Plan Review Details - Permit 03040127
Plan Review Stops For Permit 03040127
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-28 Cont ID  
Sent By jwitmer Date 2003-05-28 Time 16:22 Rev Time 1.55
Received By jwitmer Date 2003-05-28 Time 16:22 Sent To  
Notes
2003-05-28 00:00:00BUILDING PROVISO:
 BEDROMM# 3, EGRESS WINDOW
 SH34+4 OR 34.5

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-01 Cont ID  
Sent By pkrauss Date 2003-05-24 Time 08:41 Rev Time 3.25
Received By jwitmer Date 2003-05-01 Time 10:34 Sent To  
Notes
2003-05-01 00:00:00 
  
 BUILDING PLAN REVIEW
 PERMIT: 03040127
 ADD: 8198 SPYGLASS
 CONT: WESTBROOKE
 TEL: (786)367-7362
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION : DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE
 EXPLORATIONS, TESTS OR OTHER ADEQUATE
 PROOF AS TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TESTS AND RECOMMENDAT
 IONS SUBMITTED TO VERIFY BEARING CAPAC-
 ITY SHALL BE CERTIFIED BY BY A GEO TECH-
 NICAL REPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) *********NOTE ************
 ONLY FOR CONSIDERATION , FUTURE POOL
 1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.
  
 4) NOTE: SHEET A-1 DETAIL 38 INDICATES
 A FOUNDATION WITH LESS THAN 12" BELOW
 GRADE, 1804.1.3 INDICATES THIS IS A MINI
 MUM, SINCE THE ARCHITECT HAS DESIGNED &
 SEALED THIS PLAN, THE ARCHITECT RESUMES
 FULL RESPONSIBLIITY FOR THE DESIGN.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A-1,A-3, A-6 DETAIL(6):
 OPENING 8, 8A SLIDING GLASS DOOR AT THE
 FAMILY ROOM, THE PLAN INDICATES THE USE
 OF (TS-1) TUBE STEEL AND TO SEE DETAIL
 12 OF SHEET 6, THIS DETIAL, DETAIL 11
 WOULD BE ACCURATE BUT WHAT IS THE TUBE
 STEEL USED FOR?
  
 6) SHEET A-5 TRUSS CONNECTOR SCHEDULE:RE
 FERS TO USP 2001 CATALOG.SEE 2003 CATA-
 LOG "VALUES REPRESENT LOADS WHICH DO NOT
 INCLUDE STRESS INCRESS ON STEEL".
 FLORIDA SPECIFIC CODE:
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 RE-EVALUATE TRUSS TABLES WITH NEW LOAD
 REDUCTIONS!
  
 7)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 8) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOWS SINGLE HUNG / FIXED
 B) MULLIONS
 C) EXTERIOR DOORS/ GLAZED OPENINGS
 D) EXTERIOR DOORS/ SOLID
 E) OVERHEAD GARAGE DOORS
 F) ROOF ASSEMBLIES
 G) STORM SHUTTERS
  
 9)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 12)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 13)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 14) NOTE : ARCHITECT RESUME FULL RESPONS
 IBILITY FOR WINDOW / DOOR ATTACHMENT IF
 ATTACHMENT IS LESS RESTRICTIVE THAN SPEC
 IFIED BY TESTING REPORTS:
 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 15) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-22 Cont ID  
Sent By btrobaug Date 2003-12-22 Time 08:24 Rev Time 0.50
Received By btrobaug Date 2003-12-22 Time 07:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-21 Cont ID  
Sent By alange Date 2003-12-18 Time 14:36 Rev Time 0.50
Received By btrobaug Date 2003-05-21 Time 14:38 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-10 Cont ID  
Sent By shernand Date 2003-05-21 Time 14:30 Rev Time 0.33
Received By dpalmer Date 2003-04-10 Time 04:25 Sent To P
Notes
2003-04-10 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SIZE FEEDER FROM MAIN
 TO PANEL PER 310-15/310-16. SHOWN AS#2?
  
 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE.
 PER 210-12
  
 3)NOTE: PLEASE SEE MISSING RECEPT ON
 KITCHEN COUNTERSPACE. PER 210-52C-1
  
 4)NOTE: PLEASE ALSO SEE MISSING RECEPT
 FOR KITCHEN ISLAND. 210-52C-2
  
 5)NOTE: PLEASE MOVE SD INTO MASTER
 BEDROOM AREA.SD NOT TO BE IN BATHS/
 AREAS NFPA-72 8-1.4.2
  
 6)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 ON PLAN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW
 561-659-8096 EXT8372
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-18 Cont ID  
Sent By alange Date 2003-12-18 Time 14:36 Rev Time 0.00
Received By alange Date 2003-12-18 Time 14:36 Sent To E
Notes
2003-12-18 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-22 Time 12:17 Rev Time 0.00
Received By csiegber Date 2003-10-22 Time 12:17 Sent To M
Notes
2003-10-22 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 14:30 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 14:30 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 10:17 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 10:17 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-10-22 Cont ID  
Sent By hmoser Date 2003-10-22 Time 19:09 Rev Time 0.50
Received By hmoser Date 2003-10-22 Time 19:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-24 Cont ID  
Sent By csiegber Date 2003-10-22 Time 12:20 Rev Time 0.35
Received By pkrauss Date 2003-05-24 Time 08:35 Sent To B
Notes
2003-05-24 00:00:00MECHANICAL PERMIT 03040195

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-04-19 Cont ID  
Sent By btrobaug Date 2003-05-21 Time 14:42 Rev Time 0.33
Received By rregueir Date 2003-04-19 Time 11:52 Sent To B
Notes
2003-04-19 00:00:00DENIED
  
 EQUIPMENT SEER ON ENERGY CALCS DOES NOT
 MATCH THAT OF EQUIPMENT LISTED ON
 PLANS. REVISE AND RESUBMIT INFORMATION
 AS NEEDED TO CORRECT DISCREPANCY.
 REVIEWED BY: RONALD J REGUEIRO
 561-805-6734

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-16 Cont ID  
Sent By dpalmer Date 2003-04-10 Time 04:25 Rev Time 0.33
Received By jleech Date 2003-04-16 Time 18:10 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 10:17 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved