Plan Review Details - Permit 03032368
Plan Review Stops For Permit 03032368
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-03-06 Cont ID  
Sent By shill Date 2004-03-05 Time 15:51 Rev Time 1.00
Received By shill Date 2004-03-05 Time 15:51 Sent To  
Notes
2004-03-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEPARATE PERMIT REQUIRED FOR THE
 IMPACT GLASS, SEE ATTACHED PERMIT
 APPLICATION.PRODUCT INFORMATION
 NOT SUBMITTED PRIOR TO PERMIT ISSUANCE
 REQUIRES SEPARATE PERMITS AND REVIEW.
  
 2.)THE SITE SPECIFIC PRODUCT
 APPROVAL FORM IS INCOMPLETE.HOWEVER,
 THE MANUFACTURER HAS APPLIED FOR SITE
 SPECIFIC/LOCAL PRODUCT APPROVAL. PLEASE
 CALL PRIOR TO RESUBMITTAL TO DETERMINE
 STATUS OF THE LOCAL PRODUCT APPROVAL
 APPLICATION.
  
 3.)THE LICENSE NUMBER OF THE ENGINEER
 IS REQUIRED TO BE ON EACH SHEET,
 FAC61G15-23.002.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-12-03 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:15 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-12-03 00:00:00REVISIONS DATED 11/20/03 WITH HAND
 CORRECTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-11-24 Cont ID  
Sent By csiegber Date 2003-12-01 Time 13:31 Rev Time 0.00
Received By hpiskura Date 2003-11-24 Time 10:37 Sent To  
Notes
2003-11-24 00:00:00REVISIONS DATED 11/20/03, SHEETS 2,3
 AND 4, RODNEY N. GREEN, ARCHITECTS.
  
 FBC TABLE 600 EXPRESSLY PROHIBITS
 EXTERIOR WALL OPENINGS WHEN A WALL IS
 LOCATED 0' TO 3' FROM A PROPERTY LINE.
 SHEETS
 2 AND 3 PROPOSE GLASS BLOCK ON THE WEST
 SIDE WHICH ISNOT A LISTED FIRE RATED
 WALL ASSEMBLY.THIS ISSUE WAS COVERED
 PREVIOULY IN MEETINGS WITH THE
 ARCHITECT AND THE OWNER.
  
 REVISIONS TO SHEET 4 ARE NOT READILY
 DISCERNIBLE, PLEASE NOTE THE CHANGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-08-29 Cont ID  
Sent By hpiskura Date 2003-08-29 Time 09:30 Rev Time 0.00
Received By hpiskura Date 2003-08-29 Time 08:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-08-11 Cont ID  
Sent By hpiskura Date 2003-08-11 Time 07:28 Rev Time 0.00
Received By hpiskura Date 2003-08-11 Time 07:28 Sent To FIRE
Notes
2003-08-11 00:00:002ND REVIEW
 1)AS NOTED ON THE FIRST CHECKLIST THE
 OPENINGS IN THE EXTERIOR WALL ON THE
 SOUTH PROPERTY LINE ARE
 REQUIRED TO BE FIRE RATED, AND THE WEST
 WALL ARE PROHIBITTED BY FBC TABLE 600.
 THE ARCHITECT'S QUOTING OF FBC
 3401.7.2.4 IS WITHOUT STANDING FOR THIS
 PROJECT.SEE FBC 3401.7.2.6 AND REVISE
 AS NECESSARY.ALSO, SEE FBC 104.2.1
 WITH REGARDS TO QUOTING CODE SECTIONS
 NOT BEING AN ACCEPTABLE ALTERNATIVE TO
 SPECIFIC DESIGN INFORMATION.
  
 2) VERTICAL ACCESIBILITY IS REQUIRED
 FOR OFFICES SHOWN AS #4 AND #5 AS
 PREVIOUSLY NOTED.SEE FBC 11-4.1.5.6
 (1) (K) (III).
  
