Plan Review Details - Permit 03031863
Plan Review Stops For Permit 03031863 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2003-04-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-04-23 |
Time |
14:41 |
Rev Time |
1.00 |
Received By |
lhatten |
Date |
2003-04-23 |
Time |
10:00 |
Sent To |
|
|
Notes |
2003-04-23 00:00:00 | RESUB ALL MISSING -PRODUCT APPROVALS- | | DENSITIES FOR SUBSURFACE BORINGS OKED | | 04/23/2003 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-04-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-04-04 |
Time |
09:16 |
Rev Time |
2.50 |
Received By |
lhatten |
Date |
2003-04-17 |
Time |
15:27 |
Sent To |
|
|
Notes |
2003-04-18 00:00:00 | FAILED | | | | 1) NO PRODUCT APPROVALS FOR; | | A) SLIDING GLASS DOORS | | B) SINGLE LITE DOOR AT REAR OF HOUSE | | C) DOUBLE FRONT DOORS | | D) SINGLE FLUSH DOOR AT GARAGE | | | | 2) SHUTTER DETAILS, AND LAYOUT | | 3) DENSITY REPORTS INCLUDING SOIL | | BORINGS | | 4) NEEDS N.O.C. | | 5) IMPACT FEES PAID | | 6) ENERGY CALC. NEED TO BE SIGNED BY | | OWNER/AGENT - NEED 1-COPY OF COVER | | SHEET ALSO SIGNED |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2003-10-15 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-10-15 |
Time |
09:59 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2003-10-15 |
Time |
09:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-04-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-04-23 |
Time |
14:41 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2003-04-23 |
Time |
14:41 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-04-03 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2003-03-31 |
Time |
10:21 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2003-04-03 |
Time |
13:19 |
Sent To |
P |
|
Notes |
2003-04-03 00:00:00 | ***************** UNSAT ************* | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BRKRS MUST BE RATED FOR THE | | AVAILABLE FAULT CURRENT. 110-9/215-5 | | | | 2)NOTE: PLEASE SEE PLAN FOR MISSING | | HALL RECEPT PER 210-52H/210-52 | | | | 3)NOTE: PLEASE SEE 424-3B FOR SIZING | | OF OCP FOR AHU, SHOWN AS 50A ON 10KW. | | MIN @125%. | | | | 4)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | CONDUCTOR PER 250-66. MIN FOR 2/0`S IS | | #4.. | | | | 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | PROTECTED CIRCUITS ON PANEL SCHEDULE PER | | 210-12 | | | | 6)NOTE: PLEASE SEE FS/FAC 61G15-23.002 | | ALL SHEETS MUST CONTAIN A TITLE BLOCK | | W/ ALL INFORMATION AS SET FORTH UNDER | | FS. NAME/ADDRESS/LIC # AND COMPANY | | IFSO. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | [email protected] | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-04-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-04-04 |
Time |
08:31 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2003-04-03 |
Time |
15:36 |
Sent To |
P |
|
Notes |
2003-04-04 00:00:00 | PROVIDE THE FOLOWING AT ROUGH INSPECTION | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | AREA BEING VENTILATED) OR TABLE 403.3 | | FOR MECHANICAL VENTILATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2003-04-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-04-04 |
Time |
08:47 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2003-04-04 |
Time |
09:16 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-03-31 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2003-03-31 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
E |
|
Notes |
|
|
|