Review Stop B BUILDING (STRUCTURAL)
Rev No 56 Status P Date 2007-09-27 Cont ID  
Sent By jwitmer Date 2007-09-28 Time 10:39 Rev Time 4.44
Received By jwitmer Date 2007-09-27 Time 10:38 Sent To  
Notes
2007-10-17 10:41:05PLEASE SEE PERMIT 05091240 FOR SHUTTERED OPENINGS (2)
 FOR DOORS AT POOL DECK BY J GOMEZ.

Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status F Date 2006-10-19 Cont ID  
Sent By shill Date 2006-10-19 Time 09:56 Rev Time 0.00
Received By shill Date 2006-10-19 Time 09:56 Sent To  
Notes
2006-10-19 10:05:24****CORRECTIONS****
 REVISION 22
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2001
  
 1.)A2.06, A36AB, AND OTHER SHEETS STATES THAT
 OPENINGS WILL BE PROTECTED BY A HURRICANE SHUTTER.
 REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST BE
 APPROVED BY THE BUILDING OFFICIAL, SEE ATTACHED POLICY,
 ITEM 13.IF YOU HAVE NOT SUBMITTED A HURRICANE SHUTTER
 INSTALLATION PLAN, PLEASE DO SO AT THIS TIME.IF YOU
 HAVE AN APPROVED PLAN, PLEASE REVISE TO INCLUDE THE NEW
 OPENINGS AND SUBMIT.A PRELIMINARY REVIEW OF THE PLAN
 CAN BE DONE VIA EMAIL, [email protected] SHOULD BE
 DONE PRIOR TO RESUBMITTAL TO AVOID DELAYS IN REVISION
 APPROVAL.
  
 2.)WERE PRODUCT APPROVALS SUBMITTED FOR THE SHUTTERS?
 DID THE DOOR CHANGE FROM ORIGINAL APPROVAL?HAS A NEW
 PRODUCT APPROVAL BEEN SUBMITTED?NO DOOR TYPE
 INDICATED.NOTE THAT ONE DOOR IS AT AN ELEVATOR LOBBY,
 SEE FBC412.6.1.
  
 3.)A2.11 AND OTHER SHEETS SHOW A CHANGE TO JOHN
 MANVILLE MODIFIED OVER LWC.HAS THE PRODUCT APPROVAL
 BEEN REVIEWED BY THE CITY?IF NOT, SUBMIT AT THIS TIME
 AND INDICATE WHICH APPROVED ASSEMBLY YOU ARE USING.
  
 4.)A2.11 SHOWS "ACCESS DOOR PROVIDED UNDER THE STAIR
 REQUESTED BY CITY INSPECTOR."NO STAIRS SHOWN.WHAT
 WILL THIS AREA BE USED FOR?DOES NOT APPEAR TO BE AN
 EXIT STAIR, PLEASE CLARIFY ON THIS SHEET PURPOSE OF THE
 SPACE AND STAIRS.SEE FBC1006 IN REGARDS TO OPENINGS
 IN STAIRWAYS AND FBC1006.1.4 IN REGARDS TO SPACE UNDER
 THE STAIR.
  
 5.)IT IS NOT CLEAR WHAT CHANGED ON A-3-10AB.PLEASE
 CLARIFY.
  
 6.)REVISION 20 HAD ACCESSIBILITY CORRECTIONS, BUT THE
 SHEET WAS NOT SUBMITTED.SINCE THIS WAS AN AS-BUILT,
 PLEASE ADVISE AS TO HOW THIS WAS RESOLVED.SEE REVIEW
 B 49, "SEE SHEET A2.05 AND A-3-5DA FOR NEW DOOR COMMON
 TO MENS / WOMENS RESTROOM BY GYM."FBC11-4.13.6.
  
 6.)WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE
 LETTER TO EXPEDITE PLAN REVIEW.
  
  
 ALSO REVIEWED - A2.02, A2.04, A31AB, A31B0, A32B0,
 A34B0, A34AB, A36DA, A39AB, A6.07, A10.02, A36B0,
 A10.05, A10.06, A10.07, ID5.0, ID6.0, ID11.0

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status P Date 2006-04-12 Cont ID  
Sent By shill Date 2006-04-12 Time 17:44 Rev Time 0.00
Received By shill Date 2006-04-12 Time 17:44 Sent To  
Notes
2006-04-12 00:00:00PROJECT SPECS
  
 PROVISO - IN ACCORDANCE WITH FBC2001

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status P Date 2005-12-23 Cont ID  
Sent By shill Date 2005-12-23 Time 15:12 Rev Time 0.50
Received By shill Date 2005-12-23 Time 15:12 Sent To PC
Notes
2005-12-23 00:00:00REVISION 21 DATED 11/2/05, SHEETS
 A-3-5AB, A-3-6AB, A-4.02, A-8.04

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status P Date 2005-12-22 Cont ID  
Sent By shill Date 2005-12-22 Time 18:42 Rev Time 0.50
Received By shill Date 2005-12-22 Time 18:42 Sent To  
Notes
2005-12-22 00:00:00REVISED ROOF SPEC, CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2005-12-20 Cont ID  
Sent By shill Date 2005-12-20 Time 14:22 Rev Time 0.50
Received By shill Date 2005-12-20 Time 14:22 Sent To  
Notes
2005-12-20 00:00:00SUBMITTAL
  
 FLASHING SPEC FOR HIGH CURBS

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status P Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 10:00 Rev Time 0.33
Received By jwitmer Date 2005-08-28 Time 10:00 Sent To PC
Notes
2005-08-28 00:00:008-28-05 SUBMITTALS:
 EXSPANSION JOINT @ POOL DECK
 EAVE CLOSURE METAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status F Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 09:22 Rev Time 1.55
Received By jwitmer Date 2005-08-07 Time 08:41 Sent To PC
Notes
2005-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03031778
 ADD: 610 CLEMATIS
 CONT: THE WHITING-TURNER CO
 TEL: (305)409-5957
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION# 20
 ACTION:DENIED
  
 1) SEE SHEET A-2.05 & A-3-5DA FOR NEW
 DOOR COMMON TO MENS /WEMON RESTROOM BY
 GYM.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 2) SEE H MOSER COMMENTS ABOUT RETURN AIR
 NOT SHOWN IN MASTER BEDROOMS FOR UNITS,
 RETURN AIR PLENTUM PAGES.ALL A-4
 DRAWINGS.
  
 NOTE: A-5.17, A-8.02 & A-8.03 , OK JW
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status P Date 2005-07-05 Cont ID  
Sent By shill Date 2005-07-05 Time 17:20 Rev Time 0.25
Received By shill Date 2005-07-05 Time 17:20 Sent To PC
Notes
2005-07-05 00:00:00DUAL LEVEL WATERPROOFING DETAIL (SHOP
 DRAWING)

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status P Date 2005-07-05 Cont ID  
Sent By shill Date 2005-07-05 Time 17:14 Rev Time 0.50
Received By shill Date 2005-07-05 Time 17:14 Sent To PC
Notes
2005-07-05 00:00:00RAILING SHOPS PREPARED BY T KELAHER PE
 POOL FENCE
 HANDRAIL (BALCONY)
 FRENCH BALCONY

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status P Date 2005-06-29 Cont ID  
Sent By jwitmer Date 2005-06-29 Time 07:01 Rev Time 2.22
Received By jwitmer Date 2005-06-29 Time 07:00 Sent To PC
Notes
2005-06-29 00:00:00SUBMITTALS CONCRETE DESIGN MIX SIDEWALKS
 EXTERIOR ARCHITECTURAL TRIM ATTACHMENTS
 DRYVIT SOFFITS
 RECREATIONAL DECK SSECONDARY POUR

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status F Date 2005-05-20 Cont ID  
Sent By shill Date 2005-05-20 Time 11:13 Rev Time 0.50
Received By shill Date 2005-05-20 Time 11:13 Sent To PC
Notes
2005-05-20 00:00:00****CORRECTIONS****
 ROOF PULL TEST SUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED AND SEALED ORIGINALS,
 FAC61G15-23.002.
  
 2.)INCLUDE THE CA NUMBER FOR THE FIRM
 ON THE TITLE BLOCK, FAC61G15-23.002.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2005-05-20 Cont ID  
Sent By shill Date 2005-05-20 Time 10:30 Rev Time 0.50
Received By shill Date 2005-05-20 Time 10:30 Sent To PC
Notes
2005-05-20 00:00:00REVISED ARCADE FRAMING & CALCS
 PREPARED BY M KELAHER, PE 2/9/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status P Date 2005-05-18 Cont ID  
Sent By shill Date 2005-05-18 Time 09:07 Rev Time 0.50
Received By shill Date 2005-05-18 Time 09:07 Sent To PC
Notes
2005-05-18 00:00:00TREMCO FIRESTOP SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status F Date 2005-05-18 Cont ID  
Sent By shill Date 2005-05-18 Time 08:50 Rev Time 0.50
Received By shill Date 2005-05-18 Time 08:50 Sent To PC
Notes
2005-05-18 00:00:00****CORRECTIONS****
 REVISED LIGHTWEIGHT & FLAT ROOFING &
 CALCS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THIS APPEARS TO BE A CHANGE FROM
 THE APPROVED PLAN/NOAS/SPECS.PLEASE
 SUBMIT AS A REVISION TO BE REVIEWED FOR
 CODE COMPLIANCE.
  
 2.)THE NOA FOR THE ELASTIZELL
 LIGHTWEIGHT INSULATING CONCRETE DECK HAS
 BEEN REVISED (SHEET 12 OF 13).THE NOA
 ON THE MIAMI-DADE WEBSITE DOES NOT HAVE
 THIS REVISION.PLEASE ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-17 Time 16:13 Rev Time 0.50
Received By shill Date 2005-05-17 Time 16:13 Sent To PC
Notes
2005-05-17 00:00:00REVISED CABINET SHOPS
  
 PROVISO - DIMENSIONS IN ACCORDANCE WITH
 APPROVED PLAN AND FBC

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status F Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-17 Time 16:00 Rev Time 0.50
Received By shill Date 2005-05-17 Time 16:00 Sent To  
Notes
2005-05-17 00:00:00****CORRECTIONS****
 FPL VAULT DOORS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)THE DOR HAS INDICATED "REVISE AS
 NOTED" ON THE REVIEW STAMP BUT NOTHING
 WAS NOTED ON THE SUBMITTAL.
  
 2.)IS THIS AN EXTERIOR DOOR?WAS THE
 NOA SUBMITTED WITH THE ORIGINAL PERMIT?
 IF IT WAS NOT SUBMITTED AND REVIEWED
 WITH THE ORIGINAL PERMIT, EITHER SUBMIT
 AS A REVISION OR SUBMIT FOR SEPARATE
 PERMIT FOR PLAN REVIEW.
  
 IF IT WAS ALREADY APPROVED UNDER THE
 ORIGINAL PERMIT, A SUBMITTAL AT THIS
 TIME IS NOT NECESSARY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status F Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-17 Time 15:50 Rev Time 0.50
Received By shill Date 2005-05-17 Time 15:50 Sent To PC
Notes
2005-05-17 00:00:00****CORRECTIONS****
 CURB FASTENING DETAIL SUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER
 SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED AND SEALED, FAC61G15-23.002.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status N Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-17 Time 15:48 Rev Time 0.00
Received By shill Date 2005-05-17 Time 15:48 Sent To P
Notes
2005-05-17 00:00:00UNDERMOUNT SINK SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status F Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-17 Time 15:41 Rev Time 0.50
Received By shill Date 2005-05-17 Time 15:41 Sent To PC
Notes
2005-05-17 00:00:00****CORRECTIONS****
 STUCCO/PERLITE SUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)WAS STUCCO USED FOR CALCULATED FIRE
 RESISTANCE ON THE ORIGINAL PLAN?IF
 NOT, SUBMIT A LETTER STATING THIS FROM
 DOR.IF IT WAS, SHOW THAT REQUIRED FIRE
 RESISTANCE IS STILL MET WITH THE
 SUBSTITUTION OF PERLITE FOR SAND IN THE
 STUCCO.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status P Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-20 Time 15:09 Rev Time 0.50
Received By shill Date 2005-05-17 Time 15:09 Sent To PC
Notes
2005-05-17 00:00:00VARIOUS SUBMITTALS
  
 FIRE CAULK FOR TREMBO (P,E,F,M)
  
 UNIT ENTRY DOORS
  
 CLARIFICATION LETTERS PREPARED BY W.COOK
 PE RE: STOREFRONT GLASS
  
 PRECAST TAPCON SPECS
  
 POOL FINISH SPEC
  
 STUCCO TAPE SUBMITTAL
  
 DOOR SWEEPS AND SHOES
  
 DENSGLASS "ARMOR PLUS" SPEC SHEET
  
 UNIT ENTRY DOOR LOCKSETS
  
 STAIRWELL DOOR SUBMITTAL
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status N Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-17 Time 14:47 Rev Time 0.50
Received By shill Date 2005-05-17 Time 14:47 Sent To M
Notes
2005-05-17 00:00:00EXHAUST DUCT METAL WRAP THRU PLENUM
 LETTER TO NMK, ALT MATERIALS & METHODS
 DENIED BY PK, NO NOTES

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-17 Time 14:18 Rev Time 0.50
Received By shill Date 2005-05-17 Time 14:18 Sent To FIRE
Notes
2005-05-17 00:00:00VARIOUS SUBMITTALS
  
 HORIZONTAL SHAFTWALL, DENS ARMOR AT
 STAIRWELLS - PROVISO - FBC 1006.1.3.
  
 FIRE SPRINKLER PIPE & FITTINGS SUBMITTAL
 SHEET
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status F Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-17 Time 13:51 Rev Time 0.50
Received By shill Date 2005-05-17 Time 13:51 Sent To PC
Notes
2005-05-17 00:00:00****CORRECTIONS****
 FIRESTOP SUBMITTAL FROM TREMCO INC.
 PREPARED BY RICHARD REUSS PE (OHIO)
 MARKED "ENGINEERING JUDGMENT"
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A WL NUMBER IS SHOWN WITH
 "ENGINEERING JUDGMENT".IS THIS A
 CHANGE TO THE PLAN?CHANGES TO THE
 APPROVED PLAN ARE REVISIONS, NOT
 SUBMITTALS.TO PRACTICE ENGINEERING IN
 FLORIDA, A FLORIDA PE IS REQUIRED.IS
 ONE NECESSARY IN THIS CASE IF THIS IS A
 UL ASSEMBLY?
  
 PLEASE CLARIFY AND RESUBMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status F Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-17 Time 12:04 Rev Time 0.50
Received By shill Date 2005-05-17 Time 12:04 Sent To PC
Notes
2005-05-17 00:00:00****CORRECTIONS****
 CLARIFICATION LETTER PREPARED BY WILLIAM
 COOK, PE DATED 10/18/04
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLEASE INCLUDE CERTIFICATE OF
 AUTHORIZATION NUMBER ON ALL DOCUMENTS.
 THE SEAL ALSO REQUIRES A DATE.
 FAC61G15-23.002.
  
 2.)PROVIDE THE CALCULATIONS REFERRED
 TO IN THE LETTER REGARDING THE 1/2" SHIM
 GAP.DO THE ANCHORS STILL MEET THE
 MINIMUM EMBEDMENT REQUIREMENT WITH THE
 ADDITIONAL 1/4" OF SHIM SPACE?
  