 3) THE STRUCTURAL CALCULATIONS
 PREVIOUSLY REQUESTED FOR THE SECOND
 FLOOR CONSTRUCTION HAVE NOT BEEN
 PROVIDED.
 THE DECLARED 1/2" X 5" BOLTS @ 4' ON
 CENTER SHOWN IN SECTION 2/A ON SHEET 3
 APPEARS TO BE VERY INADEQUATE FOR THE
 LOADS TO BE IMPOSED ON THE WOOD
 PERPENDICULAR TO THE GRAIN. HOW WAS THE
 MINIMAL 75# LIVE LOAD DETERMINED?
 PLEASE PROVIDE COMPLETE STRUCTURAL
 CALCULATIONS.
  
 4) THE STAIRS TO OFFICES 4 AND 5
 REQUIRE HANDRAILS ON EACH SIDE AN WITHIN
 30" OF THE WIDTH REQUIRED FOR EGRESS.
 SEE FBC 1007.5.2, FBC 1007.5.5 AND FBC
 1007.5.7.DO NOT QUOTE THOSE CODE
 SECTIONS BUT
 SHOW A GRAPHIC DEPICTION AND/OR NOTES
 TO CLEARLY SHOW THE DESIGN INTENT.
 INCLUDE FASTENING AND CONNECTION
 DETAILS.
  
 5) PLEASE PROVIDE THE FIRE DESIGN
 NUMBER FOR THE SEVERAL PLACES CALLING
 OUT "1 FIRE RATED" SEE FBC 701.5.
  
  
 6) SECTION 1/A, SHEET 3. THE STEEL
 COLUMN IS 3"X3"X WHAT?
  
 7) SECTION 3/A, WHAT ARE THE
 DIMENSIONS,MATERIAL AND CONNECTION
 METHODS?
  
 8) THE SIX INCH SPACE AT THE TOE RAIL
 OF THE GUARD RAIL SHOWN IN SECTION 3/A
 DOES NOT COMPLY WITH FBC 1015.3.IF THE
 GUARD RAIL IS A DELEGATED DESIGN SHOW
 MINIMUM REQUIRED LOADS AS PROVIDED FOR
 IN FBC 1608.2.2.
  
 9) THE SECOND FLOOR STAIRS ARE REQUIRED
 TO BE ENCLOSED WITH FIRE RATED
 CONSTRUCTION AND TO PROVIDE A PROTECTED
 PATH TO THE OUTSIDE.
 SEE FBC 1006.1.1 AND FBC 1010.1.
  
 10) TWO INDEPENDENT EXITS ARE REQUIRED
 FROM THE SECOND FLOOR.SEE FBC
 1004.2.1 AND 1027.1.FURTHER, THE
 TRAVEL DISTANCE IS >75' SO A SINGLE EXIT
 IS NOT ALLOWED FOR GROUP B OCCUPANCY IN
 THIS CASE.SEE ALSO FBC 303.1 #4 WITH R
 ESPECT TO MIXED OCCUPANCIES.
  
 11) SHOW OR NOTE SPECIFICALLY THE
 EXTERIOR TRIMS TO BE USED AS TO MATERIAL
 AND METHODS SEE FBC 104.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-11 Cont ID  
Sent By hpiskura Date 2003-04-11 Time 14:47 Rev Time 0.00
Received By hpiskura Date 2003-04-11 Time 10:56 Sent To  
Notes
2003-04-11 00:00:00THE GENERAL NOTES ON SHEET 1 DECLARES
 THE 1997 STANDARD BUILDING CODE.THE
 CITYOF WEST PALM BEACH AND THE STATE OF
 FLORIDA ARE CURRENTLY USING THE 2001
 FLORIDA BUILDING CODE.
  
 SEE FBC 104.3.1.1 FOR THE MINIMUM
 CRITERIA REQUIRED FOR PLAN REVIEW.
  
 THE ADDITION OF THE SECOND FLOOR AS
 WELLAS THE CHANGE OF USE FROM
 WAREHOUSE/STORAGE TO OFFICE IS SUBJECT
 TO IMPACT FEES COLLECTED BY THE COUNTY.
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED THE FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL (561) 233-5025 FOR
 MORE INFORMATION.
  
 THE OPENINGS ON THE SOUTH AND EAST
 EXTERIOR WALLS ARE REQUIRED TO BE FIRE
 PROTECTED AS PROVIDED FOR IN FBC TABLE
 600.
  
