2003-04-28 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS WITH UPDATED SBCCI REPORT |
| THAT MATCHES ENGINEERED DRAWINGS. |
| CHECK DESIGN PRESSURES AND MAX/MIN |
| PANEL SPAN SHOWN ON THE INSTALLATION |
| SCHEDULE AND THOSE SHOWN ON ENGINEERED |
| DRAWINGS AND REVISE AS REQUIRED.SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 2-REVISE DETAIL S21 FOR COLUMN BETWEEN |
| GARAGE AND STAIRWAY TO MATCH CONDITION |
| SHOWN ON 2ND FLOOR FRAMING PLAN. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 3-REVISE CONNECTOR TC-1 SHOWN ON ROOF |
| FRAMING PLAN FOR FRONT FRAMED WALL. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 4-WINDOW 34SH DOESN'T PROVIDE THE 24" |
| CLEAR HEIGHT REQUIRED BY SEC. 1005.4 |
| FBC 2001. REVISE AS REQUIRED. |
| ALSO, MAKE CHECK THAT WINDOW SH24+5 |
| PROVIDES 24" CLEAR HEIGHT AND 5.7 S.F. |
| CLEAR OPENING. SEC. 1005.4 FBC 2001. |
| 5-RESUBMIT ENERGY CALCULATIONS WITH THE |
| ENGINEER'S ORIGINAL SIGNATURE & SEAL. |
| CHAPTER 471 FLORIDA STATUTES AND SEC. |
| 103.0 CHAPTER 13 FBC 2001. |