 3.)ALL SUBMITTALS ARE TO BE REVIEWED
 BY EOR OR DOR PRIOR TO SUBMITTAL TO THE
 CITY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status F Date 2005-05-17 Cont ID  
Sent By shill Date 2005-05-17 Time 11:18 Rev Time 0.05
Received By shill Date 2005-05-17 Time 13:45 Sent To PC
Notes
2005-05-17 00:00:00****CORRECTIONS****
 VARIOUS SUBMITTALS:
  
 CLARIFICATION LETTERS RE: WINDOW/SGD
 INSTALLATION PREPARED BY W.COOK, PE
 (BROMLEY ENGINEERING) DATED 11/12/04
  
 REVISED STACK W/D
  
 1.)ALL SUBMITTALS TO BE REVIEWED BY
 EOR OR DOR PRIOR TO SUBMITTAL TO THE
 CITY.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2005-05-13 Cont ID  
Sent By lmartine Date 2005-05-13 Time 12:36 Rev Time 0.00
Received By lmartine Date 2005-05-13 Time 12:36 Sent To  
Notes
2005-05-13 00:00:00REVISION #18 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2005-04-05 Cont ID  
Sent By jwitmer Date 2005-04-05 Time 10:23 Rev Time 4.44
Received By jwitmer Date 2005-04-05 Time 10:23 Sent To PC
Notes
2005-04-05 00:00:00ROLL PLANS REVISIONS SUBMITTED
 ORIGINALLY IN OCT WITH NEWER SUBMITTALS
 OK JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2005-01-26 Cont ID  
Sent By jwitmer Date 2005-01-26 Time 13:12 Rev Time 0.00
Received By pschmitz Date 2005-02-05 Time 09:21 Sent To  
Notes
2005-01-26 00:00:0001-26-05 TRELLIS/ TEAHOUSE SHOP
 DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2005-01-26 Cont ID  
Sent By jwitmer Date 2005-01-26 Time 11:39 Rev Time 0.33
Received By jwitmer Date 2005-01-26 Time 11:38 Sent To  
Notes
2005-01-26 00:00:001-26-05 CMU CLIPS/ BOLLARDS IN GARAGE OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2004-12-16 Cont ID  
Sent By jwitmer Date 2004-12-16 Time 13:52 Rev Time 3.00
Received By jwitmer Date 2004-12-16 Time 08:10 Sent To  
Notes
2004-12-16 00:00:0012-16-04 SUBMITTALS:
 EXSPANSION JOINT MATERIAL
 THOROSSEAL
 SPRAYED TEXTURED STUCCO
 WINDOW CAULK

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2004-12-16 Cont ID  
Sent By jwitmer Date 2004-12-16 Time 08:09 Rev Time 1.00
Received By jwitmer Date 2004-12-16 Time 08:09 Sent To  
Notes
2004-12-16 00:00:0012-16-04 POUR LETTERS,SHORING LETTERS,

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2004-11-19 Cont ID  
Sent By jwitmer Date 2004-11-19 Time 08:53 Rev Time 5.00
Received By jwitmer Date 2004-11-18 Time 08:53 Sent To  
Notes
2004-12-02 00:00:0011-18-04/ 11-19-04 REVISIONS TO ROLL
 PLAN- OK , PLANS DO NOT MATCH CITY SET,
 DESIGNER OF RECORD SUBMITTED A ROADMAP
 EXPLAINING THEY STARTED RENUMBERING
 REVISIONS AFTER PLANS WERE PERMITED.
 ALL
 REVISIONS MADE TO PLANS BEFORE PERMIT
 ARE NOT HIGHLIGHTED NOR NUMBERED, THEY
 WERE INCORPORATED INTO THE BODY OF THE
 PLAN, THEREFORE MAKING IT "VERY
 DIFFICULT" TO TRACK THE PROJECT. WE HAVE
 LET THE DESIGNERS OF RECORD KNOW THIS IS
 NOT AN ACCEPTED PRACTICE AND WISH ON
 FUTURE PROJECTS THEY ALSO CONSULT WITH
 THE BUILDING DEPARTMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2004-11-19 Cont ID  
Sent By jwitmer Date 2004-11-19 Time 13:36 Rev Time 5.50
Received By jwitmer Date 2004-11-18 Time 08:07 Sent To PC
Notes
2004-11-19 00:00:0011-19-04 SUBMITTALS
 PT 25,26 ROOF DT NORTH
 ROOF SYSTEMS- FLAT,TILE, LIGHTWEIGHT &
 CALS
 CABINET SHOP DRAWINGS
 FLOOR 6, POR # 3
 PT 27,28 ROOF SOUTH
 BALCONY ANCHOR CEMENT
 FIBERGLASS FOR STUCCO

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2004-10-06 Cont ID  
Sent By csiegber Date 2004-10-28 Time 16:43 Rev Time 5.50
Received By jwitmer Date 2004-10-06 Time 07:28 Sent To PC
Notes
2004-10-06 00:00:00SUBMITTALS, FRP DOME ASSEMBLY,KILZ
 SEALANT SPRAY,RAILING POWDER COAT,FIRE
 RETARDANT LUMBER,CONCRETE POUR LETTERS,
 TRASH COMPACTOR,EXHAUST FANS,MESH TAPE
 FOR DRYWALL,MASONRY GROUT ALTERNATE,
 PROSET FIRE SLEEVE,TRUSS DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-10-05 Time 11:55 Rev Time 0.75
Received By jwitmer Date 2004-08-25 Time 10:23 Sent To  
Notes
2004-08-25 00:00:00SUBMITTAL: GARAGE STRIPPING & WHEEL
 STOP.
 POUR LETTER FLOOR 5, POUR # 1
 ROOFING SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-08-18 Time 15:13 Rev Time 5.55
Received By jwitmer Date 2004-08-17 Time 14:30 Sent To  
Notes
2004-08-17 00:00:00SUBMITTALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status F Date 2004-08-06 Cont ID  
Sent By csiegber Date 2004-08-12 Time 15:55 Rev Time 10.00
Received By jwitmer Date 2004-08-06 Time 08:05 Sent To  
Notes
2004-08-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03031778
 ADD: 610 CLEMATIS ST
 CONT: THE WHITING-TURNER CO
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 REVISIONS
 ACTION: DENIED
  
 1) AS ASKED FROM FIRST MEETING OVER RE-
 VISIONS THE SUBMITTED PLANS DO NOT MATCH
 THE APPROVED CITY PLANS AS FAR AS THE
 NUMBERING SYSTEM. CITY APPROVED PLANS
 MAY HAVE UP TO 13 REVISIONS ON THE NEW
 PLANS SEQUENCE STARTS OVER AGAIN.
  
 2) REVISIONS FULL ROLL ARCH & STRUC
 DRAWINGS DENIED:
 REVISIONS WHITE OUT USED,
 104.2.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT".
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 WHERE THE WHITE OUT WAS USED THE
 REVISION DOES NOT HAVE THE SIGNATURE &
 DATE OF THE ARCHITECT OF RECORD.
 A-4.03 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.04 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.04ASEC 1 WHITE OUT/ HAND WRITTEN "B"
 ELE DON,T NUMBERING SEQUENCE
 A-4.06 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.07 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.07 MISSING ELE 1,2,3 OR MIS-
 LABELED
 A-4.08 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.09 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.10 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A4-10.1SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.11 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.16 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.16ASEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.18 SEC 1 WHITE OUT/ TYPE_ BLANK
 A-4.21 SEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.21ASEC 1 WHITE OUT/ HAND WRITTEN "B"
 A-4.24 SEC 1 WHITE OUT/ HAND WRITTEN "B"
  
 3) SHEET F1/F2 FOUNTAIN SHEETS:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) FOUNTAIN SHEETS F1/F2 REQUIRE SEPER-
 ATE PERMITS, NOT PART OF THIS PERMIT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-08-04 Time 11:55 Rev Time 1.72
Received By jwitmer Date 2004-07-26 Time 09:27 Sent To PC
Notes
2004-07-26 00:00:00STOREFRONT DOOR& WINDOW SYSTEM,
 WINDOW SUBMITTALS AND CAST STONE. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2004-07-21 Cont ID  
Sent By jwitmer Date 2004-07-21 Time 16:47 Rev Time 4.22
Received By jwitmer Date 2004-07-21 Time 16:47 Sent To  
Notes
2004-07-21 00:00:0018 SUBMITTALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-21 Time 14:40 Rev Time 0.50
Received By lmartine Date   Time   Sent To  
Notes
2004-07-14 00:00:00TABLE SHORINGS OK LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2004-06-17 Cont ID  
Sent By csiegber Date 2004-07-02 Time 10:32 Rev Time 3.00
Received By jwitmer Date 2004-06-17 Time 12:05 Sent To PC
Notes
2004-06-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03031778
 ADD: 610 CLEMATIS ST
 CONT: THE WHITING TURNER
 TEL: (954)868-4244
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 RE: SHOP DRAWINGS
 ACTION: DENIED
  
 1) LOW PRESSURES ON END ZONES SEE
 ENGINEERS VALUES
 2) MULLIONS: LIMITATIONS SEE PRODUCT
 APPROVALS 96" LIMITATION. (3.1)
 3)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2004-06-16 Cont ID  
Sent By jwitmer Date 2004-06-16 Time 10:14 Rev Time 0.33
Received By jwitmer Date 2004-06-16 Time 10:14 Sent To PC
Notes
2004-06-16 00:00:00BUILDING PLAN REVIEW
 PERMIT:030317768
 ADD: 610 CLEMATIS ST
 CONT: THE WHITING-TURNER
 TEL: (954)868-4244
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SUBMITTAL: STRUCTURAL STYROFOAM
 ACTION: DENIED
  
 1) F102.2.7 FIRE DISTRICT.
 FBC* F102.2.7ARCHITECTURAL TRIM,
 ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2004-06-16 Cont ID  
Sent By jwitmer Date 2004-06-16 Time 09:46 Rev Time 0.25
Received By jwitmer Date 2004-06-16 Time 09:46 Sent To PC
Notes
2004-06-16 00:00:00EXTERIOR WALLS RAISED TRIM REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2004-05-25 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 08:54 Rev Time 0.55
Received By jwitmer Date 2004-05-25 Time 09:45 Sent To  
Notes
2004-05-25 00:00:00SHORING LETTER PT 1N, EL 29'-6" QUAD B
 PT 8 & 9

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-20 Time 14:24 Rev Time 2.50
Received By jwitmer Date 2004-05-03 Time 15:46 Sent To  
Notes
2004-05-03 00:00:00SUBMITTALS:
 SHORING/ RESHORING EL 43'-6"
 CONCRETE BOLLARD/ ROSEMARY ST
 DENSE GLASS ADD INFO/ FIRE/WICK
 REVISION PT 6&7

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:41 Rev Time 0.50
Received By jwitmer Date 2004-04-22 Time 12:26 Sent To PC
Notes
2004-04-22 00:00:00BUILDING PLAN REVIEW
 PERMIT:03031778
 ADD: 610 CLEMATIS ST
 CONT: THE WHITING-TURNER
 TEL: (954)868-4244
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SUBMITTAL
 ACTION: DENIED
 RE: POUR LETTER LOWER GROUND SOD EL
 29'-6"/25'-0" #1& #2
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:20 Rev Time 5.00
Received By jwitmer Date 2004-04-22 Time 07:49 Sent To  
Notes
2004-04-22 00:00:00VARIOUS SUBMITTALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2004-02-23 Cont ID  
Sent By csiegber Date 2004-04-13 Time 16:29 Rev Time 0.50
Received By shill Date 2004-02-23 Time 09:23 Sent To  
Notes
2004-02-23 00:00:00SUBMITTALS OK BY HP
  
 VOLCLAY WATERSTOP
 BACKSHORE @ RETAINING WALLS
 SHORING TO EL 15

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-02-13 Time 15:19 Rev Time 1.10
Received By jwitmer Date 2004-01-27 Time 13:54 Sent To  
Notes
2004-01-27 00:00:0001-27-04 SHOP DRAWINGSJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-01-07 Cont ID  
Sent By csiegber Date 2004-01-09 Time 10:32 Rev Time 1.50
Received By jwitmer Date 2004-01-07 Time 15:13 Sent To  
Notes
2004-01-07 00:00:00SUBMITTAL #1:DEC.03/03
 A) F-77 CONSTRUCTION GROUT
 B) CLEAR POLYETHYLENE SHEETING
 C) VINYL CONCRETE PATCHER
 D) FAST SET CEMENT MIX
 SUBMITTAL# 2:DEC.03/03
 A) WATERSTOP
 B) BONDING AGENT
 C) EXSPANSION JOINT
 D) FORM OIL
 E) EPOXY
 F) WIRE MESH
 SUBMITTAL#_DEC.03/03
 A) CONCRETE PLACING BOOM
 SUBMITTAL#_DEC.03/03
 A) TERMITE TREATMENT
  
 SUBMITTAL#_DEC. 09/03
 A) TARMAC/ RINKER DESIGN MIXES

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-11-21 Cont ID  
Sent By csiegber Date 2003-12-09 Time 16:16 Rev Time 2.00
Received By jwitmer Date 2003-11-21 Time 14:59 Sent To  
Notes
2003-11-21 00:00:00BUILDING PLAN REVIEW
 PERMIT:03031778
 ADD: 610 CLEMATIS ST
 CONT:THE WHITING-TURNER CONTRACTING
 TEL: (954)776-0800
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 BUILDING REVIEW
 ACTION: APPROVED
 PROVISO: THRESHOLD BUILDING FL S. S.
 553.71(7)
 THRESHOLD COMPANY AND INSPECTOR TO BE
 SIGNED ON WITH CITY BEFORE ISSUANCE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-09-26 Cont ID  
Sent By jwitmer Date 2003-09-26 Time 14:40 Rev Time 22.00
Received By jwitmer Date 2003-09-26 Time 14:40 Sent To  
Notes
2003-09-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03031778
 ADD: 610 CLEMATIS STREET
 CONT: WHITING- TURNER CONTRACTING
 TEL: (954)776-0800
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ARCH B & A BERMELLO AJAMIL &
 PARTNERS
 BORAS GRANDASEN (305) 860-3822
 HECTOR VALVERDE (305) 859-2050
  
 ENG:DER DE LOS ENGINEREERING INC
 (305) 665-2778
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 2) THRESHOLD BUILDING FL. S.S.553.71(7)
 THRESHOLD COMPANY AND INSPECTOR TO BE
 SIGNED ON WITH CITY BEFORE ISSUANCE.
 CONTACT: DON NEELY 805-6665
 3) SHEETS A-3.1AB/ A-3.1BC THE ENTERIOR
 DOORS TO UNITS ARE TO BE THE "PRIMARY
 ENTRY DOORS" FAIR HOUSING ACT INDICATE
 MAIN ENTRY ON PLAN NOT SECONDARY.
 4) POOL DECK SHEET A-2.06 THERE IS ONLY
 ONE ELEVATION GIVEN, FOR THE WALKING SUR
 FACES, PROVIDE SLOPE FOR RAMPS AND ELE-
 VATIONS, TO SEE IF HANDRAILS ARE RE-
 QUIRED.
 5) SHEET A-3-5DA CORRIDOR 154 LEVEL 42
 (NORTH) INDICATES THE USAGE OF RAMPS,
 BUT NO ELEVATION IS PROVIDED NOR SLOPE
 FOR THE RAMPS?
 6)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 A) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 SHEET S-1.4.1- S-1.4.3 INDICATE
 THE OPENING PRESSURES FOR THE VARIOUS
 WALL OPENINGS. THE ONLY PROBLEM IS NO
 END ZONES ARE GIVEN FOR THE WALL, CREAT-
 ING A HIGHER PRESSURE ZONE,ALSO AT THE
 ROOF OR TOP FLOORS. UNDER ASCE7-88 THE P
 RESSURES FOR A 80' BUILDING AT ZONE@ 7
 END ZONE 110.3, EVALUATE ROOF LOADS AT
 ROOF LEVEL. WHY SUCH A DIFFERENCE?
 7) THE PRODUCT APPROVALS MIAMI-DADE
 ARE MISSING THE TECHNICAL SHEETS. THESE
 SHEETS INDICATE WHAT THE PRESSURES ARE
 APPROVED FOR, ALSO IF REINFORCEMENT
 IS REQUIRED.
 8) FENESTRATION TESTING REPORTS RE-
 QUIRE SITE SPECIFIC ENGINEERING:
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.SEE ATTACHMENT.
 9) DEPENDING ON THE REPORT A SEPARATE
 MULLION REPORT MAY BE REQUIRED.
 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
 10) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
 11) SHEET A-1 GENERAL NOTES: 34, MINI
 MUM FLAME SPREAD TO BE IN CONFORMANCE
 WITH, ID-11.1 INTERIOR FINISHES, NO IN-
 FORMATION ABOUT TABLE 803.3 FLAME SPREAD
 / SMOKE DEVELOPMENT.ANSWER COMPLIANCE
 BUT WHERE?
 12) EXTERIOR WALLS PRESSURE TREATED
 FURRING ALLOWED IF THE FOLLOWING REQUIRE
 MENTS ARE MET, 803.9.1. ANSWER SEE NOT
 A8.03 NO MENTION OF 803.9.1!!!!
 13) GYMNASIUM A-2 ASSEMBLY INDICATE
 2HR WALLS W/ 1 1/2 HR PROTECTIVE.
 ANSWER COMPLIANCE, WHERE?
 14) SHEET A-10.02 DETAILS 1&6 EXPAND-
 ED POLYSTRYRENE MOLDING, THIS MATERIAL I
 S NOT ALLOWED IN THE FIRE DISTRICT SEE
 102.7 ARCHITECTURAL TRIM. ANSWER: SEE AT
 TACHED PRODUCT CONTROL APPROVAL.???????
 15) SEE DOOR G-37 PART OF EGRESS,
 STAIR TOWER# 1, SHOULD SWING OUT.
 16)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-04-17 Cont ID  
Sent By jwitmer Date 2003-04-16 Time 16:24 Rev Time 22.22
Received By jwitmer Date 2003-04-16 Time 16:24 Sent To  
Notes
2003-04-16 00:00:00BUILDING PLAN REVIW
 CONTINUED 4/16/03
  
 *****STAIR TOWERS******
 42) SECTION 1005.6.6 APPROVED BARRIERS:
 A STAIRWAY IN A SMOKEPROOF ENCLOSURE
 SHALL NOT CONTINUE BELOW GRADE LEVEL
 UNLESS AN APPROVED BARRIER IS PROVIDED
 AT THE GROUND LEVEL TO PREVENT PERSONS
 FROM ACIDENTALLY CONTINUING INTO THE
 BASEMENT.
 1007.1.5 ENCLOSED EXIT STAIRWAYS
 THAT CONTINUE BEYOND THE FLOOR OF DIS-
 CHARGE SHALL BE INTERRUPTED AT THE FLOOR
 OF DISCHARGE BY PARTITIONS, DOORS OR
 OTHER EFFECTIVE MEANS.
 STAIR TOWERS 1, 2& 3 HAVE THIS CONDI
 TION THAT REQUIRES SOME MEANS TO PREVENT
 A PERSON FROM TURNINGIN THE WRONG
 DIRECTION AND DECENDING INTO THE
 BASEMENTS.
  
