ID  
Sent By alange Date 2003-04-21 Time 18:53 Rev Time 0.33
Received By alange Date 2003-04-21 Time 18:53 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-04-15 Time 13:42 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***