 OPENINGS IN THE WEST WALL ARE
 PROHIBITTED BY FBC TABLE 600.
  
 THE DESIGNATED FIVE FEET WIDE AISLE FOR
 THE HC PARKING SPACE IS NOT SHOWN ON THE
 SITE PLAN. SEE FBC 11- 4.6.3.
  
 VERTICAL ACCESSIBILITY IS REQUIRED FOR
 THE OFFICES SHOWN AS #4 & #5 AND THE
 SECOND FLOOR.SEE FBC 11- 4.1.6.
  
 PLEASE PROVIDE A BETTER STRUCTURAL
 FRAMING PLAN INCLUDING ALL OF THE
 DESIGN LOADS AND STANDARDS USED.SHOW
 THE MODIFICATIONS TO THE EXISTING WALLS
 IF ANY.THE PLACEMENT OF THE COLUMN AND
 FOOTING THAT ARE SHOWN IN SECTION ONLY.
  
 PROVIDE COMPLETE STRUCTURAL
 CALCULATIONSFOR THE SECOND FLOOR DESIGN.
  
 THE STAIRS MUST HAVE
 HANDRAILS COMPLYING WITH FBC 1007.5.
  
 THE SECOND FLOOR STAIRS ARE REQUIRED TO
 BE ENCLOSED IN FIRE RATED CONSTRUCTION.
 SEE FBC 1006.1.1.
  
 TWO MEANS OF EGRESS ARE REQUIRED FROM
 THE SECOND FLOOR.SEE FBC 1004.2.1 AND
 FBC 1027.1.1.
  
 THE 8" STAIR RISER SHOWN DOES NOT COMPLY
 WITH FBC 1007.3.
  
 THIS BUILDING IS LOCATED IN THE
 DESIGNATED FIRE DISTRICT AND EXTERIOR
 ARCHITECTURAL TRIM IS REQUIRED TO BE
 FIRE RETARDANT TREATED LUMBER OF
 NON-COMBUSTIBLE MATERIAL.SEE FBC
 F102.2.7 AS AMENDED BY THE CITY OF WEST
 PALM BEACH.
  
 PLEASE PROVIDE THREE COPIES OF SIGNED
 AND SEALED ENERGY CODE CALCLULATIONS.
 SEE FBC 13- 101.3.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-05-04 Cont ID  
Sent By dpalmer Date 2004-05-04 Time 17:09 Rev Time 0.50
Received By dpalmer Date 2004-05-04 Time 17:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-04-28 Time 16:00 Rev Time 0.50
Received By dpalmer Date 2004-01-21 Time 07:46 Sent To  
Notes
2004-01-21 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED WITH
 ORIGINAL SIGNATURE. PLANS ARE SEEALED
 COPIES.
 PLEASE SEE FS 481.221. REQ'S PLANS TO BE
 ORIGINAL SIGNED, DATED AND SEALED.
 THE DATE ON THE SIGNATURE IS FROM
 2/10/03
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-27 Cont ID  
Sent By csiegber Date 2004-01-16 Time 13:31 Rev Time 0.33
Received By dpalmer Date 2003-08-27 Time 20:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-08-04 Cont ID  
Sent By dbaxter Date 2003-08-27 Time 13:37 Rev Time 1.00
Received By dpalmer Date 2003-08-04 Time 16:45 Sent To  
Notes
2003-08-04 00:00:00**************** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM,
 PANEL ETC. PANEL SHOWN AS 225A,ON RISER,
 400A ON SCHEDULE AND400A OCP FEEDING
 A 225A PANEL. LOAD SHOWN AT 257A'S ON
 A 225A PANEL?
  
 215/310-16/240/230/ ETC
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 AS REQUESTED ON FIRST REVIEW. 220
 SEE ALL ART'S REFERENCED ON FIRST REVIEW
  
 3)NOTE: PLEASE CLARIFY SOME CIRCUITING
 SHOWN FOR EM/EXT LTS MISSING. PLEASE SEE
 700-12E FOR CIRCUITING.
  