 43)SECTION 1006.1.3.2 EXTERIOR WALLS OF
 AN ENCLOSED STAIRWAY SHALL COMPLY WITH
 THE REQUIREMENTS OF TABLE 600 FOR EXTER-
 IOR WALLS. WHERE NONRATED WALLS OR
 UNPROTECTED OPENINGS ARE USED TO ENCLOSE
 THE EXTERIOR OF THE STAIRWAY, THE BUILD
 ING ENCLOSURE WALLS WITHIN 10 FT HORIZON
 TALLY OF THE NONRATED WALLS OR UNPROTECT
 ED OPENINGS SHALL BE CONSTRUCTED AS REQU
 IRED FOR STAIRWAY ENCLOSURES, INCLUDING
 OPENING PROTECTIVES, BUT NEED NOT EXCEED
 1-HR FIRE RATING W 3/4 HOUR OPENING PROT
 ECTIVE. THIS CONSTRUCTION SHALL EXTEND
 VERTICALLY FROM THE GROUD TO A POINT
 10 FT ABOVE THE TOP MOST LANDING OF THE
 STAIRWAY OR TO THE ROOF LINE, WHICHEVER
 IS LOWER.
 STAIRWELLS 1,2 & 3 HAVE THIS CONFIG
 URATION WHERE THE WINDOWS/ DOORS EITHER
 SIDE OF THE OPENING OR ABOVE THE OPENING
 ARE NOT RATED.
 STAIRWELL # 3 SEE 1005.6.8.1 FOR
 SMOKEPROOF ENCLOSURE BY NATURAL VENTIL-
 ATION VESTIBULE AS OPTION.
  
 43) RETAIL AREAS, 1004.1.2 EVERY ROOM OR
 TENANT SPACE WHICH HAS AN OCCUPANT LOAD
 OF 50 OR MORE PERSONS SHALL NOT HAVE
 LESS THAN 2 EGRESS DOORS, REMOTELY
 PLACED. IF THESE SPACES ARE FITTED OUT
 AS RESTARAUNTS, THE BACK EXIT IF THROUGH
 THE KITHEN CAN'T BE COUNTED AS AN EXIT!
 JUST A WORD OF CAUTION!
  
 44) 1012.1.2 EGRESS DOORS SHALL SWING IN
 THE DIRECTION OF TRAVEL (1) WHEN SERVING
 AN OCCUPANT LOAD OF 50 OR MORE, SEE
 GYMNASIUN DOOR! PROVIDE ADDITIONAL INFO
 FOR THE CARD READER ON THIS DOOR, LOSS
 OF POWER FAIL SAFE OPEN OR FAIL SAFE
 SECURE?
  
 45) ID-9-0 ELEVATORS 3003.4.1 PROVIDE
 LAYOUT INDICATING STRETCHER REQUIREMENTS
  
 46) ELEVATOR SIGNAGE 3003.3.
  
 47)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 0BOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 SHEET A-10.02 DETAIL # 2/ WHAT IS THE
 OVERFLOW SCUPPER SIZE?
  
 48) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 49) 1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 50) SHEET A-5.14 LOWER PARKING FLOOR,
 THE 7'-0" CLEAR FLOOR HEIGHT MUST BE
 MAINTAINED, THIS IS A MINIMUM!!!!
  
 51) INDICATE WHAT HR RATING THE CONCRETE
 BLOCK USED WILL BE, EQUIVALENT THICKNESS
 WILL BE FOR THE MANUFACTURER USED?
 TABLE 709.3.1.
  
 52) SHEET A10.07 FABRIC CANOPY- FABRIC
 IS TO BE FIRE RETARDANT TREATED FABRIC.
 F102.2.8.
  
 53) SHEET A-10.10 TEAHOUSE/ TRILLIS
 NO TYPE VI CONSTRUCTION IN THE FIRE
 DISTRICT
  
 54) ID-2.2 MAIN LOBBY CURVED SOFFITS,
 DROPPED CEILING, FIBERGLASS PLASTIC
 DOME( ID-4.1 DETAIL 6) ADDITIONAL INFO,
 HOW TO HANG, MAN SPEC FLAME SPREAD/
 SMOKE DEVELOPMENT?
  
 55) ID-4.2 MAIL KIOSK DETAILS 3&6, REACH
 RANGES?11-4.2.5/11-4.2.6 FL ACC CODE.
  
 56)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-16 Cont ID  
Sent By jwitmer Date 2003-04-16 Time 12:34 Rev Time 22.22
Received By jwitmer Date 2003-04-16 Time 11:46 Sent To  
Notes
2003-04-16 00:00:00BUILDING PLAN REVIEW
 CONTINUED 4/16/03
  
 19) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 20) 1707.4.5.2 MULLIONS SHALL BE
 DESIGN-ED TO TRANSFER THE DESIGN
 PRESSURE LOADSAPPLIED BY THE WINDOW OR
 DOOR ASSEMBLIESTO THE ROUGH OPENING
 SUBTRATE.
  
 21)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND
 TEST-ED FOR A PERIOD EQUAL TO THE
 QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 22)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD. SEE ATTACHMENT.
  
 23) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 24) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE
 ANCHORED IN ACCORDANCE WITH THE
 PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS
 DEMONSTRA-TED BY ACCEPTED ENGINEERING
 PRACTICES.
  
 25) SECTIONS; 103.6, 1606.4, 1707.4
 WPB IMPLEMENTATION STANDARD FOR HURRI-
 CANE MISSLE IMPACT STANDARD, QUESTION
 # 14, ARE REMOVABLE STORM PANELS APPRO-
 PRIATE FOR USE ON VERY LARGE, MID OR
 HIGH-RISE STRUCTURES? NO, EXCEPT ON THE
 GROUND FLOOR. ON COMMERCIAL AND MULTI-
 UNIT RESIDENTIAL STRUCTURES, ABOVE THE
 FIRST LEVEL, IMPACT RESISTANT OR
 PERMANENTLY AFFIXED PROTECTIVE DEVICES
 SHALL
 REQUIRE THE WRITTEN APPROVAL OF THE
 BUILDING OFFICIAL.
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE
 USEDFOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE
 INSTALLATIONSCHEDULE SUMMARIZING &
 IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL
 PRES-SURE ZONES, SLAT TYPES, ETC.,
 SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 26) SHEET S-5.1 STRUCTURAL NOTE (9):
 BALCONY / TERRACE RAILINGS & STAIR
 RAIL-INGS SHALL BE DESIGNED TO RESIST A
 LOAD OF 50 LBS. APPLIED IN ANY
 DIRECTION,
 (1608.2.2.2) THIS SECTION REFERS TO
 GAURD RAILS WITHIN DWELLING UNITS.
 1608.2.2.3 REFERS TO EXTERIOR GUARD
 RAILSYSTEMS, BEING ABLE TO RESIST A 200
 LB
 CONCENTRATED HORIZONTAL LOAD APPLIED ON
 A 1 SQ FT AREA AT ANY POINT IN THE
 SYSTEM INCLUDING INTERMEDIATE RAILS OR
 OTHER ELEMENTS SERVING THIS PURPOSE.
  
 27) SHEET S-1.38 PREFAB METAL TRUSS
 CON-NECTIONS SEE SCHEDULE "D,E& F" THE
 2003 USP CATOLOG, FORMULTIPLE ANCHOR
 INSTAL- LATIONS NOTE: MULTIPLE
 INSTALLATIONS NOTCLOSER THAN 8", A
 DERATING FACTOR WILL
 BE REQUIRED BECAUSE CONE FAILURE.
 *****NEW IN FL CODE****
 1609.4.3 LOAD REDUCTIONS!!!!!
  
 28) SHEET A-1 GENERAL NOTES: 34 MINIMUM
 FLAME SPREAD TO BE IN CONFORMANCE WITH,
 ID-11.1 INTERIOR FINISHES, NO INFORMA-
 TION ABOUT TABLE 803.3 FLAME SPREAD/
 SMOKE DEVELOPMENT.
 TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 29) EXTERIOR WALLS PRESSURE TREATED
 FURRING ALLOWED IF THE FOLLOWING
 REQUIREMENTS ARE MET, 803.9.1.
  
 30) INTERIOR WALLS, BACKING TO BE NON-
 COMBUSTIBLE MATERIAL OR FIRE RETARDANT
 TREATED WOOD. 609.2.1.
  
 31) GYMNASIUM AN A-2 SMALL ASSEMBLY,
 INDICATE 2 HR WALLS W/ 1 1/2 HR PROTEC-
 TIVES.
  
 32) GYMNASIUM REQUIRES 2 MEANS OF
 EGRESS11-4.1.3 (9) IN A BUILDING OR
 FACILITIESOR PORTION S OF BUILDINGS OR
 FACILITIES REQUIRED TO BE ACCESSIBLE,
 ACCESSIBLE
 MEANS OF EGRESS SHALL BE PROVIDED IN
 THESAME NUMBER AS REQUIRED BY THE LOCAL
 BUILDING LIFE SAFETY REGULATIONS.
 THE GYM DOES HAVE 2 EXITS BUT ONLY
 ONE IS ACCESSIBLE!!!
  
 33) GYMNASIUM EGRESS DOORS, 1019.7.2
 EACH DOOR IN A MEANS OF EGRESS FROM AN
 AREA OF A GROUP A OCCUPANCY MAY BE PRO-
 VIDED WITH A LATCH OR LOCK ONLY IF IT
 ISPANIC HARDWARE OR FIRE EXIT HARDWARE,
 WHICH RELEASES WHEN 15 LBS IS APPLIED
 TOTHE RELEASING DEVISE. THIS DOOR ALSO
 INDICATES A CARD READER, PROVIDE
 INFORMATION FOR FAIL SAFE RELEASE?
  
 34) SHEET A-3-5DA STAIRWELL # 1, HAS A
 ROOMIN THE STAIRWELL, NO DESIGNATION?
 IS THIS A AREA OF REFUGE? INACCESSIBLE
 TO HANDICAPPED PEOPLE!
 STAIWELL# 1 HAS NO DOOR AT THE END
 OF THE VERTICAL SECTION, TO CONTINUE
 THERATING OF 2 HRS,ALSO SEE 1006.1.3.1
 FOR WHAT IS ALLOWABLE IN THE STAIRWELL.
  
 35) 705.2.4.3 REFUSE CHUTE ACCESS ROOMS.
 ACCES OPENINGS FOR REFUSE CHUTES SHALL
 BE LOCATED IN ROOMS OR COMPARTMENTS
 COMPLETELY ENCLOSED BY CONSTRUCTION &
 OPENING PROTECTIVES IN ACCORDANCE WITH
 TABLE 705.1.2. ACCESS OPENINGS TO REFUSE
 CHUTES SHALL NOT BE LOCATED IN EXIT
 ACCESS CORRIDORS OR EXIT ENCLOSURES.
 ***SHEETA-3-6AB***
 36) ELEVATOR LOBBY VS ENTRY DOOR TO
 SUITE, COMMON TO ALL FLOORS.
 412.6.3 REVIEW WHAT DORS AREN'T ALLOWED
 IN ELEVATOR LOBBIES, GUEST ROOM DOOR
  
 37)SAME SHEET GRID 8/C, STORAGE UNIT,
 WHAT TYPE OF STORAGE, S1 OR S2?
 WALL RATING?
  
 38) UNIT H210 BALCONY DETAIL 3/A8.11
 NO SUCH DETAIL?
  
 39) SHEET A-8.12 GUARDRAILS: WITHIN
 INDIVIDUAL LIVING UNITS OR GUEST ROOMS
 MAY BE 36",1026.5.1.
 EXTERIOR GUARDRAIL HEIGHT,MINIMUM IS
 42"1015.2.
 1015.3 OPENINGS: SO A 4" SPHERE CAN NOT
 PASSTHROUGH ANY OPENING. A BOTTOM RAIL
 OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER SPHERE
  
 40) STAIRWAY GUARDRAILS 1015.3 SEE
 EXCEPTION (1) A 6" SPHERE SHALL NOT
 PASSTHROUGH THE TRIANGLE OPENING FORMED
 BY
 A TREAD, RISER AND BOTTOM OF A GUARDRAIL
 SEE A-10.07 DETAIL #2.
  
 41) SHEET A-10.02 DETAILS 1 & 6
 RE: EXPANDED POLYSTYRENE MOLDING, THIS
 MATERIAL IS NOT ALLOWED IN THE FIRE
 DISTRICT. SEE F 102.2.7 ARCHITECTURAL
 TRIM ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT SHALL BE CONSTRUCTED OF
 APPROVED NONCOMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.
  
 THIS SESSION OF PENEMATION WILL NOT
 EXCEPT MORE THAN 200 LINES, A THIRD
 BUILDING REVIEW WILL NEED TO BE OPENED.
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-16 Cont ID  
Sent By jwitmer Date 2003-04-16 Time 07:00 Rev Time 22.22
Received By jwitmer Date 2003-04-16 Time 07:00 Sent To  
Notes
2003-04-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03031778
 ADD: 610 CLEMATIS ST
 CONT: WHITING -TURNER CONTRACTING
 TEL: (954)776-0800
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ARCH: B & A BERMELLO.AJAMIL &
 PARTNERS INC
 TEL: (305)859-2050
 FAX: (305)859-9638
  
 ENG:DER DE LOS REYE ENGINEERING INC
 TEL: (305)665-2778
 FAX: (305)665-2793
  
 BUILDING PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE DOCUMENTATION OF UNITY OF
 TITLE, SECOND THAT THE CITY ABANDED THE
 ALLEY WAY.
  
 3)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 FOR THRESHOLD BUILDINGS FOR THE PER-
 MIT SET OF PLANS, PROVIDE (3) THREE COP-
 IES OF ALL DOCUMENTS, INCLUDING SHOP
 DRAWINGS, PRODUCT APPROVALS, LETTERS,
 ETC. EXCEPTION: THE STRUCTURAL CALCULA-
 TIONS (7 BOOKS).
  
 4) PLANS INDICATE THAT THIS BUILDING
 IS PLANNED TO BE A CONDOMINIUM. BEFORE
 THE BUILDING WILL RECEIVE A CERTIFICATE
 OF OCCUPANCY THE DOCUMENT " DECLARATION
 OF CONDOMINIMUM" IS TO BE SUBMITTED TO
 THE STATE, APPROVED AND THEN RECORDED
 AT THE COUNTY CLERK OF THE COURT. THE
 CITY WILL NEED TO HAVE A RECORDED COPY
 FOR OUR RECORDS, ADDRESSING AND NOTIFICA
 TION OF THE PROPERTY APPRAISERS OFFICE.
  
 5) AMENDMENTS TO APPENDIX F, FLORIDA
 BUILDING CODE, 2001 ED. LOCAL FIRE
 DISTRICT, SECTIONS 102- 105 SHALL APPLY
 TO THIS STRUCTURE. SEE ATTACHMENTS.
  
 6) CHAPTER 13, FLORIDA ENERGY CODE,
 SECTION 400, ENERGY CALCULATIONS FOR THE
 WHOLE BUILDING.
  
 7) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PLEASE PROVIDE SOILS REPORT PREFORMED BY
 ARDAMAN & ASSOCIATES, GEOTECNICAL
 REPORT # 01-2233 BASED ON 10-01-02
 INVESTIGATION. (VIBROFLOTATION).
 3 SIGNED/ SEALED COPIES.
  
 8) REQUIREMENTS FOR SPECIAL FOUNDATION
 PERMIT:
 A) THRESHOLD INSPECTOR TO BE SIGNED ON
 WITH DON NEELY THRESHOLD/ RESIDENT
 INSPECTOR PROGRAM COORDINATOR @ EXT.
 6665.
 B) FILED SOILS REPORTS.
 C) PROVIDE THE DESIGN FOR SHEET PILE
 BY SPECILITY ENGINEER, TO BE REVIEWED
 BY & ACCEPTED BY THE ENGINEER OF RECORD
 ( HECTOR DE LOS REYES).
 D) COUNTY IMPACT FEES PAID FOR THE
 COMPLETE BUILDING.
 E) STATE RADON FEES TO BE PAID TO CITY.
  
