Plan Review Details - Permit 03032191
Plan Review Stops For Permit 03032191
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-08-05 Cont ID  
Sent By rbrown Date 2003-08-05 Time 13:13 Rev Time 0.00
Received By rbrown Date 2003-08-05 Time 13:13 Sent To  
Notes
2003-08-05 00:00:00REVISION SUBMITTED 7/22/03 FOR VALUE
 ENGINEERING REVISIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-11 Cont ID  
Sent By alange Date 2003-07-23 Time 08:39 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
2003-07-11 00:00:00REVIEWED AND PASSED BROWNS COMMENTS FROM
 4/14/03.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-15 Cont ID  
Sent By rbrown Date 2003-04-15 Time 18:35 Rev Time 0.00
Received By rbrown Date 2003-04-14 Time 11:23 Sent To  
Notes
2003-04-14 00:00:00PROJECT: SLADE, N. FLAGLER DR
 ASSOCIATED BUILDING PERMIT # 03020961
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PLANS STAMPED BY THEM
 AND A COPY OF THE RECEIPT SUBMITTED TO
 THE CITY OF WEST PALM BEACH, DEPARTMENT
 OF CONSTRUCTION SERVICES, BEFORE THE
 FOUNDATION PERMIT IS ISSUED.
  
 2) SPECIAL INSPECTOR.RECEIPT OF THE
 'THRESHOLD INSPECTION PLAN', PREPARED BY
 O'DONNELL, NACCARATO, MIGNOGNA & JACKSON
 INC., IS NOTED.BEFORE A PERMIT CAN BE
 ISSUED, THE NAME AND CONTACT DETAILS OF
 THE THRESHOLD INSPECTOR SHALL BE
 SUBMITTED TO DON NEELY, INSPECTION
 PROGRAM MANAGER (TEL: 561 805 6665).
  
 NOTE:
 FBC* 104.4.5 SPECIAL FOUNDATION PERMIT.
 THE PERMIT HOLDER IS PROCEEDING AT HIS/
 HER OWN RISK AND WITHOUT ASSURANCE THAT
 A PERMIT FOR THE REMAINDER OF THE WORK
 WILL BE GRANTED AND THAT CORRECTIONS
 WILL NOT BE REQUIRED IN ORDER TO MEET
 THE PROVISIONS OF THE TECHNICAL CODES.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-11 Cont ID  
Sent By btrobaug Date 2003-07-11 Time 09:45 Rev Time 0.50
Received By btrobaug Date 2003-07-11 Time 09:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-15 Cont ID  
Sent By dpalmer Date 2003-04-15 Time 05:30 Rev Time 0.50
Received By dpalmer Date 2003-04-15 Time 05:30 Sent To  
Notes
2003-04-15 00:00:00**************NOTE **************
  
 1)NOTE: PLEASE NOTE, PLANS FOR MAIN
 ELECTRICAL SERVICE WERE NOT COMPLETE AND
 APPROVED AT TIME OF SUBMITTAL FOR
 BUILDING FOUNDATION PERMIT.
 PLEASE NOTE, ANY UNDERGROUND/SLAB
 ELECTRICAL CONDUITS WILL BE INSTALLED
 AT CONTRACTOR OWN RISK.
 CONTRACTOR MAY PROCEED WITH REDLINED
 AND HIGHLIGHTED ELECTRICAL CONDUITS ON
 ES-1/E-1 ONLY.
 PLEASE SEE ADIM CODE. 104.4.5
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-03-28 Cont ID  
Sent By mamini Date 2003-03-28 Time 14:17 Rev Time 1.00
Received By mamini Date 2003-03-28 Time 14:17 Sent To  
Notes
2003-03-28 00:00:00PASSED WITH PROVISOS:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORKS IS REQUIRED,
 PLEASE SUBMIT TWO SETS OF CIVIL PLANS
 ONLY, SIGNED AND SEALED.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-04-28 Cont ID  
Sent By nmccray Date 2003-04-28 Time 15:00 Rev Time 0.00
Received By nmccray Date 2003-04-28 Time 15:00 Sent To  
Notes
2003-04-28 00:00:00**************FOUNDATION****************
 1) NOTES INDICATE NFPA 101 LIFE SAFETY
 CODE. PLEASE REF 2000 EDITION OF THE
 NFPA 101 LIFE SAFETY CODE.
  
 NATE MCCRAY, CAPTAIN
 658-8096, EXT 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-23 Cont ID  
Sent By alange Date 2003-07-23 Time 08:39 Rev Time 0.00
Received By alange Date 2003-07-23 Time 08:39 Sent To B
Notes
2003-07-23 00:00:007/23/03 TO RBROWN DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-11 Cont ID  
Sent By sthyng Date 2003-03-27 Time 13:01 Rev Time 0.00
Received By lmartine Date 2003-03-27 Time 12:43 Sent To  
Notes
2003-03-27 00:00:00TO COMM BOARD #1
 PLANS ON RACK (2 ROLLS)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-07-10 Cont ID  
Sent By rbrown Date 2003-07-10 Time 15:56 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-10 Cont ID  
Sent By kstevens Date 2003-07-10 Time 12:19 Rev Time 1.00
Received By kstevens Date 2003-07-10 Time 12:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-18 Cont ID  
Sent By kstevens Date 2003-04-18 Time 14:37 Rev Time 3.25
Received By kstevens Date 2003-04-18 Time 14:37 Sent To  
Notes
2003-04-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT P-18 GAS ISOMETRIC, REFERENCE
 NFPA-54 (1996) - NFPA-54 NOT ADOPTED IN
 FBC-2001. PLEASE INDICATE CODE IN FBC-
 2001 FUEL GAS CODE THAT WILL SHOW 400'
 DEVELOPED LENGTH @ 2PSI.
 2) SHT P-18 GAS ISOMETRIC, LINE SUPPLY-
 ING REGULATOR #2 SHOWS 1775 MBH, BUT
 ONLY SHOWS 2 @ 400 MBH & 1 @ 200 MBH =
 1000 MBH. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-10 Cont ID  
Sent By rbrown Date 2003-07-10 Time 15:54 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
2003-07-10 00:00:00PER SHIRLEY GRAHAM