 4)NOTE: PLEASE CLARFIY LIGHTING SHOWN
 AS REQ'D SIGN CIRCUIT? SHOWN AS WHAT
 APPEARS TO BE FLOOD LTS? SYMBOL NOT
 SHOWN ON ELECTRICAL LEGEND?
 PLEASE SHOW REQ'D SIGN CIRCUIT AT
 ENTRANCE PER 600-5
  
 5)NOTE: PLEASE CLARIFY TWO A/C SYSTEMS
 NOW SHOWN ON PLANS AND ONLY ONE ON PANEL
 SCHEDULE? PLEASE ALSO INCLUDE ON LOAD
 CALCUALTIONS PER 220/215-5
 CIRCUIT #'S SHOWN ON PLANS BUT DO NOT
 CORRELATE W/ PANEL SCHEDULE?
  
 6)NOTE: PLEASE CLARIFY SEC`S, NOT SHOW-
 -ING ANY CONDUCTOR SIZE FROM METER TO
 MAIN? PLEASE ALSO SEE SIZE SHOWN FROM
 MAIN TO PANEL AS 3-# 4/0 MCM,,,?
 PLEASE SEE 310-16 FOR SIZING
  
 7)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM, PER 250-50 GRND RD, COLD WATER
 ETC, IF AVAILABLE.
  
 8)NOTE: PLEASE SEE COPY OF FS 553.80(2)-
 (B) W/ RESPECT TO DESIGN PROFESSIONAL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-07 Cont ID  
Sent By dpalmer Date 2003-04-07 Time 13:09 Rev Time 0.75
Received By dpalmer Date 2003-04-07 Time 13:09 Sent To  
Notes
2003-04-07 00:00:00*********** UNSAT *****************
  
 1)NOTE; PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL HAVE AN AFFECT ON E-SHEETS.
  
 2)NOTE: PLEASE CALRFIY IF THIS IS A NEW
 OR EXISTING SERVICE? SHOWN AS NEW, IS
 THIS REPLACING EXIST?
  
 3)NOTE; PLEASE SEE FEEDER/SEC`S FOR
 NEW 400A SERVICE. PLEASE SIZE PER 310-16
 SHOWN AS 3/0` WHICH ARE ONLY RATED FOR
 200A`S.
  
 4)NOTE ; PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE W/ SUBMITTED PANEL
 SCHEDULE.
  
 5)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PER 220-3,220-10,220-11,220-13 ETC AND
 ALL CONTINUOUS LOADS PER 215-3/230-42
  
 6)NOTE: PLEASE SIZE OCP FOR AHU HEAT
 PER 424-3B MIN @125%.
  
 7)NOTE:PLEASE CALRIFY CIRCUITING FOR
 EM/EXXT LTS PER700-12E
  
 PLEASE SUBMIT THE ABVOVE INFORMATION
 FOR REVIEW/.
 561-659-8096 EXT 8372
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-09-05 Cont ID  
Sent By nmccray Date 2003-09-05 Time 09:25 Rev Time 0.00
Received By nmccray Date 2003-09-05 Time 09:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-08-13 Cont ID  
Sent By nmccray Date 2003-08-13 Time 13:52 Rev Time 0.00
Received By nmccray Date 2003-08-13 Time 13:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-04-04 Cont ID  
Sent By hpiskura Date 2003-08-11 Time 09:06 Rev Time 0.00
Received By mcarsill Date 2003-04-04 Time 16:11 Sent To  
Notes
2003-04-04 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS.
  
 2) NO INTERIOR FINISH CLASSIFICATION
 FOR THE WALLS AND CEILINGS.
  
 3) RISERS FOR STAIRS NEAR SECRETARY
 POOL AREA DOES NOT MEET CODE.
  
 4) STAIRS NEAR KITCHEN DOES NOT MEET
 CODE.
  
 5) ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTS SHALL BE PLACED ON THE SAME
 DRAWING.
  
 6) NO FIRE EXTINGUISHERS SHOWN ON THE
 PLANS.
  
 7) IF NO FIRE SPRINKLERS ARE PLANNED,
 THEN STORAGE ROOMS SHALL BE FIRE
 RATED AT LEAST ONE HOUR WITH PROPER
 OPENING PROTECTIVES.
  