 104.4.5. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT
 OR ENLARGE A BUILDING HAS BEEN FILED, &
 PENDING ISSURANCE OF SUCH PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR
 THE FOUNDATION ONLY, UPON WRITTEN RE-
 QUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PRO-
 CEEDING AT HIS OR HER OWN RISK AND WITH-
 OUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE RE-
 QUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODE.
 *****FAIR HOUSING ACT*****
 9)THE PRIMARY ENTRY DOOR OF COVERED
 DWELLING UNITS IS PART OF PUBLIC AND
 COMMON USE SPACES, THEREFORE, IT MUST BE
 ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE,
 I.E., MEET THE ANSI REQUIREMENTS OF
 4.13 DOORS.
 SHEET A-3-5AB,5BC & 5DA UNITS @ ELE.
 42', ENTRY VS, SECONDARY ENTRY DOORS,
 THE PLANS INDICATE THAT THE ENTRY (PRI-
 MARY) DOORS ARE TO THE EXTERIOR, THE
 PRIMARY DOORS ARE TO BE ON AN ACCESSIBLE
 ROUTE, THE COORIDOR ENTRY DOOR SINCE IT
 IS SERVED BY AN ELEVATOR. LEVER HANDLE
 OR OTHER EASY TO USE DOOR HARDWARWE,
 ANSI 4.13.9.
  
 10) A-3.1AB/ A-3.1BC LOWER BASEMENTS,
 NOT ON A ACCESSIBLE ROUTE, PLANS DO NOT
 INDICATE SIGNAGE "NOT ACCESSIBLE ROUTE".
  
 11) POOL, POOL DECK AND SURROUNDING
 AREAS ARE TO BE ACCESSIBLE. NO INFORMA-
 TION IS PROVIDED FOR THIS AREA.
  
 12)FAIR HOUS REGUIREMENT 7.2 USEABLE
 BATHROOMS(I) NOTE: CABINETS UNDER LAVA-
 TORIES ARE ACCEPTABLE PROVIDED THE BATH-
 ROOM HAS SPACE TO ALLOW A PARALLEL
 APPROACH BY A PERSON IN A WHEELCHAIR;
 IF PARALLEL APPROACH IS NOT POSIBLE WITH
 IN THE SPACE, ANY CABINETS PROVIDED
 WOULD HAVE TO BE REMOVABLE TO AFFORD THE
 NECESSARY KNEE CLEARENCE FOR FORWARD
 APPROACH.
  
 13) POOLS ARE TO HAVE AN EFFICTIVE
 BARRIER ( PUBLIC POOLS DOH RULE 64E-9
 FL ADMINISTRATIVE CODE) INDICATE WHERE
 THIS WILL BE AN ACCESSIBILITY THROUGH
 THE ENCLOSURE?
 IF CONCIDERED A PRIVATE POOL SEE SEC-
 TION 424.2.17.(1) -(8).
  
 14) SHEET A-3-5DA CORRIDOR 154 LEVEL 42
 (NORTH) INDICATES THE USAGE OF RAMPS BUT
 NO ELEVATIONS ARE PROVIDED?
 *****GENERAL BUILDING COMMENTS******
 15) IT IS DIFFICULT TO DO PLAN REVIEWS
 WITHOUT A LEGEND INDICATING WHAT TYPE
 OF INFORMATION IS BEING RELAYED THE
 BOX WITH A NUMBERIN IT???????ALL PAGES!
  
 16) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 17)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 18)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) FIXED WINDOWS INCLUDING STORE FRONT
 B) SINGLE HUNG WINDOWS
 C) MULLIONS VERTICAL & HORIZONTAL
 D) EXTERIOR GLAXED DOORS BOTH SWINGING
 AND SLIDING DOORS.
 E) SOLID EXTERIOR DOORS
 F) EXTERIOR DOORS W/ TRANSOMS (1 UNIT)
 G) OVERHEAD GARAGE DOOR
 H) LOUVERED VENTS
 I) ROOFING ASSEMBLIES:(II) ROOF TILE
 (III) FLAT ROOF W/ INSULATION
  
 COMMENTS TO BE CONTINUED ON THE NEXT
 PENTIMATION BUILDING REVIEW SESSION!!!!

Review Stop E ELECTRICAL
Rev No 22 Status P Date 2007-11-07 Cont ID  
Sent By jleahy Date 2007-11-07 Time 07:19 Rev Time 0.45
Received By jleahy Date 2007-11-07 Time 07:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 21 Status F Date 2007-10-04 Cont ID  
Sent By jleahy Date 2007-10-04 Time 18:51 Rev Time 6.00
Received By jleahy Date 2007-10-04 Time 18:42 Sent To  
Notes
2007-10-04 18:49:11PG.E.04HAND HOLE DETAIL CALLS FOR A 4" GROUND WIRE?
  
 PG. E.41UNIT V33 BEDROOM WALL THAT BACKS UP TO THE
 TUB MISSINGOUTLETS.
 WALL SPACE BEHIND MASTER BEDROOM
 MISSING OUTLET
  
 PG. E4.4UNIT J12 LIVING ROOM WALLS BY ELEVATOR SHOWS
 NO OUTLETS OR DOORS.IS THIS IN UNIT OR NOT?

Review Stop E ELECTRICAL
Rev No 20 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dpalmer Date 2007-09-22 Time 18:56 Sent To  
Notes
2007-09-23 11:22:002007-09-23 11:22:00
  
 IN REVIEW:
2007-09-22 19:24:252007-09-22 19:24:25
  
 IN ELEC FOR REVIEW:
 TO CONTINUE ON 9/23

Review Stop E ELECTRICAL
Rev No 19 Status F Date 2006-10-26 Cont ID  
Sent By dpalmer Date 2006-10-26 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2006-10-26 Time 18:15 Sent To  
Notes
2006-10-26 18:51:26*** UNSAT ***
  
 SEE NOTE DATED ON PREVIOUS REVIEW NUMBER 18, DATED ALSO
 10/26/06

Review Stop E ELECTRICAL
Rev No 18 Status F Date 2006-10-26 Cont ID  
Sent By dpalmer Date 2006-10-26 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2006-10-26 Time 18:15 Sent To  
Notes
2006-10-26 18:50:10***** UNSAT *********
  
  
 1) NOTE: PLEASE SEE REVISED PLANS ARE NOW BEING
 SUBMITTED AS OF SEPT 6, 2006 WHEN FINAL ELECTRICAL
 INSPECTION WAS PASSED AND PERMIT CLOSED ON 3/31/06.
 PLEASE KNOW AS THE ELECTRICAL PERMIT HAS ALREADY BEEN
 FINAL-ED OUT NO ELECTRICAL REVIEWS CAN BE DONE AT THIS
 TIME.
 PLEASE SEE I HAVE ATTACHED NUMEROUS PRINT OUTS FROM OUR
 SYSTEM WHICH INDICATES "LEXENT SERVICE" WHICH IS THE
 ELECTRICAL CONTRACTOR OBTAINING THAT FINAL INSPECTION.
 ALL SHEETS ARE SHOWN.
 PLEASE ALSO SEE PREVIOUS NOTES ARE ALSO ATTACHED FOR
 ELECTRICAL COMMENTS DATING BACK TO JAN 19, 2005 WERE
 NOT ADDRESSED.
 PLEASE KNOW AT THIS TIME IN ORDER FOR ELECTRICAL
 REVISIONS TO BE REVIEWED FOR CODE COMPLIANCE, A NEW
 ELECTRICAL PERMIT MUST BE APPLIED FOR TO "RENEW" THE
 CLOSED PERMIT IN ORDER FOR APPROPRIATE INSPECTIONS TO
 BE DONE ONCE ALL REVISIONS HAVE BEEN REVISED AND
 STAMPED FOR CODE COMPLIANCE.
 PLEASE KNOW ANY AND ALL AREAS WHICH WERE ON PREVIOUS
 REVIEW NOTES ON PLANS FROM PREVIOUS COMMENTS WILL BE
 REQUIRED TO BE INSPECTED AT THE JOB-SITE BY CITY
 INSPECTION/PLAN REVIEW STAFF.
  
 AT THIS TIME ELECTRICAL REVISIONS ARE NOT BEING
 REVIEWED AS PERMIT HAS BEEN CLOSED.
  
  
 *** PLEASE ALSO KNOW, "TRUE" "AS-BUILTS" ARE NOT NEEDED
 IF ALL REVISIONSTO DATE HAVE ALREADY INDEED BEEN
 SUBMITTED AS REVISIONS PREVIOUSLY.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 17 Status F Date 2005-12-19 Cont ID  
Sent By dpalmer Date 2005-12-19 Time 13:21 Rev Time 10.00
Received By dpalmer Date 2005-12-15 Time 10:23 Sent To  
Notes
2005-12-19 00:00:00******* UNSAT ********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO
 INFORMATION ADDED TO PLANS.
  
  
  
 1)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIREMENTS FOR MAIN ELECTRICAL ROOM.
 PLEASE ALSO SEE THAT A MIN 6' OPENING
 AND DOUBLE WORKING SPACE.
 THIS WAS NOTED AS BEING CORRECTED ,
 HOWEVER PLANS STILL SHOWN WITH OUT
 CHANGES MADE.
 110.26
  
 2)NOTE: PLEASE SEE V-33 RM W/O RECEPTS,
 PLEASE SEE OTHER LOCATIONS ON NUMEROUS
 UNITS MISSING RECEPTS REQUIRED PER
 210.52
 PLEASE SEE REDLINED PLANS.
  
 3)NOTE: PLEASE SEE V-33, PLEASE
 CORRELATE THE NUMBER OF COMPLETE A/C
 SYSTEMS ON SCHEDULE, LOAD CALCS AND
 PLANS.
 SHOWS TWO, ONE AND ONE.
 215.5
  
 4)NOTE: PLEASE COMPLETE ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE SEE
 REDLINED PLANS FOR UNITS INCOMPLETE AT
 THIS TIME. SOME FROM PREVIOUS REVIEW
 WERE DONE.
 215.5
 NEED TO VERIFY, PLEASE SEE NEXT COMMENT.
  
 5)NOTE: PLEASE SEE MANY DINING RM AREAS
 WHICH INDICATE 15A, #14 AWG FOR DINING
 RM CIRCUIT.
 PLEASE SEE 210.52B1, 210.11C
 MUST BE 20A AND #12.
 D36,28, G14, H10 ETC
  
 6)NOTE: PLEASE SEE UNIT J-12, UNIT WALLS
 NOT COMPLETE 210.52
 PLEASE ALSO SEE SD'S ON TWO CIRCUITS.
 PLEASE SEE NFPA-72 WHICH REQUIRES SD'S
 TO BE WIRED "INLINE".
  
 7)NOTE: PLEASE SEE MISSING DOORS ON
 UNITS C-21, J-12ETC.
  
 8)NOTE: PLEASE SEE MANY UNITS WHERE SD'S
 ARE MISSING THE CIRCUITING NUMBERS, NEED
 TO VERIFY.
 215.5, NFPA-72
  
 9)NOTE: PLEASE SEE REDLINED PLANS FOR
 MISSING GFI RECEPTS PER 210.52C1, SEEMS
 TO BE ONLY A COUPLE AT THIS TIME.
 S1(S),
  
 10)NOTE: PLEASE CORRELATE THE NUMBER OF
 SM APPL CIRCUITS ON PLANS, PANEL
 SCHEDULE AND LOAD CALCS. A-13
  
 11)NOTE: PLEASE SEE MANY UNITS WHERE
 MORE THEN ONE BATHROOM IS ON THE SAME
 CIRCUIT. THIS INLCUDES , RECEPTS AND
 LIGHTS ON SAME CIRCUIT, HOWEVER THIS
 CIRCUIT ALSO FEEDS OTHER BATHROOMS.
 PLEASE ALSO SEE BATH CIRCUIT ON WITH
 LIVING RM.
 PLEASE SEE A17, U-1, R1(S) S1(S) Q1,
 R1,(N) ETC ETC.
 MOST OF THESE ARE REDLINED.
 PLEASE SEE 210.52D, AND 210.11C3, WHICH
 PERMITS EITHER MORE THAN ONE BATH GFI ON
 THE SAME CIRCUIT, BUT MUST NOT HAVE ANY
 LIGHTING OR OTHER LOADS ON THAT 20A,#12
 GFI CIRCUIT, OR
 BATH GFI AND LTS MAY ON TOGETHER, BUT
 SHALL NOT FEED ANY OTHER RECEPTS,LTS OR
 OTHER LOADS OUTSIDE THAT PARTICULAR
 BATHRM.
  
 12)NOTE: PLEASESEE MIN CLEARENCE FOR
 CLOASET LT IN UNIT S1(N), 410.8
  
 13)NOTE: PLEASE INDICATE THE GROUNDING
 ELECTRODE SYSTEM FOR GENERATOR.
 250.30
  
 14)NOTE: PLEASE VERIFY BASEMENT SUMP
 PUMPS COMING FROM THE NON-EMERGENCY OF
 HOUSE POWER.
 THIS IS NOT AN ELECTRICAL NEC CODE
 COMMENT, ONLY TO VERIFY.
  
 ** PLEASE SEE MANY OF THE ABOVE ITEMS
 ARE REDLINED ON PLANS FOR AREAS OF
 COMMENTS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 16 Status F Date 2005-07-12 Cont ID  
Sent By dpalmer Date 2005-07-12 Time 13:53 Rev Time 7.00
Received By dpalmer Date 2005-07-12 Time 13:53 Sent To  
Notes
2005-07-12 00:00:00ELECTRICAL REVISIONS DATED 6/6/05
  
 *********** UNSAT *****************
  
 1)NOTE: PLEASE SEE MIN OPENINGS AND
 OPENING SIZES FOR ELECTRICAL ROOMS.
 PLEASE SEE MAIN ELECTRICAL ROOM HAD
 CHANGED AND NO REVISION IS SHOWN FOR
 110.26
 THIS WAS GONE OVER DURING A WALK THROUGH
 AT SAID PROJECT A FEW MONTHS BACK.
  
 2)NOTE: PLEASE LABEL AND INDICATE ALL
 MAINS ON ELECTRICAL ROOM PLANS AND ON
 RISER.
 PLEASE ALSO SEE METER-CENTER "A" IS
 SHOWN AS MAIN #1??
  
 3)NOTE: PLEASE SEE NUMEROUS RECEPTS
 REQUIRED PER 210.52 HAVE NOW BEEN
 REMOVED FROM PLANS.
 THESE WERE ON ORIGINAL PLANS.
 THIS WAS GONE OVER WITH ELECTRICAL
 CONTRACTOR, GEN CONTRACTOR, ENGINEERING
 STAFF AT JOBSITE WHICH THE DECISION THAT
 ALL RECEPTS ARE REQUIRED AND SHALL BE
 INSTALLED. MANY OF THESE HAVE NOW BEEN
 REMOVED FROM PLANS??
  
 4)NOTE: PLEASE SEE MISSING RECEPTS IN
 MANY UNITS REQUIRED PER 210.52C1-5
  
 5)NOTE: PLEASE SHOW ALL RECEPTS REQUIRED
 TO BE GFI/GFI PROTECTEDON PLANS.
 PLEASE SEE KITCHEN COUNTERSPACES, BATHS
 ETC. 210.8A6, 210.8A3
  
 6)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED FOR UNITS. PLEASE ALSO SEE
 OTHER NOTES;
  
 7)NOTE: PLEASE CORRELATE CIRCUITS; SOME
 SHOWN ON PLANS, HOWEVER PANEL SCHEDULE
 INDICATES THESE CIRCUITS AS A
 "SPACE"/"SPARE".
 PLEASE SEE MIN SMALL APPLIANCE CIRCUITS,
 SOME CIRCUITS SHOWN FOR FRIG IS ALSO
 SMALL APPL ETC.
  
 8)NOTE: PLEASE SEE OSME UNITS NO LONGER
 CONTAIN ROOM DESIGNATIONS?
 PLEASE SHOW.
  
 9)NOTE: PLEASE SEE MANY OF THE
 ELECTRICAL PANELS ARE SHOWN AS 120A??
 PLEASE SEE SOME ARE HAVE 125A FEEDS AND
 SOME HAVE 200A FEEDS. BOTH OF WHICH ARE
 ON 120A(?) PANELS.
  
 10)NOTE: PLEASE SOME UNITS INDICATE TWO
 A/C SYSTEMS , HOWEVER LOAD CALCUALTIONS
 DO NOT SEEM TO CORRELATE WITH NUMBER OF
 A/C UNITS AND LOADS.
 PLEASE SHOW KW RATINGS FOR EACH AHU ON
 ALL PANEL SCHEDULES.
 PLEASE ADJUST ALL.
  
 11)NOTE: PLEASE SEE COMPLETE SHIFT OF
 ELECTRICAL ONC/21.
  
