Plan Review Details - Permit 03031801
Plan Review Stops For Permit 03031801
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-04-03 Cont ID  
Sent By dpalmer Date 2003-04-02 Time 17:54 Rev Time 0.00
Received By lsmith Date 2003-04-03 Time 14:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-21 Cont ID  
Sent By dpalmer Date 2003-04-21 Time 10:51 Rev Time 0.50
Received By dpalmer Date 2003-04-21 Time 10:51 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-02 Cont ID  
Sent By shernand Date 2003-04-16 Time 14:32 Rev Time 0.33
Received By dpalmer Date 2003-04-02 Time 17:54 Sent To B
Notes
2003-04-02 00:00:00**************** UNSAT ************
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS,
 SHOWS 157A LOAD ON AN EXISTING 150A
 SERVICE?
 PLEASE SUBMIT PLANS AND PERMIT APPLICAT-
 ION FOR SERVICE CHANGE.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-16 Time 14:32 Rev Time 0.00
Received By shernand Date 2003-04-16 Time 14:32 Sent To E
Notes
2003-04-16 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-21 Cont ID  
Sent By sthyng Date 2003-03-21 Time 11:07 Rev Time 0.00
Received By sthyng Date 2003-03-21 Time 11:07 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-23 Cont ID  
Sent By kstevens Date 2003-04-23 Time 18:10 Rev Time 1.25
Received By kstevens Date 2003-04-23 Time 18:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-01 Cont ID  
Sent By dpalmer Date 2003-04-21 Time 10:51 Rev Time 0.50
Received By kstevens Date 2003-04-01 Time 16:26 Sent To E
Notes
2003-04-01 00:00:00DENIED
 REFERENCE: FBC 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 3) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-27 Cont ID  
Sent By sthyng Date 2003-03-21 Time 11:07 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***