Plan Review Stops For Permit 03032421 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2003-06-24 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2003-06-24 |
Time |
17:57 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2003-06-24 |
Time |
17:57 |
Sent To |
PC |
|
Notes |
2003-06-24 00:00:00 | IMPACT FEES PAID. PLANS APPROVED WITH | | PROVISO. SEE DRAWING A-2. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
|
Date |
2003-06-17 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-24 |
Time |
16:33 |
Rev Time |
3.00 |
Received By |
jgomez |
Date |
2003-06-17 |
Time |
17:46 |
Sent To |
PC |
|
Notes |
2003-06-17 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE SOIL TEST REPORT PRIOR TO | | CONSTRUCTION. SOIL TEST REPORT IN FILE | | IS PRELIMINARY ONLY AND IT REQUIRES | | ADDITIONAL BORINGS TO BE PERFORMED. | | SEE LIMITATIONS ON PRELIMINARY REPORT. | | 2-UPDATE TRUSS ANCHOR SCHEDULE AND ALL | | DETAILS THAT ARE AFFECTED BY SECTION | | 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW | | THE STRESS INCREASE TO BE USED. | | **NOTE: ANCHORS HIGHLIGHTED ON THE USP | | 2003 CATALOGUE ARE THE ONLY ONES THAT | | DON'T INCLUDE THE INCREASE. OTHERS DO. | | SEE FOOTNOTE ON USP 2003 CATALOGUE. | | 3-REVISE DETAIL 2/A3. THIS CAN NOT BE A | | BEARING WALL ACCORDING TO THE SPECS | | SHOWN. SEC. 104.2.1.2 CITY AMENDMENTS | | TO FBC 2001. | | 4-MISSING PRODUCT APPROVAL FOR SINGLE | | HUNG WINDOWS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2003-05-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-06-14 |
Time |
07:54 |
Rev Time |
3.00 |
Received By |
jgomez |
Date |
2003-05-28 |
Time |
08:49 |
Sent To |
|
|
Notes |
2003-05-28 00:00:00 | CHECKLIST: | | 1-PROVIDE COPY OF THE SOIL TEST REPORT. | | 2-ENERGY CALCULATIONS NEED TO BE SITE | | SPECIFIC OR CALCULATED FOR THE WORST | | CASE SCENARIO. REVISE AS REQUIRED. | | 3-NEED TO UPDATE WORKER'S COMPENSATION | | INSURANCE. | | 4-PAY IMPACT FEES AND FILE NOTICE OF | | COMMENCEMENT. | | 5-SPECIFICATIONS FOR FIREBLOCKING DON'T | | APPLY ONLY TO CONCEALED SPACES UNDER | | STAIRS, BUT TO ALL CONCEALED SPACES | | IN THE BUILDING. SEE SEC. 2305 FBC | | 2001 AND REVISE AS REQUIRED. | | 6-SHEET A-6: A)REVISE HANDRAIL HT. SEE | | SEC. 1007.5.1 FBC 2001. | | B)THERE ARE NOT SPECS FOR RISER HEIGHT. | | SEE SEC. 1007.3.1 (EXCEPTION #1). | | C)TYPICAL TWO STORY WALL SECTION IS | | MISSING ALL THE CONNECTORS TOP & BOTT. | | FOR 2X FRAMED WALL. SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | **NEED 7/8" MIN. STUCCO THICKNESS AS | | REQUIRED BY ASTM C-926. | | **REVISE WALL SHEATHING THICKNESS. SEE | | DIAPHRAGM SCHEDULE ON SHEET A-9. | | **SEE PLANS FOR ADDITIONAL COMMENTS. | | 7-CLARIFY WHAT IS THE DETACHABLE SAFETY | | RAIL SPECIFIED ON ELEVATION ON SHEET | | A-4 AND WHERE IS IT GOING TO BE | | INSTALLED. SEC. 104.2.1.2 CITY AMENDM. | | 8-UPDATE TRUSS SCHEDULE. 33% ALLOWABLE | | STRESS INCREASE IS NOT ALLOWED BY SEC. | | 1609.4.3 FBC 2001. SEE USP 2003 | | CATALOGUE WITH REVISED LOADS AND | | REVISE AS REQUIRED. | | 9-PROVIDE COMPLETE DETAILS & STRUCTURAL | | INFORMATION FOR PRECAST GUARDRAIL | | INSTALLATION. DETAIL PROVIDE IS NOT | | COMPLETE. SEE SEC. 1608.2.2 FBC 2001. | | 10-FOUNDATION PLAN: CLARIFY FOOTING AT | | GARAGE INTERIOR BEARING WALL. IS IT | | F8 OR TE-17? SEE PLAN. | | 11-THERE ARE SOME CONNECTORS THAT ARE NO | | SPECIFIED. SEE FRAMING PLAN FOR | | COMMENTS. SEC. 104.2.1.2 CITY AMENDM. | | 12-FRAMING DETAIL FOR ARCHED OPENINGS | | NEED TO HAVE 2X BLOCKS, NOT 1X BLOCKS | | TO PROVIDE STRUCTURAL SUPPORT FOR | | WINDOW. SEC. 104.2.1.2 CITY AMENDMENTS | | TO FBC 2001. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
|
Date |
2003-05-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-05-24 |
Time |
09:29 |