 12)NOTE: PLEASE SEE RISER NOW SHOWS A
 NEW PANEL "B", HOWEVER NO INFORMATION ON
 PANEL OR PANEL SCHEDULE WAS SUBMITTED.
 PLEASE SEE 240.21,408.16 ETC?
  
 13)NOTE: PLEASE CORRELATE FEEDERS ON
 RISER WITH FEEDERS ON HEDP FOR SC.
  
 14)NOTE: PLEASE VERIFY DEDICATED
 CIRCUITS FOR EACH OF THE ELEVATOR
 MACHINE RMS 620.23,24
  
 15)NOTE: PLEASE VERIFY CIRCUITING OF
 EGRESS PATHS IN HALLWAYS AND STAIRWELLS.
 ALTERNATING CIRCUITS OR POSSIBLE BATTERY
 BACK UP FIXTURES.
 LS 101 7-9
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 15 Status F Date 2005-02-01 Cont ID  
Sent By dpalmer Date 2005-02-01 Time 10:36 Rev Time 0.30
Received By dpalmer Date 2005-02-01 Time 10:16 Sent To  
Notes
2005-02-01 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE SEE ANY REVISED
 PHOTOMETRICS MUST BE DONE BY THE
 ENGINEER OF RECORD.
 PLEASE SEE LIGHTING SUBMITTALS MAY COME
 BACK WITH REVISED PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 14 Status F Date 2005-01-19 Cont ID  
Sent By dpalmer Date 2005-01-19 Time 10:15 Rev Time 0.25
Received By dpalmer Date 2005-01-19 Time 10:15 Sent To M
Notes
2005-01-19 00:00:00*********** UNSAT *****************
  
  
 1)NOTE: PLEASE SEE ALL COPIES OF LTRS
 PLANS ETC, MUST CONTAIN ORIGINAL
 SAIGNATURE, DATE AND SEAL BY ENGINEER OF
 RECORD.
 PLEASE SEE THIS IS A THRESHOLD JOB AND
 REQUIRES A MIN OF 3 COPIES. ONLY TWO
 SUBMITTED.
  
 2)NOTE: PLEASE SEE THAT LTR REFERENCES
 DELETION OF AN UNREQUIRED SYSTEM FROM
 BLDG. THIS IS FINE , HOWEVER, PLANS NEED
 TO BE REVISED TO DELETE THIS FROM
 ELECTRICAL PLANS AND ANY OTHER PLANS
 WHICH MAY SHOW THIS SYSTEM. PLEASE
 REMOVE CIRCUITING/FANS FROM PLANS ALONG
 WITH REVISED PANEL SCHEDULE(S) AND LOAD
 CALCS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2004-12-14 Cont ID  
Sent By dpalmer Date 2004-12-14 Time 09:54 Rev Time 0.25
Received By dpalmer Date 2004-12-14 Time 09:54 Sent To  
Notes
2004-12-14 00:00:00LT FIX Q, E

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2004-12-07 Cont ID  
Sent By dpalmer Date 2004-12-07 Time 09:34 Rev Time 0.33
Received By dpalmer Date 2004-12-07 Time 09:33 Sent To  
Notes
2004-12-07 00:00:00SUBMITTIALS FOR STEAM/SAUNA UNITS.

Review Stop E ELECTRICAL
Rev No 11 Status N Date 2004-11-15 Cont ID  
Sent By kstevens Date 2004-11-27 Time 13:40 Rev Time 0.30
Received By dpalmer Date 2004-11-15 Time 06:54 Sent To  
Notes
2004-11-15 00:00:00ELECTRICAL SUBMITTALS FOR MISC BOXES,
 CONDUIT,WIRE, ETC NOT NEEDED.
 ALL EQUIPMENT INSTALLED SHOULD BE LISTED
 BY A NRTL.

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2004-10-22 Cont ID  
Sent By csiegber Date 2004-10-28 Time 16:42 Rev Time 1.50
Received By dpalmer Date 2004-10-22 Time 15:40 Sent To  
Notes
2004-10-22 00:00:00LT SPECS OK, PULLED TYPE "E" FROM
 SUBMITTALS.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-10-07 Time 13:00 Rev Time 0.75
Received By dpalmer Date 2004-07-22 Time 08:38 Sent To  
Notes
2004-07-22 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE THERE ARE NUMEROUS
 SPECS SHEETS FOR FIXTURE TYPE WHICH DO
 NOT CONTAIN ANY APPROVED TESTING LISTED.
  
 A,Q,W,SA,SD,AA,BB,LA,LB,LC,B,C,D,A,D
  
 PLEASE ALSO SEE SOME FIXTURE TYPES SEEM
 TO BE REPEATED ALSO?
  
 NEC 110.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status N Date 2004-07-22 Cont ID  
Sent By dpalmer Date 2004-07-22 Time 08:33 Rev Time 1.00
Received By dpalmer Date 2004-07-22 Time 08:32 Sent To  
Notes
2004-07-22 00:00:00******* N *********
  
 NO ELECTRICAL PLANS SUBMITTED FOR REVIEW

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-06-01 Cont ID  
Sent By csiegber Date 2004-07-02 Time 10:35 Rev Time 0.25
Received By dpalmer Date 2004-06-01 Time 14:59 Sent To  
Notes
2004-06-01 00:00:00SUBMITTAL, FLR BOX ONLY.
 DATE STAMPED, ONE COPY TO HP.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-06-01 Cont ID  
Sent By dpalmer Date 2004-06-01 Time 14:54 Rev Time 0.50
Received By dpalmer Date 2004-06-01 Time 14:54 Sent To  
Notes
2004-06-01 00:00:00SW GEAR SUBMITTIALAS ONLY.
 DATE STAMPED, ONE COPY TO HP.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-05-28 Time 16:27 Rev Time 1.00
Received By dpalmer Date 2004-04-20 Time 16:46 Sent To FIRE
Notes
2004-04-20 00:00:00NOTES REDLINED FOR TRANSFER SWITCH TO
 MEET 230.76/230.79/ 110.27
 MANUAL MEANS OF DISCONNECT REQ'D ON
 OUTSIDE RATED FOR THE LOAD SERVED.
  
 DEWEY PALMER

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-04-13 Time 16:25 Rev Time 0.25
Received By dpalmer Date 2004-02-12 Time 07:01 Sent To P
Notes
2004-02-12 00:00:00SUMP PUMP SUBMITTALS, NOT REQ'D FOR
 ELECTRICAL REVIEW. TO PLUMB

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-29 Cont ID  
Sent By csiegber Date 2004-02-11 Time 11:38 Rev Time 6.00
Received By dpalmer Date 2003-10-28 Time 14:48 Sent To  
Notes
2003-10-29 00:00:00********* NOTES REDLINED ***********
  
 1)NOTE: GFI RECEPTS TO BE W/IN 3' OF
 LAV/ SINKS IN BATHROOMS.
 E-4.11(L-19), E-4.16 (R1(N)
  
 2)NOTE: RECEPT SPACING PER 210.52
 E-4.5 (16,18,20), 4.5 (T1), 4.18 (M/01,
 M38
  
 3)NOTE: COLOR CODING REDLINED FOR CITY
 OF WEST PALM BEACH AMEDMENTS.
 PLANS MENTION PALM BEACH COUNTY.
  
 THE ABOVE HAS BEEN REDLINED ON EACH SET
 AND PLANS DO NOT NEED TO BE REVISED AT
 THIS TIME FOR THIS.
 ELECTRICAL PLANS HAVE BEEN PASSED, PEND-
 -ING COMMENTS FROM ANY OTHER REVIEWERS
 THAT MAY OR MAY NOT HAVE COMMENTS THAT
 MAY AFFECT ELECTRICAL PLANS.
 ELEECTRICAL SHEETS ONLY HAVE BEEN
 STAMPED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 PLANS SUBMITTED FOR TEMPORARY ELECTRICAL
 SERVICE MUST BE SUBMITTED UNDER SEPARATE
 PERMIT APPLICATION.
 PLEASE ALSO HAVE PLANS DONE AND AN
 ENGINEER PER FS 471.003
 PLANS MUST CONTAIN ALL INFORMATION AS
 SET FORTH UNDER FAC 61G15-23.002

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-04 Cont ID  
Sent By dpalmer Date 2003-09-04 Time 06:29 Rev Time 12.00
Received By dpalmer Date 2003-09-03 Time 19:44 Sent To  
Notes
2003-09-04 00:00:00*************** UNSAT **************
  
 PLEASE SEE THAT SOME NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SHOW POINT OF ATTACHED
 FOR TRANSFORMERS. IT IS NOTED ON X-FORM-
 -ER SCHEDULE FOR THE SIZE BUT NOT
 LOCATION. 250.30 (NOTE#6 FIRST REVIEW)
  
 2)NOTE: (NOTE# 1 FIRST REVIEW), RESPONSE
 LETTER MENTIONS THAT A NOTE WOULD BE
 ADDED TO RISER DIAGRAM. PLEASE CLARFIY/
 SHOW WHERE THIS NOTE IS FOR TEMPORARY
 CONDUITS FOR POWER??
  
 3)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 WHAT APPEARS TO BE ONE BUS-DUCT COMING
 FROM FPL FEEDINGMAINS 1 AND 2?
 PLEASE SEE RISER NOTES: MENTIONS BUS
 DUCT TO BE 3000A'S AND LOAD ON BOTH OF
 THESE MAINS EXCEED RATING OF 3000A DUCT?
 PLEASE CLARIFY IF THESE ARE TO BE
 SEPARATE? 215.5
  
 4)NOTE: PLEASE SEE E6.1, SHOWS TWO
 MC-"B"'S, APPEARS TO BE A MISPRINT?
  
 5)NOTE: PLEASE SEE RISER DIAGRAM NOTES,
 MENTIONS 1 1/2" CONDUIT FOR 3-3/0'S AND
 1-#6. PLEASE SEE CONDUIT FILL TABLES IN
 NEC. CHPT 9
  
 6)NOTE: PLEASE CORRELATE ALL PAGES,
 MAINLY E2.7 AND 3.1, FOR FUEL ALARMS,
 ONE MENTION 80% AND 90% AND OTHERS
 MENTION 85 AND 95%.
  
 7)NOTE: PLEASE SEE NOTE FROM FIRST
 REVIEW FOR GFI PROTECTION REQ'D FOR
 HDP. RESPONSE LETTER MENTIONS THAT
 INDICVATION WOULD BE MADE LARGER?
 PLEASE CLARIFY WHERE THIS IS. PANEL
 SCHEDULE DOES NOT MENTION AND RISER
 IS NOT CLEAR. PLEASE INDICATE AT BOTH
 LOCATIONS,RISER AND PANEL.
 230.95/215.10 ETC.
  
 8)NOTE: PLEASE SEE DISCONNECT SHOWN ON
 RISER DIAGRAM FOR X-FORMER TP, THERE IS
 NO INFORMATION GIVEN FOR SIZE,OCP ETC,
 PANEL SCHEDULE FOR HDP MENTIONS TO
 FEED X-FORMER TP W/ 200A OCP, YET
 X-FORMER SCHEDULE MENTIONS 100A OCP?
 PLEASE CLARIFY AND PROVIDE MORE INFOR.
 215.5
  
 9)NOTE: PLANS INDICATE ON 1.2 TO SEE
 3.1 FOR ENLARGED ELECTRICAL RM LAYOUT
 FOR REQ'D ELECTRICAL. PLEASE CLARIFY
 WHERE LIGHTING/POWER IS SHOWN? MINLTS
 ALSO PER 700.16, PLEASE ALSO SEE FIRE
 REVIEW NOTES FOR POSSIBLE REQ'D SD IN
 ELECTRICAL RM.
  
 11)NOTE: PLEASE SEE 110.26C FOR ENTRANCE
 INTO AND OUT OF ELECTRICAL RM.
 PLEASE SEE THE EXCEPT.'S
 PER SCALE, IT DOES NOT SEEM TO MEET
 TWICE THE DISTANCE ACCROSS FOR CLEARENCE
 ? PLEASE CLARIFY AND/OR ADJUST.
  
 12)NOTE: PLEASE SEE 210.52 FOR RECEPTS
 SPACING. THERE ARE MANY UNITS MISSING
 RECEPTS FOR 2' OF WALL ETC.
 ON SET OF PLANS HAVE SOME OF THESE AREAS
 REDLINED. F.R>
  
 13)NOTE: PLEASE ALSO SEE 210.52C-1 FOR
 RECEPTS REQ'D FOR COUNTERSPACE, THERE
 ARE ONLY A COUPLE MISSING, SEE UNIT D36.
 F.R.
 14)NOTE: PLEASE SEE NOTE#22 FROM FIRST
 REVIEW. RESPONSE LETTER MENTIONS, UNIT
 IS 800 SQ FT AND WILL COMPLY? PLEASE SEE
 D36, PANEL SCHEDULE SHOWS UNIT AT 1059SQ
 FT?? PLEASE SEE OTHER UNITS THAT ARE
 LARGER AND NO CHANGE WAS MADE>
 PLEASE ALSO SEE SQFT FOR ALL OTHER UNITS
 SOME DO NOT SEEM TO CORRELATE W/SCALE?
  
 15)NOTE: PLEASE SEE NOTE 26 FROM FIRST
 REVIEW, RESPONSE MENTIONS, WILL COMPLY.
 PLANS DO NOT SEEM TO HAVE AHD SD'S
 MOVED OR NOTE ADDED FOR INSTALLATION OF
 SD'S? NFPA-72
  
 16)NOTE: PLEASE SEE NOTE#36 FR> RESPONSE
 MENTIONS; WILL COMPLY, HOWEVER PANELS
 STILL DO NOT INDICATE SPECS ON PANELS,
 SIZE? THEY ARE NOTED WITH SIZE OF FEEDER
 -S. 215.5
  
 17)NOTE: PLEASE SEE NOTE#27 , PLEASE
 SEE SOME UNITS MOVED RECEPTS TO COMPLY,
 HOWEVER PLEASE SEE SOME UNIT(S), THERE
 ARE MANY UNITS STILL NEED TO MEET
 210.52D, TO BE W/IN 3' OF LAV/SINKS.
  
 18)NOTE: PLEASE SEE NOTE#39 ,PLEASE
 CLARIFY WHERE NOTE IS FOR COLOR CODING
 OF CONDUCTOR PER LOCAL AMENDMENTS?
 215. 277/480V BROWN/PURPLE/YELLOW
  
 PLEASE SEE FIRE REVIEW COMMENTS AND
 COMMENTS FROM OTHER REVIEWERS THAT MAY
 HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2003-09-03 00:00:00NOTES TO FOLLOW,

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-15 Cont ID  
Sent By dpalmer Date 2003-04-14 Time 16.58 Rev Time 10.00
Received By dpalmer Date 2003-04-14 Time 15:27 Sent To  
Notes
2003-04-15 00:00:00PLEASE SEE COMMENTS STARTED 4/14 AND
 COMPLETED 4/15/03
2003-04-14 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE PROVIDE NOTE ON ELECTRIC-
 -AL RISER DIAGRAM: ELECTRICAL CONTRACTOR
 TO PROVIDE SPARE CONDUITS TO ANY
 PANELS AND/OR EQUIPMENT THAT MAY NEED TO
 BE FED FROM TEMPORARY POWER BEFORE
 MAIN SERVICE IS RELEASED ON BLDG.
 PLEASE ALSO NOTE: TEMPORARY SERVICE MUST
 BE OF ADEQUATE SIZE.
  
 2)NOTE: PLEASE SEE DOUBLE PRINT ON TITLE
 BLOCK FOR ENGINEER OF RECORD. PLEASE
 REPRINT FOR CLARITY. FAC 61G15-23.002
  
 3)NOTE: PLEASE SUBMIT AND SHOW AIC
 RATINGS FOR ALL NEW EQUIPMENT BEING
 INSTALLED. MAINS/PANELS/BREAKERS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT. PER 110-9 IT IS NOTED, ELECTRI-
 -CAL CONTRACTOR TO PROVIDE SIGNED AND
 SEALED SHOP DRAWINGS FOR THIS.
 PLEASE NOTE, THIS MUST BE SUBMITTED WITH
 PLANS FROM THE ENGINEER OF RECORD.
  
 4)NOTE: PLEASE SEE E3.1. GENERATOE SHOWN
 AS 600W? PLEASE CORRELATE W/ RISER
 DIAGRAM.
  
 5)NOTE: PLEASE SHOW(MAP) LOCATION AROUND
 FUEL FILL AREA REMOTE FROM GENERATOR
 PER NEC 500.
  
 6)NOTE: PLEASE SHOW/LIST GROUNDING FOR
 ALL TRANSFORMERS PER 250-30
  
 7)NOTE: PLEASE SEE E3.1, SHOWS 2-4"
 CONDUITS FOR 400A SE RATED SWITCH,
 PLEASE SEE RISER, SHOWS ONLY ONE CONDUIT
 FROM FPL.? PLEASE CORRELATE.
  