 8) WRONG BUILDING CODE REFERENCED ON
 THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 16:00 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 16:00 Sent To E
Notes
2004-04-28 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:14 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 14:14 Sent To B
Notes
2004-02-27 00:00:00TO SH DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 13:31 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 13:31 Sent To E
Notes
2004-01-16 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-01 Cont ID  
Sent By csiegber Date 2003-12-01 Time 13:31 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 13:31 Sent To B
Notes
2003-12-01 00:00:00TO HP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-27 Cont ID  
Sent By dbaxter Date 2003-08-27 Time 13:31 Rev Time 0.00
Received By dbaxter Date 2003-08-27 Time 13:31 Sent To E
Notes
2003-08-27 00:00:00TO DPALMER DESK.
 TO COMM BD. #48

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-24 Cont ID  
Sent By alange Date 2003-07-24 Time 14:17 Rev Time 0.00
Received By alange Date 2003-07-24 Time 14:17 Sent To  
Notes
2003-07-24 00:00:00TO COMM BD. #52

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-01 Cont ID  
Sent By shernand Date 2003-04-01 Time 13:30 Rev Time 0.00
Received By shernand Date 2003-04-01 Time 13:30 Sent To  
Notes
2003-04-01 00:00:00COMM BOARD #29

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-11-19 Cont ID  
Sent By pkrauss Date 2003-11-19 Time 15:25 Rev Time 0.40
Received By pkrauss Date 2003-11-19 Time 15:25 Sent To  
Notes
2003-11-19 00:00:00AS BUILT DWGS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-04 Cont ID  
Sent By pkrauss Date 2003-08-04 Time 11:09 Rev Time 0.40
Received By pkrauss Date 2003-08-04 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-04-15 Cont ID  
Sent By pkrauss Date 2003-04-15 Time 08:55 Rev Time 0.45
Received By pkrauss Date 2003-04-15 Time 09:20 Sent To  
Notes
2003-04-15 00:00:00DENIED:2001 FLORIDA BUILDING CODE,
 (MECHANICAL)
 1.AS PER 2001 FBC(M) 501.3, EXHAUST
 SYSTEM SHALL BE DISCHARGED OUTDOORS AT
 A POINT FROM WHICH IT CANNOT AGAIN BE
 DRAWN IN BY THE VENTILATION SYSTEM.
 (EXHAUST OUTLET IN RELATION TO OUTSIDE
 AIR INTAKE).
  
 2.CLARIFY THE 6" OUTSIDE AIR DUCT
 TERMINATING IN THE AHU CLOSET.THE
 RETURN AIR APPEARS TO BE DUCTED INTO
 THE AHU.IS THE O.A. TIED INTO THE
 RETURN OR OPEN TO THE AHU CLOSET?
  
 3.TOILET ROOM BETWEEN OFFICE #4 & 5
 DOES NOT INDICATE AN EXHAUST FAN.AS
 PER 2001 FBC(M) 501.2 SINGLE OR COMBINED
 MECHANICAL EXHAUST SYSTEMS FROM TOILET,
 URINAL & SIMILAR ROOMS SHALL BE
 INDEPENDENT IF OTHER EXHAUST SYSTEMS.
 ALSO 403.2.1, ROOMS CONTAINING SHOWERS,
 BATHTUBS OR SIMILAR BATHING FIXTURES
 SHALL BE MECHANICALLY EXHAUSTED.
  
 4.FRESH AIR CALCS ARE INCOMPLETE, THE
 DO NOT INDICATE SQ FOOTAGE OR NUMBER
 OF PEOPLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-09-04 Cont ID  
Sent By kstevens Date 2003-09-04 Time 16:52 Rev Time 0.33
Received By kstevens Date 2003-09-04 Time 16:52 Sent To  
Notes
2003-09-04 00:00:00PASSED/PROVISO
  
