Plan Review Details - Permit 03031863
Plan Review Stops For Permit 03031863
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-23 Cont ID  
Sent By dpalmer Date 2003-04-23 Time 14:41 Rev Time 1.00
Received By lhatten Date 2003-04-23 Time 10:00 Sent To  
Notes
2003-04-23 00:00:00RESUB ALL MISSING -PRODUCT APPROVALS-
 DENSITIES FOR SUBSURFACE BORINGS OKED
 04/23/2003

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-18 Cont ID  
Sent By kstevens Date 2003-04-04 Time 09:16 Rev Time 2.50
Received By lhatten Date 2003-04-17 Time 15:27 Sent To  
Notes
2003-04-18 00:00:00FAILED
  
 1) NO PRODUCT APPROVALS FOR;
 A) SLIDING GLASS DOORS
 B) SINGLE LITE DOOR AT REAR OF HOUSE
 C) DOUBLE FRONT DOORS
 D) SINGLE FLUSH DOOR AT GARAGE
  
 2) SHUTTER DETAILS, AND LAYOUT
 3) DENSITY REPORTS INCLUDING SOIL
 BORINGS
 4) NEEDS N.O.C.
 5) IMPACT FEES PAID
 6) ENERGY CALC. NEED TO BE SIGNED BY
 OWNER/AGENT - NEED 1-COPY OF COVER
 SHEET ALSO SIGNED

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-15 Cont ID  
Sent By btrobaug Date 2003-10-15 Time 09:59 Rev Time 0.25
Received By btrobaug Date 2003-10-15 Time 09:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-23 Cont ID  
Sent By dpalmer Date 2003-04-23 Time 14:41 Rev Time 0.25
Received By dpalmer Date 2003-04-23 Time 14:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By sgraham Date 2003-03-31 Time 10:21 Rev Time 0.50
Received By dpalmer Date 2003-04-03 Time 13:19 Sent To P
Notes
2003-04-03 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BRKRS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT. 110-9/215-5
  
 2)NOTE: PLEASE SEE PLAN FOR MISSING
 HALL RECEPT PER 210-52H/210-52
  
 3)NOTE: PLEASE SEE 424-3B FOR SIZING
 OF OCP FOR AHU, SHOWN AS 50A ON 10KW.
 MIN @125%.
  
 4)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66. MIN FOR 2/0`S IS
 #4..
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE PER
 210-12
  
 6)NOTE: PLEASE SEE FS/FAC 61G15-23.002
 ALL SHEETS MUST CONTAIN A TITLE BLOCK
 W/ ALL INFORMATION AS SET FORTH UNDER
 FS. NAME/ADDRESS/LIC # AND COMPANY
 IFSO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-04 Cont ID  
Sent By pkrauss Date 2003-04-04 Time 08:31 Rev Time 0.40
Received By pkrauss Date 2003-04-03 Time 15:36 Sent To P
Notes
2003-04-04 00:00:00PROVIDE THE FOLOWING AT ROUGH INSPECTION
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-04 Cont ID  
Sent By pkrauss Date 2003-04-04 Time 08:47 Rev Time 0.33
Received By kstevens Date 2003-04-04 Time 09:16 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-31 Cont ID  
Sent By sgraham Date 2003-03-31 Time 10:21 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***