 8)NOTE: PLEASESUBMIT/SHOW MORE ON
 SERVICE FOR FUTURE TENANT SPACES.
 SERVICE, MAINS ETC?
 PLEASE CLARFIY IF 400A SE RATED MAIN IS
 FOR FUTURE TENANTS?
  
 9)NOTE: PLEASE SEE CODE REFERENCED FOR
 GROUNDING ELECTRODE IS FROM THE 96 NEC.
 (250-81) PLEASE NOTE:250-66 99NEC
  
 10)NOTE: PLEASE NOTE, AS PER PLANS,
 MAINS IN BLDG ARE NOT GROUPED. PLANS
 ARE SHOWING 13 MAINS IN BLDG WHICH DOES
 NOT INCLUDE FIRE PUMP.230-2/230-70,
 230-72, 225-38 ETC.
 MAINS ARE TO BE LOCATED AT THE NEAREST
 POINT OF ENTRANCE TO A BLDG.E
 PLEASE ALSO NOTE, FIRE AND LIFE SAFTEY
 ISSUES COME INTO PLAY W/ THE MAJOR
 TRAVEL DISTANCES AND NUMEROUS LOCATIONS
 TO TURN POWER OFF IN BLDG.
 PLEASE ALSO NOTE, SERVICES CROSSING
 EACH OTHER, AND/OR HOUSE (277/480V)
 POWER.
  
 11)NOTE: PLEASE CLARIFY HDP, RISER SHOWS
 PLEASE SEE 240-3B FOR SIZING OF SEC`S
 FROM FPL. SHOWS ONLY, 4-500MCM`S IN
 4-SETS.310-16/110-14
  
 12)NOTE: PLEASE INDICATE AND SHOW REQ`D
 GFI PROTECTION FOR HDP. 230-95/215-10 ET
  
 13)NOTE: PLEASE CLARIFY/INDICATE METER
 TYPES FOR HOUSE AND FIRE PUMP? OF THE
 CT TYPE?
  
 14)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROETECTED CIRCUITS ON EACH PANEL SCHED-
 -ULE PER 210-12
  
 15)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED PER 210-8A-6THIS WOULD INCLUDE ANY
 ISLAND RECEPTS.
  
 16)NOTE: PLEASE SEE PLANS AND UNITS,
 MISSING RECEPTS PER 210-52. 2',6',12'
 RULE.
  
 17)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRLEATE W/ SUBMITTED PANEL
 SCHEDULES.
  
 18)NOTE: PLEASE SEE V/33, APPEARS TO
 HAVE 2-WATER HEATERS AND 2-A/C UNITS?
 PLEASE CLARIFY.
  
 19)NOTE: PLEASE SEE MISSING COUNTERSPACE
 RECEPTS PER 210-52-1
  
 20)NOTE: PLEASE CLARIFY GFI PROTECTION
 FOR WHIRLPOOL TUBS 680-70
  
 21)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-52D/210-11C-3
 MUST BE 20A/ #12AWG.
  
 22)NOTE: PLEASE CLARIFY SQ FT SHOWN FOR
 UNIT D36, "L"UNITS? "L" UNITS ARE SHOWN
 MUCH LARGER ON SMAE SCLE THAN D36 , YET
 SQFT ON LOAD CALCS AND PANEL SCHEDULE
 DO NOT SEEM TO REFLECT THIS.
 PLEASE VERIFY OTHE UNITS ALSO.
  
 23)NOTE: PLEASE VERIFY SQ FT ON OTHER
 UNITS ALSO. SOME OTHERS DO NOT SEEM TO
 SCALE OUT.
  
 24)NOTE: PLEASE SEE OTHER UNITS FOR
 MISSING RECEPTS PER 210-52/210-52C-1
  
 25)NOTE: PLEASE SEE MISSING RECEPT W/IN
 3' OF LAV IN "L" UNITS. 210-52D
  
 26)NOTE: PLEASE NOTE: ALL SD`S TO BE A
 MIN OF 3' FROM BATHS AND KITCHENS.
 NFPA-72 8-1.4.2
  
 27)NOTE: PLEASE SEE MISSING RECEPT W/IN
 3' OF LAV`S IN OTHER UNITS ALSO 210-52D
  
 28)NOTE: PLEASE CLARIFY EGRESS LIGHTING
 CONTROL IN MULTI-LEVEL UNIT A/13.
 FOR STAIRWAY ,210-70
 PLEASE ALSO SEE A17
  
 29)NOTE:PLEASE CLARIFY MEANS OF EGRESS
 LIGHTING/CONTROL OR AUTOMATIC MEANS
 FOR GRADE LEVEL UNITS W/ ACCESS TO
 STREET.
  
 30)NOTE: PLEASE SHOW LIGHTING AND RECEPT
 -S SHOWN 2.9/2.10 ETC ON UNITS,, G-14,
 K-16,K18,K-20, L-22 ETC.OR NOTE
 LOCATION FO LIGHTING AND RECEPT.
  
 31)NOTE: PLEASE SEEMISSING RECEPTS
 FOR 12" OF COUNTERSPACE,210-52C1
  
 32)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN
 IN MIDDLE OF MASTER BEDROOM FLOOR IN
 UNIT C/17, E 4.8
  
 33)NOTE: AS PER 210-52, RAIL AREA IN
 BEDROOMS ON MULTI-LEVEL UNITS ARE
 CONSIDERED WALL SPACE. RECEPT RE`D.
  
 34)NOTE: PLEASE CLARFIY MEANS OF EGREES
 CONTROL COMING INTO S1(N) FROM HALL INTO
 LIVING ROOM.210-70
  
 35)NOTE: PLEASE CLARIFY METER CENTER "A"
 SHOWS 150A MAINS AND ONLY 7 V/33 UNITS?
  
 36)NOTE: PLEASE SHOW SPECS ON PANEL
 SCHEDULES. FEEDERS ARE NOTED AS 125A AND
 150ABUT PANELS DO NOT INDICATE SIZE
 ETC.
  
 37)NOTE: PLEASE NOTE, POOL WILL BE REQ`D
 TO BE UNDER SEPARATE PERMIT FOR STRUC/
 ELEC/PLUMB. PLEASE ALSO NOTE, A SEPARATE
 ELECTRCIAL WIRING DIAGRAM FOR PUMPS/
 HEATERS AND EQUIPMENT WILL BE REQ`D TO
 BE SUBMITTED W/ POOL PERMIT.
  
 38)NOTE:PLEASE NOTE, LIGHTNING PROTECT-
 -ION WILL BE REQ` TO BE UNDER SEPARATE
 PERMIT.
  
 39)NOTE: PLEASE NOTE; COLOR CODING OF
 FEEDERS TO BE PER LOCAL AMENDMENTS. 215
 277/480V
 BROWN/ PURPLE /YELLOW
 120/208V
 BLACK/RED/BLUE
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE DO NOT HESITATE TO CALL
 AND EITHER SET UP A MEETING TO GO OVER
 PLANS/COMMENTS ON PHONE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 561-805-6717
 [email protected]
  
 PLEASE SEE FIRE REVIEW COMMENTS THAT
 WILL HAVE AN AFFECT ON ELECTRICAL PLANS
 DUE TO THE REQUEST OF MORE EXIT/EM LTS.

Review Stop ENG ENGINEERING CSD
Rev No 8 Status N Date 2005-08-02 Cont ID  
Sent By mwennerg Date 2005-08-02 Time 10:53 Rev Time 0.00
Received By mwennerg Date 2005-08-02 Time 10:53 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 7 Status P Date 2005-01-20 Cont ID  
Sent By mamini Date 2005-01-20 Time 15:33 Rev Time 0.50
Received By mamini Date 2005-01-20 Time 15:33 Sent To  
Notes
2005-01-20 00:00:00PASSED:
  
 1. REVIEWED FOR REVISION.

Review Stop ENG ENGINEERING CSD
Rev No 6 Status P Date 2004-11-19 Cont ID  
Sent By mamini Date 2004-11-19 Time 09:12 Rev Time 0.00
Received By mamini Date 2004-11-19 Time 09:12 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2004-07-28 Cont ID  
Sent By mamini Date 2004-07-28 Time 14:55 Rev Time 0.50
Received By mamini Date 2004-07-28 Time 14:55 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2003-11-17 Cont ID  
Sent By mamini Date 2003-11-17 Time 16:00 Rev Time 1.00
Received By mamini Date 2003-11-17 Time 15:59 Sent To  
Notes
2003-11-17 00:00:00PASSED:
 1. UNDERGROUND UTILITIES AND SITE WORK
 /CIVIL PLANS AND PERMIT ARE INCLUDED IN
 BUILDING PERMIT.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2003-10-24 Cont ID  
Sent By mamini Date 2003-10-24 Time 13:30 Rev Time 1.00
Received By mamini Date 2003-10-24 Time 13:16 Sent To  
Notes
2003-10-24 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR "UNDERGROUND
 UTILITIES AND SITE WORK" PERMIT IS
 REQUIRED.PLEASE SUBMIT THREE SETS OF
 FINAL CIVIL ENGINEERING PLANS WITH ALL
 THE COMMENTS FROM ENGINEERING AND
 CONSTRUCTION SERVICES ARE ADDRESSED AND
 IMPLILEMENTED, ALSO INCLUDE STORM WATER
 SYSTEM FOR THE PROPOSED SITE.
 2. SUBMIT STORM WATER CALCULATION WHICH
 INCLUDES CALCULATIONS FOR PERVIOUS &
 IMPERVIOUS FOR THE TOTAL SITE AREA.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-08-15 Cont ID  
Sent By mamini Date 2003-08-15 Time 10:35 Rev Time 1.00
Received By mamini Date 2003-08-15 Time 10:35 Sent To  
Notes
2003-08-15 00:00:00FAILED:
 1. SHEET C-1.1 SHOWS STAIRS LEADING TO
 GROUND FLOOR ON DATURA ARE EXTENDED INTO
 THE SIDEWALKS, THIS WILL CREATE A PUBLIC
 SAFETY ISSUE.
 2. SHEET C-1.1 CALLS FOR MILLING OF 7"
 IN DATURA AND CLIMATIS, PLEASE VERIFY
 THE ADEQUACY OF THE EXISTING BASE.
 DETAILS FOR RECONSTRUCTION SHOULD BE
 SHOWN.
 3. PLEASE CALL OUT THE ACCESS RAMP TO
 ROSEMARY STREET.
 4. SHEET C-2.1 SHOWS TWO DETAILS FOR THE
 CONTROL STRUCTURES #5, ONE SHOULD BE FOR
 #6, PLEASE VERIFY. ALSO CHECK THE
 "STRUCTURE TABLE" FOR INVERT AND RIM
 ELEVATIONS.
 5. PLEASE ADD NOTE TO G.C. TO CONTACT
 PARKING ADMINISTRATION, SUE OLEY @
 659-8022 EXT. 8122 TO COORDINATE THE
 RELOCATION OF THE PARKING METERS ON
 DATURA AND CLIMATIS.
 6. BEGIN MILLING AND RESURFACING ON
 DATURA TO INCLUDE NEWLY INSTALLED
 MANHOLED #2.
 7. PLEASE CLARIFY THE CONNECTION FOR 2"
 PVC IRRIGATION SERVICE LINE, SHEET C-3.1
 AND C-3.2 .
 8. PLEASE ADD NOTE TO G.C. THAT IT SHALL
 BE THE RESPONSIBILITY OF THE CONTRACTOR
 TO RESTORE THE EXISTING SIDEWAKS, CURB
 & GUTTERS, TREES LIGHT POLES, PARKING
 METTERS, IRRIGATION SYS, ETC. ADJACENT
 TO PROPERTY ALL SIDES TO THE ORIGINAL OR
 BETTER IF DAMAGE DURING THE CONSTRUCTION
 9. PLEASE SUBMIT STORM WATER CALCULATION
 FOR OUR REVIEW, THIS SUBMITTAL SHOULD
 INCLUDE PERVIOUS AND IMPERVIOUS AREA
 CALCULATIONS FOR THE ENTIRE SITE, AND
 ALSO A COPY OF SFWMD PERMIT.(SIGNED &
 SEALED)
 10. PLEASE NOTE THAT CIVIL PLANS SHOULD
 INCLUDE POLLUTION/ EROSION PREVENTION
 PLAN AND NOTE TO G.C. TO INSTALL IN
 FIELD PRIOR TO ANY CONSTRUCTION.
 11. FDC ( FIRE DEPARTMENT CONNECTION)
 MUST BE SHOWN ON CIVIL PLANS, 150' MAX.
 FROM A EXISTING FIRE HYDRANT.
 12. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK WILL BE REQUIRED
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-03-28 Cont ID  
Sent By mamini Date 2003-03-28 Time 10:59 Rev Time 2.00
Received By mamini Date 2003-03-28 Time 10:59 Sent To  
Notes
2003-03-28 00:00:00FAILED :
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND CIVIL/ SITE WORK AT THE
 TIME OF ACTUAL PERMITING WILL BE
 REQUIRED.
 2. PLEASE SUBMIT STORM WATER CALCULATION
 FOR OUR REVIEW, THIS SUBMITALL SHOULD
 ALSO INCLUDE PERVIOUS AND IMPERVIOUS
 AREA CALC. FOR THE ENTIRE SITE AND COPY
 OF SFWMD PERMIT. ALL CALCULATIONS
 SUBMITALLS MUST BE SIGNED AND SEALED.
 3. PLEASE NOTE THAT CIVIL PLANS SHOULD
 ALSO INCLUDE POLLUTION PREVENTION PLANS,
 NOTE TO GC TO INSTALL IN FIELD PRIOR TO
 ANY EARTH/ EXCAVATION WORK.
 4. PLEASE NOTE THAT ALL CONNECTION TO
 CITY SERVICES AND LOCATION FOR BACKFLOWS
 AND METERS MUST BE APPROVED BY PUBLIC
 UTILITIES.
 5. FDC (FIRE CONNECTIONS) FOR FIRE
 PROTECTION MAY BE REQUIRED, PLEASE
 CONTACT CAP. MIKE CARSILLO AT 659-8096
 EXT. 8497.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 18 Status N Date 2007-11-01 Cont ID  
Sent By mwennerg Date 2007-11-01 Time 13:39 Rev Time 0.00
Received By mwennerg Date 2007-11-01 Time 13:39 Sent To  
Notes
2007-11-01 13:41:04NO FIRE PROTECTION SHEETS SUBMITTED FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 17 Status P Date 2006-12-29 Cont ID  
Sent By mwennerg Date 2006-12-29 Time 11:35 Rev Time 0.00
Received By mwennerg Date 2006-12-29 Time 11:35 Sent To  
Notes
2006-12-29 11:40:20***PROVISO***
  
 1) NEW RAILLING INSTALLATIONS SHALL MEET THE
 PRESCRIPTIVE STRENGTH REQUIREMENTS.
  
 2) FIRE ALARM RISER SHOWN ON E-5.3 ILLUSTRATES A NEW
 DATE STAMP, HOWEVER A FIRE REVIEW WAS CONDUCTED AFTER
 THE REVISION DATE OF 9/30/05. PLEASE REFER TO LAST FIRE
 REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 16 Status P Date 2005-12-27 Cont ID  
Sent By mwennerg Date 2005-12-27 Time 10:22 Rev Time 0.00
Received By mwennerg Date 2005-12-27 Time 10:22 Sent To  
Notes
2005-12-27 00:00:00REVISION DATED 10/20/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status P Date 2005-10-20 Cont ID  
Sent By nmccray Date 2005-10-20 Time 15:09 Rev Time 0.00
Received By nmccray Date 2005-10-20 Time 15:09 Sent To  
Notes
2005-10-20 00:00:00DOORS HARDWARE FOR UNIT ENTRANCE

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status N Date 2005-08-02 Cont ID  
Sent By mwennerg Date 2005-08-02 Time 10:54 Rev Time 0.00
Received By mwennerg Date 2005-08-02 Time 10:54 Sent To  
Notes
2005-08-02 00:00:00NO FIRE PROTECTION OR LIFE SAFETY SHEETS
 SUBMITTED FOR REVIEW OF REVISIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status P Date 2005-05-05 Cont ID  
Sent By mwennerg Date 2005-05-05 Time 14:23 Rev Time 0.00
Received By mwennerg Date 2005-05-05 Time 14:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2005-03-24 Cont ID  
Sent By mwennerg Date 2005-03-24 Time 10:28 Rev Time 0.00
Received By mwennerg Date 2005-03-24 Time 10:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2005-03-01 Cont ID  
Sent By nmccray Date 2005-03-01 Time 10:28 Rev Time 0.00
Received By nmccray Date 2005-02-28 Time 10:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status F Date 2005-02-08 Cont ID  
Sent By mcarsill Date 2005-02-08 Time 16:41 Rev Time 0.00
Received By mcarsill Date 2005-02-08 Time 16:41 Sent To  
Notes
2005-02-08 00:00:001. FDC SHOWN ON C-32 SHOULD FACE
 DATURA STREET. THE POSITION SHOWN
 ON C-32 WATER SERVICE DETAIL WILL
 CAUSE THE HOSE TO KINK WHEN
 CONNECTED TO IT.
  
