Plan Review Details - Permit 03040233
Plan Review Stops For Permit 03040233
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-04-09 Cont ID  
Sent By btrobaug Date 2003-04-08 Time 19:02 Rev Time 0.50
Received By lsmith Date 2003-04-09 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-08 Cont ID  
Sent By kstevens Date 2003-04-08 Time 08:09 Rev Time 0.33
Received By btrobaug Date 2003-04-08 Time 18:53 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-07 Cont ID  
Sent By shernand Date 2003-05-07 Time 14:12 Rev Time 0.00
Received By shernand Date 2003-05-07 Time 14:12 Sent To P
Notes
2003-05-07 00:00:00KSTEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-10 Cont ID  
Sent By shernand Date 2003-04-10 Time 16:53 Rev Time 0.00
Received By shernand Date 2003-04-10 Time 16:53 Sent To P
Notes
2003-04-10 00:00:00KSTEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 16:10 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 16:10 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-05-14 Cont ID  
Sent By kstevens Date 2003-05-14 Time 10:50 Rev Time 0.75
Received By kstevens Date 2003-05-14 Time 10:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-05-07 Time 14:12 Rev Time 0.33
Received By kstevens Date 2003-04-16 Time 13:50 Sent To  
Notes
2003-04-16 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 ANY CHANGES TO A SIGNED AND SEALED SET
 OF PLANS SHALL BE SIGNED AND DATED BY
 THE ENGINEER OF RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-04-10 Time 16:53 Rev Time 0.33
Received By kstevens Date 2003-04-08 Time 08:06 Sent To E
Notes
2003-04-08 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 2) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 4) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-07 Cont ID  
Sent By shernand Date 2003-04-03 Time 16:10 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***