Plan Review Details - Permit 03032124
Plan Review Stops For Permit 03032124
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-25 Cont ID  
Sent By btrobaug Date 2003-04-25 Time 13:49 Rev Time 0.00
Received By rbrown Date 2003-04-25 Time 11:07 Sent To  
Notes
2003-04-25 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 HURRICANE MISSILE IMPACT SHUTTERS.THE
 SUBMITTED FRENCH DOOR AND SINGLE HUNG
 WINDOW PRODUCT APPROVALS NOA# 02-0625.01
 AND NOA# 01-0516.10 BOTH STATE THAT
 HURRICANE SHUTTERS WILL BE REQUIRED.
 SUBMIT A PRODUCT APPROVAL FOR SHUTTERS
 OR NEW PRODUCT APPROVALS FOR AN IMPACT
 RESISTANT DOOR AND WINDOW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-21 Time 13:48 Rev Time 0.00
Received By rbrown Date 2003-04-11 Time 15:07 Sent To  
Notes
2003-04-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3 ) SUBMIT A PRODUCT APPROVAL FOR THE
 WINDOWS.
  
 4) SUBMIT A PRODUCT APPROVAL FOR THE
 EXTERIOR DOOR.
  
 5) DETAIL 1/1, SECTION.FOR THE #5
 VERTICAL WALL REINFORCEMENT DOWELLED TO
 THE EXISTING TIE BEAM AND THE SLAB
 REINFORCEMENT DOWELLED TO THE EXISTING,
 ANNOTATE THE PLANS TO SHOW THE MATERIAL/
 METHOD FOR ANCHORING THE DOWELS TO THE
 EXISTING STRUCTURE.
  
 6) DETAIL 1/1, SECTION.AMEND THE PLANS
 TO SHOW THE FOOTING DOWELS TO HAVE MIN.
 25" LAP WITH THE VERTICAL WALL
 REINFORCEMENT.
  
 7) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.
  
 8) DETAIL 1/1, SECTION.ADD A NOTE TO
 THE PLAN FOR THE CONTRACTOR TO NOTIFY
 THE ARCHITECT ABOUT EXISTING ROOF ANCHOR
 TYPE FOR VERIFICATION AGAINST THE
 CURRENT WIND LOAD CRITERIA (SEE COMMENT
 # 7, ABOVE).ALTERNATIVELY, SPECIFY
 RETROFIT TRUSS ANCHORS.
  
 9) FBC 2309.6ATTIC ACCESS.PROVIDE A
 MIN. 20"X36" INTERIOR ACCESS OPENING TO
 THE ATTIC SPACE FORMED BY INSTALLATION
 OF THE NEW CEILING.
  
 10) FBC 2309.7ATTIC SPACE VENTILATION.
 ANNOTATE THE PLANS TO CONFIRM/SPECIFY
 VENTILATION OF THE ATTIC SPACE FORMED
 BY INSTALLATION OF THE NEW CEILING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-25 Cont ID  
Sent By btrobaug Date 2003-04-25 Time 13:48 Rev Time 0.50
Received By btrobaug Date 2003-04-25 Time 13:48 Sent To B
Notes
2003-04-25 00:00:00RE-REDLINED,SEE DVP'S COMMENTS./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-07 Cont ID  
Sent By sthyng Date 2003-04-01 Time 11:02 Rev Time 0.25
Received By dpalmer Date 2003-04-07 Time 15:47 Sent To P
Notes
2003-04-07 00:00:00********** NOTES REDLINED ************
  
 210-52
 210-52C-3
 210-8-A-6

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-21 Time 13:48 Rev Time 0.00
Received By shernand Date 2003-04-21 Time 13:48 Sent To B
Notes
2003-04-21 00:00:00RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-01 Cont ID  
Sent By sthyng Date 2003-04-01 Time 10:41 Rev Time 0.00
Received By sthyng Date 2003-04-01 Time 10:41 Sent To E
Notes
2003-04-01 00:00:00TO ELEC IN BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-26 Cont ID  
Sent By sgraham Date 2003-03-28 Time 11:08 Rev Time 0.00
Received By sthyng Date 2003-03-26 Time 14:33 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-04-09 Cont ID  
Sent By kstevens Date 2003-04-08 Time 07:31 Rev Time 0.25
Received By pkrauss Date 2003-04-09 Time 11:12 Sent To B
Notes
2003-04-09 00:00:00NO MECHANICAL PLANS SUBMITTED

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-08 Cont ID  
Sent By dpalmer Date 2003-04-07 Time 15:47 Rev Time 0.00
Received By kstevens Date 2003-04-08 Time 11:31 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-28 Cont ID  
Sent By sthyng Date 2003-03-26 Time 14:33 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***