 BATHROOM BETWEEN OFFICES SHALL COMPLY
 WITH 11-4.23 - SHOWER SHALL COMPLY WITH
 11-4.21

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-09-04 Cont ID  
Sent By kstevens Date 2003-07-24 Time 13:03 Rev Time 0.00
Received By kstevens Date 2003-07-24 Time 16:02 Sent To  
Notes
2003-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) FROM PREVIOUS REVIEW: SHOW DETAIL FOR
 TOILET ROOMS. FOR WATER CLOSETS SHOW
 CLEAR FLOOR SPACE 11-4.16.2, HEIGHT
 11-4.16.3, GRAB BARS 11-4.16.4, AND
 FLUSH CONTROLS 11-4.16.5. FOR LAVS SHOW
 HEIGHT & CLEARANCES 11-4.19.2, CLEAR
 FLOOR SPACE 11-4.19.3, EXPOSED PIPES
 11-4.19.4, AND FAUCETS 11-4.19.5. FOR
 BREAK ROOM SINK SHOW HEIGHT 11-4.24.2,
 KNEE CLEARANCES 11-4.24.3, DEPTH 11-4.
 24.4, CLEAR FLOOR SPACE 11-4.24.5, EX-
 POSED PIPES & SURFACES 11-4.24.6, AND
 FAUCETS 11-4.24.7. SECTION 104.2.1 -
 INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A
 WHOLE OR IN PART, NOR SHALL THE TERM
 "LEGAL" OR ITS EQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION.
 2) TOILET ROOM FOR OFFICES #'S 4 & 5 IS
 NOT A PRIVATE TOILET ROOM BUT A COMMON
 USE TOILET ROOM AND SHALL BE ACCESSIBLE.
 SEE COMMENT #1 FOR DETAILS REQUIRED FOR
 TYPICAL ACCESSIBLE TOILET ROOM. ALSO
 SHOW COMPLIANCE WITH 11-4.21 AND ALL
 SUBSECTIONS. SIZE & CLEARANCE 11-4.21.2,
 SEAT 11-4.21.3, GRAB BARS 11-4.21.4,
 CONTROLS 11-4.21.5, & CURBS 11-4.21.7
 3) NEW COMMENT, PER TABLE 403.1 A DRINK-
 ING FOUNTAIN IS REQUIRED. ALSO SEE SECT-
 ION 410.1
 4) NEW COMMENT SUBMIT A WATER RISER DIA-
 GRAM. WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 (AT DISHWASHER & ICE MAKER
 IN REFRIG. IF INSTALLED), SHALL BE LOCA-
 TED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" AND NOT IN THE CEILING AT THE TOP
 OF THE DROPS.
 5) PLEASE SEE ATTACHED SHEET CONCERNING
 ARCHITECTS SEAL AND TITLE BLOCK REQUIRED
 FOR EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-12 Cont ID  
Sent By kstevens Date 2003-04-12 Time 11:54 Rev Time 0.50
Received By kstevens Date 2003-04-12 Time 11:44 Sent To  
Notes
2003-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 2 SECTION 11-4.1.6, IF EXISTING
 ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH SUCH ALTERED ELEMENT,
 SPACE, FEATURE, OR AREA SHALL COMPLY
 WITH THE APPLICABLE PROVISIONS OF
 11-4.1.1 TO 11-4.1.3 - IF TOILET ROOMS
 ARE PROVIDED THEN EACH PUBLIC AND COMMON
 USE TOILET SHALL COMPLU WITH 11-4.22
 IF BATHING ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE BATHROOM SHALL
 COMPLY WITH 11-4.23. - PLEASE SHOW CLEAR
 FLOOR SPACE, TURNING CIRCLE ECT. TO
 COMPLY WITH 11-4.16 AND ALL SUB SECTIONS
 ALSO SHOW DETAIL FOR SHOWER SHOWING
 COMPLIANCE WITH 11-4.21 AND ALL SUBSEC-
 TIONS.
 2) SHT 2 NEW BREAK SINK, SUBMIT DETAIL
 SHOWING COMPLIANCE WITH 11-4.24 AND ALL
 SUBSECTIONS.
 3) SEPARATE PERMIT REQUIRED FOR IRRIGAT-
 ION. SUBMIT PLANS AT TIME OF APPLICATION
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status N Date 2003-09-05 Cont ID  
Sent By kstevens Date 2003-09-05 Time 11:03 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***