Plan Review Details - Permit 03031817
Plan Review Stops For Permit 03031817
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-25 Cont ID  
Sent By sthyng Date 2003-04-25 Time 16:39 Rev Time 0.50
Received By sthyng Date 2003-04-25 Time 16:39 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-24 Time 11:03 Rev Time 1.00
Received By sthyng Date 2003-04-21 Time 17:11 Sent To  
Notes
2003-04-21 00:00:00**********CORRECTIONS************
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 2.)PROVIDE AN ATTACHMENT DETAIL FOR
 THE POOL EQUIPMENT.
  
 3.)SAFETY REQUIREMENTS TO BE SHOWN
 THE PLAN (FBC 424.2.17).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-18 Cont ID  
Sent By kstevens Date 2003-04-17 Time 10:20 Rev Time 0.50
Received By btrobaug Date 2003-04-18 Time 13:51 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-24 Cont ID  
Sent By shernand Date 2003-04-24 Time 11:03 Rev Time 0.00
Received By shernand Date 2003-04-24 Time 11:03 Sent To B
Notes
2003-04-24 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 08:15 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 08:15 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-26 Cont ID  
Sent By kstevens Date 2003-04-26 Time 08:10 Rev Time 0.25
Received By kstevens Date 2003-04-26 Time 08:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-17 Cont ID  
Sent By sthyng Date 2003-04-25 Time 16:39 Rev Time 0.33
Received By kstevens Date 2003-04-17 Time 10:18 Sent To E
Notes
2003-04-17 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 2) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 2 Status P Date 2003-04-14 Cont ID  
Sent By sgraham Date 2003-04-14 Time 16:11 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-04-10 Cont ID  
Sent By sthyng Date 2003-03-24 Time 08:15 Rev Time 0.00
Received By sgraham Date 2003-03-26 Time 11:50 Sent To  
Notes
2003-03-26 00:00:00DENIED, SIDE SETBACK MUST BE 10'