Plan Review Details - Permit 03040061
Plan Review Stops For Permit 03040061
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-28 Cont ID  
Sent By jwitmer Date 2003-05-28 Time 11:09 Rev Time 1.25
Received By jwitmer Date 2003-05-28 Time 11:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-14 Cont ID  
Sent By jwitmer Date 2003-04-14 Time 13:27 Rev Time 0.88
Received By jwitmer Date 2003-04-14 Time 13:27 Sent To  
Notes
2003-04-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03040061
 ADD: 2316 S DIXIE HWY
 CONT: MIKE MOORE CONST
 TEL: (561)745-1054
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) WHAT TYPE OF OCCUPANCY IS THIS STRUC-
 TURE TO BE USED FOR? EXITING MERCANTILE
 VS BUSSINESS SEE EXCEPTIONS 1018.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 IDENTIFY ROOM USAGE?
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 4)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-16 Cont ID  
Sent By dpalmer Date 2003-05-16 Time 12:44 Rev Time 0.25
Received By dpalmer Date 2003-05-16 Time 12:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-10 Cont ID  
Sent By dpalmer Date 2003-04-10 Time 06:36 Rev Time 0.50
Received By dpalmer Date 2003-04-10 Time 06:36 Sent To  
Notes
2003-04-10 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE, SHOW
 FOUR COND UNITS? PLEASE ALSO SEE OCP
 SHOWN AS 2-P 30A,PLEASE SEE 7.5KW LOAD
 SHOWN FOR AHU/HEAT. PLEASE CORRELATE
 AND SIZE OCP PER 424-3
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE. 215-5
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215-3/230-42 ETC.
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT REQ`D PER 600-5
  
 5)NOTE: PLEASE SEE 700-12E FOR CIRCUIT-
 -ING FO EM/EXT LTS. SAME AS GEN LTS.
  
 6)NOTE: PLEASE CLARIFY/SHOW NEW OR EXIST
 -ING SHOW WINDOW RECEPTS 210-62/220-12
  
 7)NOTE: PLEASE SEE SEE SIZE OPENING FOR
 ACCESS TO ELECTRICAL ROOM, @ 1/8 SCALE
 IT APPEARS DOOR IS LESS THAN 2' WIDE?
 110-26
  
 8)NOTE: PLEASE NOTE, MAX OCP FOR WATER
 HEATER CAN NOT EXCEED 150% OF LOAD.
 WATER HEATER IS SHOWN AS HAVING 40A
 OCP.422-11
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]
  
 9)NOTE: PLEASE CLARIFY REQ`D ROOFTOP
 RECEPT. 210-63

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-05-22 Cont ID  
Sent By mcarsill Date 2003-05-22 Time 16:39 Rev Time 0.00
Received By mcarsill Date 2003-05-22 Time 16:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-04-11 Cont ID  
Sent By mcarsill Date 2003-04-11 Time 14:37 Rev Time 0.00
Received By mcarsill Date 2003-04-11 Time 14:36 Sent To  
Notes
2003-04-11 00:00:001) WHAT IS THE REAR ROOM TO BE USED FOR.
  
 2) PLEASE LABEL VARIOUS AREAS.
  
 3) WHAT IS THE SPACE USED FOR PRESENTLY.
  
 4) PLEASE INDICATE AN OCCUPANT LOAD.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 09:25 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 09:24 Sent To  
Notes
2003-05-14 00:00:00COMM BOARD #7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 11:35 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 11:34 Sent To  
Notes
2003-04-03 00:00:00COMM BOARD #9

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-05-19 Cont ID  
Sent By pkrauss Date 2003-05-19 Time 16:21 Rev Time 0.35
Received By pkrauss Date 2003-05-19 Time 16:21 Sent To  
Notes
2003-05-19 00:00:00NO MECHANICAL TO BE DONE UNDER THIS
 PERMIT.HVAC IS EXISTING.PLEASE NOTE
 OUTSIDE AIR CALCS REQUIRED FOR CHANGE
 OF OCCUPANCY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-04-12 Cont ID  
Sent By hmoser Date 2003-04-12 Time 10:39 Rev Time 1.00
Received By hmoser Date 2003-04-12 Time 10:38 Sent To  
Notes
2003-04-12 00:00:00PLAN DENIED
 1) NO EQUIPMENT SECHEDULE
 2) NO DUCTSIZE,GRILL SIZE,OR CFM.ON
 PLANS
 3) NEED FRESH AIR CALCULATIONS
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-04-12 Cont ID  
Sent By kstevens Date 2003-04-12 Time 13:49 Rev Time 0.25
Received By kstevens Date 2003-04-12 Time 13:49 Sent To  
Notes
2003-04-12 00:00:00NO PLUMBING PLANS SUBMITTED - FIXTURE
 SET ONLY