 2. ALL EXIT STAIRS SHALL SWING IN THE
 DIRECTION OF EXIT TRAVEL.
  
 3. ALL EXITS SHALL COMPLY WITH
 THE LIFE SAFETY CODE, APPROPRIATE
 EDITION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status F Date 2004-11-24 Cont ID  
Sent By nmccray Date 2004-11-24 Time 13:18 Rev Time 0.00
Received By nmccray Date 2004-11-24 Time 13:18 Sent To  
Notes
2004-11-24 00:00:00DENIED**********************************
 ENIED**********************************
 REVISION DATED 06-08-04
  
 SHEET FP-2.7 SHOWS THAT THE ELECTRIC
 VAUTH ROOM NOT FIRE SPRINKLER
 PROTECTED. ONLY FPL VAUTH ROOMS ARE
 PERMITTED TO BE UNPROTECTED BY FIRE
 SPRINKLER SYSTEM.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2004-10-28 Cont ID  
Sent By nmccray Date 2004-10-28 Time 10:32 Rev Time 0.00
Received By nmccray Date 2004-10-28 Time 10:32 Sent To  
Notes
2004-10-28 00:00:00FS SUBMITTAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2004-06-01 Cont ID  
Sent By csiegber Date 2004-07-19 Time 14:52 Rev Time 0.00
Received By nmccray Date 2004-06-01 Time 11:21 Sent To  
Notes
2004-06-01 00:00:00 
 SUBMITTAL FIRE SPRINKLER VALAE CABINET
 STANDPIPE DATED 05-28-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-28 Time 16:26 Rev Time 0.00
Received By nmccray Date 2004-05-06 Time 09:39 Sent To  
Notes
2004-05-06 00:00:00SUBMITTALS FOR FIRE ALARM SYSTEM AND
 FIRE PROTECTION SYSTEM. SEPARATE PLANS
 AND PERMIT APPLICATIONS ARE REQUIRED FOR
 FIRE ALARM AND FIRE PROTECTION SYSTEMS.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2004-05-05 Cont ID  
Sent By nmccray Date 2004-05-05 Time 15:40 Rev Time 0.00
Received By nmccray Date 2004-05-05 Time 15:40 Sent To  
Notes
2004-05-05 00:00:00SUBMITTALS FOR GENERATOR. SEPARATE PLANS
 AND PERMIT APPLICATION ARE REQUIRED FOR
 GENERATOR.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-11-14 Cont ID  
Sent By alange Date 2004-04-22 Time 12:15 Rev Time 0.00
Received By mcarsill Date 2003-11-14 Time 15:26 Sent To  
Notes
2003-11-14 00:00:001) FP2.2 TAKES PRECEDENCE WITH REGARDS
 TO THE INSTALLATION OF THE FDC. THE
 INFORMATION ON PAGE C-32 IS NOT CORRECT.
  
 2) ELECTRONIC SWITCHES WILL BE
 REQUIRED ON THE OS&Y BACKFLOW DEVICE.
  
 3) STORAGE ROOM DOORS OPPOSE ONE
 ANOTHER ON PAGE A-2.03.
  
 4) EXIT SIGNS AND EMERGENCY LIGHTNING
 REQUIRED FOR RECREATIONAL DECK.
  
 5) EXPANDED POLYSTYRENE NOTED ON
 A-2.11.
  
 6) A LETTER IS TO BE WRITTEN BY THE
 ARCHITECT CONCERNING DETAILS THAT
 WERE DISCUSSED IN A MEETING AT CITY
 HALL 11-14-03.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-11-06 Cont ID  
Sent By mcarsill Date 2003-11-06 Time 14:51 Rev Time 0.00
Received By mcarsill Date 2003-11-06 Time 14:51 Sent To  
Notes
2003-11-06 00:00:001) ELECTRONIC SWITCHES WILL BE
 REQUIRED ON THE FIRE-LINE BACKFLOW
 DEVICE.
  
 2) PLEASE EXPLAIN VARIABLE TREADS ON
 GROUND FLOOR PLAZA STEPS HARDSCAPE.
  
 3) PROPANE GRILL DETAIL STILL
 SHOWN ON L-7.2.
  
 4) EXPANDED POLYSTYRENE MOLDING STILL
 SHOWN A-102, TYPICAL BALCONY DETAILS.
  
 5) DOUBLE DOORS ON GROUND FLOOR
 LS PLAN-104 STILL SHOWS THE DOUBLE
 DOORS OPENING INWARD. PLEASE VERIFY
 DOUBLE DOORS SWING AND CORRECT
 ANY DEFICIENCIES.
  
 6) TRASH CHUTE DOORS ON PAGE A-2.07
 AND OTHER SHEETS NEAR 303 APPEARS
 TO SWING INTO CORRIDOR TOO FAR.
  
 7) INFORMATION CONCERNING ROOF PLAN
 PAGE A-2.11 IS DIFFICULT TO READ.
  
 8) PLEASE EXPLAIN WHY SHAFT ACCESS
 OPENING IS LOCATED NEXT TO EXIT DOOR.
 PLEASE EXPLAIN RATIONALE.
  
 9) STORAGE OPENINGS S26,S27,S41 DOORS
 OPPOSE ONE ANOTHER. S36,S37 ALSO
 OPPOSE ANOTHER.
  
 10) DOORS STILL SWING OVER THE STAIRS
 ON PAGE A-4.02.
  
 11) FABRIC AWNINGS ARE TO BE FIRE
 RETARDANT.
  
 12) PORTIONS OF THE BUILDING ARE OVER
 THE PROPERTY LINE ON PAGE A-5.02.
  
 13) EXPANDED POLYSTYRENE STILL SHOWN
 ON WALL SECTION DETAILS.
  
 14) WHAT IS THE VOID BELOW THE
 ELEVATOR MACHINE ROOM GOING TO BE
 USED.
  
 15) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENT FOR HANDRAILS
 AND GUARDRAILS.
  
 16) FIRE EXTINGUISHER CABINET DISPLAYS
 BREAK GLASS BUT NO BREAK GLASS RODS
 SHOWN.
  
 17) SOME TRASH CHUTE DOORS STILL
 APPEAR TO BE TOO LARGE FOR THE
 CORRIDORS.
  
 18) PLEASE EXPLAIN WHY SHAFT OPENING
 IS LOCATED DIRECTLY NEXT TO EXIT DOOR
 ON M-1.1.
  
 19) PROVIDE SEPARATE PLANS AND PERMITS
 FOR GENERATOR AND ASSOCIATED FUEL
 TANK.
  
 20) EXIT SIGNS APPEAR TO BE MISSING
 ON PAGE E-2.4 DIRECTING PERSONS TO
 STAIRWELL.
  
 21) FIRE COMMAND NOTES ON E-2.5 DOES
 NOT APPEAR TO CONTAIN ALL EQUIPMENT.
 PLEASE REVIEW FBC SECTION 412.4.
  
 22) AN EXIT SIGN APPEARS MISSING FROM
 GARAGE AREA NEAR DOUBLE DOORS.
  
 23) EXIT SIGNS APPEAR TO BE MISSING
 FROM E-2.6 FROM GARAGE AREA. ALSO
 NO DIRECTIONAL SIGNS ARE PRESENT TO
 DIRECT PERSONS FROM RETAIL # 5.
  
 24) MORE EXIT SIGNS APPEAR TO BE
 NEEDED ON E-2.7.
  
 25) PLEASE EXPLAIN EXIT SIGN FROM
 RESTROOMS TO GARAGE AREA.
  
 26) ONLY ONE STANDPIPE VALVE SHOWN ON
 FP-11.
  
 27) FDC FACES THE WRONG DIRECTION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-08-29 Cont ID  
Sent By mcarsill Date 2003-08-29 Time 15:15 Rev Time 0.00
Received By mcarsill Date 2003-08-29 Time 15:15 Sent To  
Notes
2003-08-29 00:00:001) SHAFTWAY SIGNS SHALL BE AT LEAST
 6" HIGH.
  
 2) KNOX-BOXES WILL BE REQUIRED.
  
 3) HOW DOES THE CARD SWIPE DEVICE USED
 FOR ACCESS NEAR SAUNA 165 EFFECT
 EXITING.
  
 4) PLEASE REVIEW ID-12 WHERE THE TRASH
 CHUTE OPENS INTO THE CORRIDOR NEAR
 THE TOP OF THE PAGE. IT APPEARS THE DOOR
 OPENS INTO THE CORRIDOR MORE THAN
 50 PERCENT.
  
 5) EXPANDED STYRENE OBSERVED ON A-10.10.
 PLEASE SEE APPENDIX F, OF THE LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 6) LOFT STAIRS ON PAGE A-10.07 ARE
 NOT WIDE ENOUGH. IF OCCUPANT LOADS
 OF LESS THAN 50 ARE EXPECTED THEN
 STAIR CAN BE 36" WIDE.
  
 7) FE CABINET ON A-10.07 INDICATES
 BREAK GLASS. HOW IS BREAK GLASS DONE.
 NO BREAK GLASS ROD SHOWN.
  
 8) PLEASE CONFIRM THAT THE EXIT SIGNS
 SHOWN ON A-10.03 COMPLIES WITH
 CHAPTER 7, OF THE LIFE SAFETY CODE.
  
 9) EXTERIOR GRADE PLYWOOD SHOWN ON
 SOME ROOF DETAILS. PLEASE SEE APPENDIX
 F, OF THE LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE.
  
 10) TRASH CHUTE SECTION MAKES NO
 REFERENCE ABOUT FIRE RATED DOORS,
 FIRE SPRINKLERS, OR BOTTOM DOOR.
  
 11) PLEASE DESCRIBE VOID AREA ON
 PAGE A-6.06.
  
 12) IT APPEARS THAT THE BUILDING
 CAN BE CONSIDERED A HIGH-RISE BUILDING
 ACCORDING TO THE BUILDING SECTIONS.
  
 13) ITEMS ON THE BUILDING STILL APPEAR
 TO PROTECT OVER THE PROPERTY LINES
 ACCORDING TO THE BUILDING SECTION
 DIAGRAMS.
  
 14) IT APPEARS THAT EXITING ON LEVELS
 B1 AND B2 PASSES BY IN SOME CASES
 PARKING SPACES THAT PERSONS MUST
 BACKUP.
  
 15) SIGNS WILL BE NEEDED TO IDENTIFY
 THE STRETCHER ACCESSIBLE ELEVATORS.
  
 16) IT APPEARS THAT THE DOOR AT
 GROUND LEVEL FOR STAIR # 3 OPENS
 DIRECTLY INFRONT OF A WALL.
  
 17) PLEASE INDICATE HOW STAIR # 1
 LEADS DIRECTLY TO THE EXTERIOR. IT
 APPEARS TO TERMINATE WITHIN THE
 BUILDING.
  
 18) IF LESS THAN THREE STEPS ARE PLANNED
 FOR A LOCATION, THEN THE MINIMUM TREAD
 DEPTH MUST BE AT LEAST 13" WIDE.
  
 19) STAIRS THAT FACE CITY STREETS AT
 GROUND LEVEL DO NOT APPEAR TO HAVE
 HANDRAILS.
  
 20) SECOND FLOOR LIFE SAFETY PLAN CHART
 INDICATES AN OCCUPANT LOAD OF 560
 PERSONS. YOUR COMMENTS OF 540 OCCUPANTS
 ALLOWED AND 526 PERSONS ALLOWED DO
 NOT ALIGN THEMSELVES WITH ONE ANOTHER.
  
 21) COULD NOT LOCATE ANY STAIRS TO
 THE ROOF ON THE ROOF PLAN.
  
 22) THE FIRE ALARM ANNUNCIATOR SHOULD
 BE INSTALLED NEAR THE MAIN ENTRY DOORS
 NOT IN THE FIRE COMMAND ROOM WHERE THE
 MAIN PANEL WILL BE LOCATED.
  
 23) PLEASE EXPLAIN NOTE # 12 ON FIRE
 ALARM SEQUENCE OF OPERATIONS.
  
 24) FIRE SPRINKLER PROTECTION WILL
 BE REQUIRED TO BE INSTALLED IN THE
 RETAIL SPACES OF THE BUILDING PRIOR
 TO RECEIVING A C OF O.
  
 25) THE FIRE COMMAND ROOM NOTES ON
 E-2.5 IS NOT CORRECT. PLEASE SEE
 FBC, SECTION 412 FIRE COMMAND ROOMS.
  
 26) ALL MECHANICAL, ELECTRICAL, AND
 SERVICE ROOMS SHALL BE EQUIPPED WITH
 SMOKE DETECTORS.
  
 27) NO EXIT SIGNS SHOWN IDENTIFYING
 EXIT LOCATIONS FROM POOL AND PLANTER
 AREA.
  
 28) ALL HOSE VALVES SHALL BE PROVIDED
 WITH 2 1/2 TO 1 1/2 REDUCERS.
  
 29) WHERE IS THE FIRE PROTECTION FOR
 THE UNIT LOWER LEVEL FLOOR PLAN
 BETWEEN THE TWO DOORS NEAR THE
 HANDICAPPED BATHROOM ON FP-4.10.
  
 30) NO STANDPIPE INDICATED ON FP -1.1.
  
 31) FDC ON PAGE FP-2.2 IS FACING THE
 WRONG WAY.
  
 32) UNIT C/17 ON PAGE FP-4.4 DOES NOT
 APPEAR TO HAVE ENOUGH SPRINKLER
 COVERAGE.
  
 33) PLEASE PROVIDE A DIAGRAM FOR
 THE SMOKE MANAGEMENT PANEL IN THE
 FIRE ALARM CONTROL ROOM.
  
 34) STAIRWELL PRESSURIZATION WATER
 COLUMN REQUIREMENTS SHALL BE NOTED
 ON THE PLANS. ALSO TESTING REQUIREMENTS
 SHALL BE DOCUMENTED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By mcarsill Date 2003-04-03 Time 15:12 Rev Time 0.00
Received By mcarsill Date 2003-04-03 Time 15:12 Sent To  
Notes
2003-04-03 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED FOR
 FIRE AND PARAMEDICAL EQUIPMENT DURING
 CONSTRUCTION.
  
 3) ALL CONSTRUCTION RELATED WORK SHALL
 COMPLY WITH NFPA 241.
  
 4) BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. CERTAIN RESTRICTIONS APPLY.
 PLEASE SEE APPENDIX F, LOCAL AMENDMENTS
 TO THE FLORIDA BUILDING CODE.
  
 5) ELECTRONIC SWITCHES ARE REQUIRED ON
 THE FIRE LINE OS & Y VALVES.
  
 6) ALL RAMPS AND STAIRS SHALL BE
 EQUIPPED WITH HANDRAILS.
  
 7) PLEASE REVIEW NFPA 1, WITH REGARDS TO
 PROPANE GRILLS BEING LOCATED ABOVE
 THE FIRST FLOOR IN A MULTI-FAMILY
 DWELLING.
  
 8) SEVERAL DRAWINGS DEPICT EXTERIOR
 DOORS ON THE DATURA STREET SIDE
 OPENING OVER STAIRS.
  
 9) POLYSTYRENE MOLDING NOTED ON TYPICAL
 BALCONY DETAILS. PLEASE SEE APPENDIX F,
 LOCAL AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 10) A TWO HOUR FIRE RATING IS REQUIRED
 BETWEEN THE PARKING GARAGE AND OTHER
 PORTIONS OF THE BUILDING. OPENING
 PROTECTIVES SHALL BE AT LEAST 1 1/2
 HOURS.
  
 11) PLEASE INDICATE WHICH ELEVATORS
 COMPLY WITH THE STRETCHER REQUIREMENTS
 OF THE FBC.
  
 12) VERIFY DOUBLE DOOR SWING IN
 CORRIDOR 119.
  
 13) THE FIRE CONTROL ROOM SHOULD HAVE
 A DOOR FROM THE RESIDENTIAL LOBBY SIDE.
  
 14) IT APPEARS SOME NOTES ON ROOF PLAN
 ARE ILLEGIBLE.
  
 15) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS.
  
 16) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 17) THE SIGNAGE SHOULD BE REVISED TO
 READ "ELECTRICAL ROOM, NO STORAGE BY
 ORDER OF THE FIRE MARSHAL".
  
 18) ALL ELEVATORS TO COMPLY WITH 61C-5.
  
 19) PLEASE ADVISE WHAT THE FIRE ALARM
 ACTIVATION MESSAGE WILL SAY.
  
 20) PLEASE INDICATE WHERE THE APARTMENTS
 THAT HAVE SPEAKER STROBES IN THEM.
  
 21) PLEASE ADD NOTE-SMOKE DETECTORS ARE
 TO BE INSTALLED A MINIMUM OF THREE FEET
 FROM AC DIFFUSERS.
  