Rev Time |
4.00 |
Received By |
jgomez |
Date |
2003-05-01 |
Time |
10:40 |
Sent To |
|
|
Notes |
2003-05-01 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE SOIL TEST REPORT PRIOR TO | | CONSTRUCTION. | | 2-SHEET C-1: SPECIFY THE APPLICABLE | | INTERNAL PRESSURE COEFFICIENT ON THE | | DESIGN INFORMATION AS REQUIRED BY SEC. | | 1606.1.7 FBC 2001. | | 3-PROVIDE COMPLETE DETAIL/SPECIFICATIONS | | FOR HANGING AIR HANDLER UNIT FROM | | TRUSSES. SPECIFY ALL FASTENERS. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | 4-PROVIDE SPECIFICATIONS FOR FIREBLOCK'G | | AT ALL CONCEALED SPACES AS REQUIRED BY | | SEC. 2305 FBC 2001. INCLUDING STAIRS. | | 5-PROVIDE COMPLETE DETAILS AND SPECS FOR | | HANDRAIL HEIGHT AND OPENINGS ALLOWANCE | | AS REQUIRED BY SEC. 1007.5 FBC 2001. | | 6-SPECIFY SAFETY GLASS FOR WINDOW AT | | COVERED ENTRY. SEC. 2405.2 FBC 2001. | | 7-CLARIFY WHAT IS THE DETACHABLE SAFETY | | RAIL SPECIFIED ON ELEVATION ON SHEET | | A-4. SEC. 104.2.1.2 CITY AMENDMENTS. | | 8-UPDATE TRUSS SCHEDULE. SEE UPDATED | | USP CATALOGUE (2003). ALSO, PROVIDE | | ENGINEERING CALCULATIONS FOR VALUES | | OTHER THAN THOSE SHOWN BY USP. SECTION | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | **NOTE: ALSO CONSIDER THAT IF USING 10D | | NAILS, THEN IT NEEDS 1 3/4" MINIMUM | | PENETRATION TO USE THIS VALUES. ONE | | TRUSS DOESN'T HAVE THIS THICKNESS. | | 9-ROOF FRAMING PLAN: REVISE CONNECTORS | | SPECIFIED FOR FRAMED WALLS. NEED WOOD | | TO WOOD CONNECTORS. SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | 10-PROVIDE COMPLETE DETAILS & STRUCTURAL | | INFORMATION FOR PRECAST GUARDRAIL TO | | BE USED ON 2ND FLOOR BALCONY.SECTION | | 1015 FBC 2001 AND SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | 11-SHEET A-1: CLARIFY FOOTING AT GARAGE | | INTERIOR BEARING WALL. F8 OR TE-1?. | | DETAIL #2 DOESN'T APPLY AT GARAGE. | | REVISE AS REQUIRED. | | DETAIL 38 NEED 12" MIN. BELOW GRADE. | | 12-PROVIDE COMPLETE/CORRECT INFORMATION | | FOR STORM SHUTTERS UNDER A SEPARATE | | PERMIT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2004-06-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-06-15 |
Time |
10:43 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-06-15 |
Time |
10:43 |
Sent To |
|
|
Notes |
2004-06-15 00:00:00 | MISSING EQUIPMENT GROUNDING FROM MAIN | | PANEL TO 60A SUB PANEL. | | REDLINED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2003-07-14 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2004-06-14 |
Time |
15:33 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2003-07-14 |
Time |
12:54 |
Sent To |
|
|
Notes |
2003-07-14 00:00:00 | ************ NOTE ********* | | | | PLANS STILL SHOW WRONG GROUNDING ELEC- | | -TRODE COND. 310-15/250-66 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-05-16 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-07 |
Time |
12:02 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2003-05-16 |
Time |
15:54 |
Sent To |
P |
|
Notes |
2003-05-16 00:00:00 | PLANS STILL SHOW WRONG SIZE ELECTRODE | | GROUNDING CONDUCTOR. NEEDS TO BE #2 | | 250-66 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-04-10 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-15 |
Time |
16:35 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2003-04-10 |
Time |
03:34 |
Sent To |
P |
|
Notes |
2003-04-10 00:00:00 | ************* UNSAT *************** | | | | 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | CONDUCTOR PER 250-66. PLEASE NOTE, SEC`S | | ARE BASED ON 310-15FOR 400A SERVICE. | | | | 2)NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR | | PANEL "C" AS SHOWN ON RISER? | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | GROUNDING COND FROM MAIN DISC TO PANEL | | "B". 250-122 | | | | 4)NOTE: SD NOT PERMITTED IN KITCHEN | | PER NFPA-72 8-1.4.2 | | | | 5)NOTE: PLEASE SEE 220-16 FOR MIN KW FOR | | WASHER CIRCUIT. 1.5KW | | | | 6)NOTE: PLEASE SEE MISSING REQ`DBATH | | CIRCUIT(S) 210-52D/210-11C-3 | | | | PLEASE VERIFY SIZE OF SERVICE WITH | | CONTRACTOR. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEYPALMER | | ELECTRICAL PLANREVIEW | | 561-659-8096 EXT 8372 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2004-06-14 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2004-06-14 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2004-06-14 |
Time |
15:33 |
Sent To |
E |
|
Notes |
2004-06-14 00:00:00 | TO DP DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2003-07-07 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-07 |
Time |
12:02 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-07-07 |
Time |
12:02 |
Sent To |
E |
|
Notes |
2003-07-07 00:00:00 | DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2003-06-24 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-24 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-24 |
Time |
16:33 |
Sent To |
B |
|
Notes |
2003-06-24 00:00:00 | JGOMEZ DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2003-06-11 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-11 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-11 |
Time |
09:45 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-05-15 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-15 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-15 |
Time |
16:35 |
Sent To |
E |
|
Notes |
2003-05-15 00:00:00 | DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-04-01 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-04-01 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
sthyng |
Date |
2003-04-01 |
Time |
10:30 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-04-19 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2003-04-16 |
Time |
16:40 |
Rev Time |
0.33 |
Received By |
rregueir |
Date |
2003-04-19 |
Time |
11:59 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2003-06-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-06-14 |
Time |
07:54 |
Rev Time |
0.25 |
Received By |
kstevens |
Date |
2003-06-14 |
Time |
07:54 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2003-05-24 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-11 |
Time |
09:45 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2003-05-24 |
Time |
09:17 |
Sent To |
B |
|
Notes |
2003-05-24 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) SANITARY RISER DIAGRAM DOES NOT RE- | | FLECT FLOOR PLAN, AND DOES NOT MEET CODE | | 2) EXTRA LAV IN MASTER BATH NOT SHOWN ON | | FLOOR PLAN. | | 3) CANNOT ROUTE DRAINAGE FROM M/BATH TUB | | AND LAV IN TWO DIRECTIONS. SEE RED LINE | | CORRECTIONS ON PLANS AND MAKE CORRECTION | | 4) NOTE: ALL RISERS ON THIS MODEL HAVE | | BEEN REVERSED. PLEASE SUBMIT A RISER | | DIAGRAM THAT REFLECTS THE FLOOR PLAN OF | | THIS MODEL. IT WILL HELP EXPEDITE THE | | PLAN REVIEW PROCESS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-04-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-05-16 |
Time |
16:12 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2003-04-16 |
Time |
16:40 |
Sent To |
M |
|
Notes |
2003-04-16 00:00:00 | DENIED; | | PAGE A-1 PLUMBING RISER DIAGRAM NOT TO | | CODE. SEC. 909.1. WET VENTS FOR BATHROOM | | S ARE PERMITED TO VENT ONLY BATHROOM | | FIXTURES. WASHING MACHINE AND LAUNDRY | | TUB ARE REQUIRED TO DISCHARGE DOWN | | STREAM OF THE BATHROOM GROUP. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT 8369 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-04-03 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-04-01 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
E |
|
Notes |
|
|