 22) ALL SHAFTWAYS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY IN RED LETTERS.
  
 23) SOME MORE EXIT SIGNS APPEAR TO
 BE NEEDED ON SOME OF THE ELECTRICAL
 PAGES.
  
 24) SOME EXIT SIGNS APPEAR TO OPPOSE
 ONE ANOTHER.
  
 25) FABRIC AWNINGS ARE NOTED. THESE
 MUST BE FIRE RETARDANT.
  
 26) SOUTH COURTYARD ELEVATION APPEARS
 TO EXTEND OVER PROPERTY LINE.
  
 27) PLEASE INDICATE WHICH STAIRTOWERS
 LEAD DIRECTLY TO THE EXTERIOR. AT LEAST
 50 PERCENT OF THE EXIT STAIRS MUST
 LEAD DIRECTLY TO THE EXTERIOR.
  
 28) ACCORDING TO THE GROUND FLOOR,
 RESTAURANTS ARE PROPOSED. HOW AND
 WHERE WILL THE KITCHEN HOOD SYSTEMS
 EXHAUST.
  
 29) PLEASE EXPLAIN EXITING RATIONALE
 FROM THE GARAGE.
  
 30) PLEASE PROVIDE INFORMATION ON TYPE
 OF CONSTRUCTION THE BUILDING WILL BE.
  
 31) STAIR # 6 APPEARS TO EXIT INTO
 RETAIL # 1. IS THIS PROPER.
  
 32) STAIR # 8 APPEARS TO TERMINATE
 INTO STORAGE # 2.
  
 33) ANY EXIT CORRIDORS ADJACENT TO
 STAIRTOWERS SHOULD HAVE THE SAME FIRE
 RATING AS THE STAIR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 126 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 14:06 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 14:06 Sent To  
Notes
2007-09-21 08:30:43TO "COMM" BD#11/PLANS ON RACK--4 ROLLS
2007-08-29 14:06:41WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 125 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 14:32 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 14:32 Sent To P
Notes
2007-03-10 14:33:06TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 124 Status N Date 2006-09-15 Cont ID  
Sent By adarroug Date 2006-09-15 Time 16:55 Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 16:55 Sent To  
Notes
2006-10-05 00:00:00TO "COMM" BD#15
2006-09-15 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 123 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 16:39 Sent To E
Notes
2006-09-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 122 Status N Date 2006-04-06 Cont ID  
Sent By adarroug Date 2006-04-06 Time 11:25 Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 11:25 Sent To B
Notes
2006-04-06 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 121 Status N Date 2005-11-21 Cont ID  
Sent By adarroug Date 2005-11-21 Time 14:17 Rev Time 0.00
Received By adarroug Date 2005-11-21 Time 14:17 Sent To B
Notes
2005-11-21 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 120 Status N Date 2005-11-21 Cont ID  
Sent By adarroug Date 2005-11-21 Time 14:15 Rev Time 0.00
Received By adarroug Date 2005-11-21 Time 14:15 Sent To M
Notes
2005-11-21 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 119 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-10-21 Time 09:52 Rev Time 0.00
Received By adarroug Date 2005-10-21 Time 09:52 Sent To  
Notes
2005-11-15 00:00:00TO "COMM" BD#21/PLANS ON RACK 6 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 118 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 16:02 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 16:02 Sent To B
Notes
2005-11-14 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 117 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 11:10 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 11:10 Sent To B
Notes
2005-11-14 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 116 Status N Date 2005-10-13 Cont ID  
Sent By adarroug Date 2005-10-13 Time 08:44 Rev Time 0.00
Received By adarroug Date 2005-10-13 Time 08:44 Sent To FIRE
Notes
2005-10-13 00:00:00TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 115 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 09:20 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 09:20 Sent To P
Notes
2005-07-20 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 114 Status N Date 2005-07-13 Cont ID  
Sent By adarroug Date 2005-07-13 Time 14:07 Rev Time 0.00
Received By adarroug Date 2005-07-13 Time 14:07 Sent To B
Notes
2005-07-13 00:00:00TO "JWITMER" DESK/ 2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 113 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 08:29 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 08:29 Sent To M
Notes
2005-07-07 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 112 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 08:12 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 08:12 Sent To M
Notes
2005-07-06 00:00:00TO "PKRAUSS" BOX/10 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 111 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 17:28 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 17:28 Sent To B
Notes
2005-07-01 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 110 Status N Date 2005-06-27 Cont ID  
Sent By adarroug Date 2005-06-27 Time 08:30 Rev Time 0.00
Received By adarroug Date 2005-06-27 Time 08:30 Sent To M
Notes
2005-06-27 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 109 Status N Date 2005-06-16 Cont ID  
Sent By shill Date 2005-06-16 Time 08:35 Rev Time 0.00
Received By mjacobs Date 2005-06-16 Time 08:35 Sent To  
Notes
2005-06-20 00:00:00COMM BD#35 PLANS ON RACK
  
2005-06-16 00:00:00WAITING FOR COMM BOARD
 PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 108 Status N Date 2005-06-14 Cont ID  
Sent By mjacobs Date 2005-06-14 Time 08:14 Rev Time 0.00
Received By mjacobs Date 2005-06-14 Time 08:14 Sent To P
Notes
2005-06-14 00:00:00TO 'P' BOX REV/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 107 Status N Date 2005-06-14 Cont ID  
Sent By mjacobs Date 2005-06-14 Time 08:11 Rev Time 0.00
Received By mjacobs Date 2005-06-14 Time 08:11 Sent To B
Notes
2005-06-14 00:00:00TO 'JW' DESK SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 106 Status N Date 2005-06-07 Cont ID  
Sent By mjacobs Date 2005-06-07 Time 10:39 Rev Time 0.00
Received By mjacobs Date 2005-06-07 Time 10:38 Sent To P
Notes
2005-06-07 00:00:00TO 'P' BOX.

Review Stop I INCOMING/PROCESSING
Rev No 105 Status N Date 2005-05-05 Cont ID  
Sent By adarroug Date 2005-04-27 Time 11:08 Rev Time 0.00
Received By adarroug Date 2005-04-27 Time 16:58 Sent To  
Notes
2005-05-05 00:00:005/5/05- TO "COMM" BD#44
2005-05-03 00:00:00IN INCOMING/AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 104 Status N Date 2005-03-16 Cont ID  
Sent By adarroug Date 2005-03-16 Time 10:25 Rev Time 0.00
Received By adarroug Date 2005-03-16 Time 10:25 Sent To B
Notes
2005-03-16 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 103 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 10:02 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 10:02 Sent To B
Notes
2005-03-14 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 102 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 10:01 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 10:01 Sent To B
Notes
2005-03-14 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 101 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 10:00 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 10:00 Sent To B
Notes
2005-03-14 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 100 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 09:59 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 09:59 Sent To B
Notes
2005-03-14 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 99 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 09:58 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 09:58 Sent To B
Notes
2005-03-14 00:00:00TO "JWITMER"DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 98 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 09:57 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 09:57 Sent To B
Notes
2005-03-14 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 97 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 09:30 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 09:30 Sent To P
Notes
2005-03-14 00:00:00TO "KSTEVENS" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 96 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 09:28 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 09:28 Sent To P
Notes
2005-03-14 00:00:00TO "KSTEVENS" BOX

Review Stop I INCOMING/PROCESSING
Rev No 95 Status N Date 2005-02-24 Cont ID  
Sent By adarroug Date 2005-02-24 Time 14:28 Rev Time 0.00
Received By adarroug Date 2005-02-24 Time 14:28 Sent To  
Notes
2005-02-24 00:00:00TO "COMM" BD#26/SUBMITTAL
 ON BD AS REVISION

Review Stop I INCOMING/PROCESSING
Rev No 94 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 08:57 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 08:57 Sent To B
Notes
2005-02-15 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 93 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 08:55 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 08:54 Sent To B
Notes
2005-02-15 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 92 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 09:52 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 09:52 Sent To  
Notes
2005-01-20 00:00:00TO "COMM BD#7"

Review Stop I INCOMING/PROCESSING
Rev No 91 Status N Date 2005-01-19 Cont ID  
Sent By mjacobs Date 2005-01-19 Time 13:22 Rev Time 0.00
Received By mjacobs Date 2005-01-19 Time 13:22 Sent To B
Notes
2005-01-19 00:00:00TO "JW" DESK./SUBMITTALS/LETTERS.

Review Stop I INCOMING/PROCESSING
Rev No 90 Status N Date 2005-01-18 Cont ID  
Sent By mjacobs Date 2005-01-18 Time 11:00 Rev Time 0.00
Received By mjacobs Date 2005-01-18 Time 11:00 Sent To B
Notes
2005-01-18 00:00:00TO "JW" DESK/SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2004-12-08 Cont ID  
Sent By mjacobs Date 2004-12-08 Time 14:48 Rev Time 0.00
Received By mjacobs Date 2004-12-08 Time 14:48 Sent To M
Notes
2004-12-08 00:00:00SENT TO "M/AC " BOX.

Review Stop I INCOMING/PROCESSING
Rev No 88 Status N Date 2004-12-08 Cont ID  
Sent By mjacobs Date 2004-12-08 Time 14:43 Rev Time 0.00
Received By mjacobs Date 2004-12-08 Time 14:43 Sent To B
Notes
2004-12-08 00:00:00SENT TO "JW" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2004-12-08 Cont ID  
Sent By mjacobs Date 2004-12-08 Time 14:40 Rev Time 0.00
Received By mjacobs Date 2004-12-08 Time 14:40 Sent To P
Notes
2004-12-08 00:00:00SENT TO "P" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2004-12-08 Cont ID  
Sent By mjacobs Date 2004-12-08 Time 14:37 Rev Time 0.00
Received By mjacobs Date 2004-12-08 Time 14:37 Sent To E
Notes
2004-12-08 00:00:00SENT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2004-11-19 Cont ID  
Sent By csiegber Date 2004-11-19 Time 14:21 Rev Time 0.00
Received By csiegber Date 2004-11-19 Time 14:21 Sent To  
Notes
2004-11-19 00:00:00TO JW DESK/5 SUBMITTALS
 ROOF POUR 3
 FLOOR 5 POUR 4
 FLOOR 6 POUR 5
 FLOOR 6 POUR 4
 SHORING LETTER

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2004-11-09 Cont ID  
Sent By csiegber Date 2004-11-09 Time 09:03 Rev Time 0.00
Received By csiegber Date 2004-11-09 Time 09:03 Sent To M
Notes
2004-11-09 00:00:00TO PK BOX/SUBMITTAL
 GENERATOR PIPE INSULATION

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2004-11-09 Cont ID  
Sent By csiegber Date 2004-11-09 Time 09:01 Rev Time 0.00
Received By csiegber Date 2004-11-09 Time 09:00 Sent To P
Notes
2004-11-09 00:00:00TO KS BOX/3 SUBMITTALS
 MISC PLUMBING
 STEAM GENERATOR
 1/2 BATH FAUCET

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2004-11-09 Cont ID  
Sent By csiegber Date 2004-11-09 Time 08:41 Rev Time 0.00
Received By csiegber Date 2004-11-09 Time 08:41 Sent To B
Notes
2004-11-09 00:00:00TO JW DESK/3 SUBMITTALS/
 PT 27,28, ROOF SOUTH
 FIBERGLASS MESH FOR STUCCO
 GRANITE COUNTERTOPS FOR KITCHEN/09000-01

Review Stop I INCOMING/PROCESSING
Rev No 81 Status N Date 2004-11-04 Cont ID  
Sent By csiegber Date 2004-11-04 Time 09:22 Rev Time 0.00
Received By csiegber Date 2004-11-04 Time 09:22 Sent To B
Notes
2004-11-04 00:00:00TO JW DESK/SUBMITTAL/BALCONY ANCHOR
 CEMENT

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 16:48 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 16:48 Sent To  
Notes
2004-10-28 00:00:00TO HAROLD PISKURA
 8 SUBMITTALS
 DRY-IN PLAN
 FLR 3, POUR #5
 BALCONY ANCHOR CEMENT
 FLR 2,POUR #7
 FLR 7, POUR #2
 FLR 6 POUR #2
 FLR 8, POUR #1
 FLR 3, POUR #4
 FLR 8 POUR #2
 FLR 7 POUR #3

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 16:44 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 16:44 Sent To M
Notes
2004-10-28 00:00:00TO PK DESK/SUBMITTAL
 MISC HVAC SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 16:43 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 16:43 Sent To B
Notes
2004-10-28 00:00:00TO JW DESK/SUBMITTAL
 PT 25,26 ROOF DT NORTH

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 16:42 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 16:42 Sent To E
Notes
2004-10-28 00:00:00TO DP DESK/SUMBITTAL
 MISC ELEC

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2004-10-13 Cont ID  
Sent By csiegber Date 2004-10-13 Time 10:22 Rev Time 0.00
Received By csiegber Date 2004-10-13 Time 10:22 Sent To  
Notes
2004-10-13 00:00:00TO COMM BD#50/3 ROLLS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2004-10-13 Cont ID  
Sent By csiegber Date 2004-10-13 Time 09:34 Rev Time 0.00
Received By csiegber Date 2004-10-13 Time 09:34 Sent To B
Notes
2004-10-13 00:00:00TO JW DESK/2 SUBMITTALS
 FASCIA LETTER
 COMPLETE ROOFING SYSTEM

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-07 Time 13:00 Rev Time 0.00
Received By csiegber Date 2004-10-07 Time 13:00 Sent To E
Notes
2004-10-07 00:00:00TO DP DESK/SUBMITTAL
 LIGHTING FIXTURE REV

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-07 Time 12:59 Rev Time 0.00
Received By csiegber Date 2004-10-07 Time 12:59 Sent To  
Notes
2004-10-07 00:00:00TO KS DESK/PER KS
 SUBMITTAL WATER HEATERS

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-07 Time 10:11 Rev Time 0.00
Received By csiegber Date 2004-10-07 Time 10:11 Sent To B
Notes
2004-10-07 00:00:00TO JW DESK/3 SUBMITTALS
 FLR 6, POUR #3

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2004-10-06 Cont ID  
Sent By ptjomsto Date 2004-10-06 Time 15:37 Rev Time 0.00
Received By ptjomsto Date 2004-10-06 Time 15:37 Sent To  
Notes
2004-10-06 00:00:00SUB GIVEN TO LYNN ATTN NEIL

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:30 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:30 Sent To  
Notes
2004-10-05 00:00:00TO JW DESK/SUBMITTALS/CABINET SHOP DRAWS

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 11:57 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 11:57 Sent To P
Notes
2004-10-05 00:00:00TO KS BOX/SUBMITTAL
 1/2 BATH VANITY

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 11:55 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 11:55 Sent To B
Notes
2004-10-05 00:00:00TO JW DESK/4 SUBMITTALS
 KILZ SEALANT SPRAY
 RAILING POWDER COAT
 FIRE RETARDANT & LUMBER
 FLOOR 7, POUR #1

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 11:07 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 11:07 Sent To M
Notes
2004-10-05 00:00:00TO PK BOX/SUBMITTAL
 DUCTWORK SHOPS

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2004-09-16 Cont ID  
Sent By csiegber Date 2004-09-16 Time 12:10 Rev Time 0.00
Received By csiegber Date 2004-09-16 Time 12:10 Sent To B
Notes
2004-09-16 00:00:00TO JW DESK/13 SUBMITTALS
 TRUSS SHOP DRAWS/MASONRY GROUT ALTERNATE
 PRO SET FIRE SLEEVE/TRASH COMPACTOR/
 EXHAUST FANS/MESH TAPE FOR DRYWALL/
 FRP DOME FOR LOBBY/WASHING MACHINE VALVE
 BOX/FLR 6 POUR #1/FLR 5 POUR #2/
 4TH FLR POUR #3/FLR 2 POUR #6/FLR 5 POUR
 #3/2ND FLR POUR #5

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2004-09-16 Cont ID  
Sent By csiegber Date 2004-09-16 Time 12:09 Rev Time 0.00
Received By csiegber Date 2004-09-16 Time 12:09 Sent To E
Notes
2004-09-16 00:00:00TO DP DESK/SUBMITTAL FOR APPLIANCES

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2004-08-18 Cont ID  
Sent By csiegber Date 2004-08-18 Time 15:13 Rev Time 0.00
Received By csiegber Date 2004-08-18 Time 15:13 Sent To B
Notes
2004-08-18 00:00:00TO JW DESK/SUBMITTAL
 FLOOR 5/POUR #1

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2004-08-18 Cont ID  
Sent By csiegber Date 2004-08-18 Time 12:53 Rev Time 0.00
Received By csiegber Date 2004-08-18 Time 12:53 Sent To B
Notes
2004-08-18 00:00:00JW DESK/SUBMITTAL
 GARAGE STRIPING PAINT & WHEEL STOPS

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2004-08-12 Cont ID  
Sent By mmclean Date 2004-08-18 Time 10:20 Rev Time 0.00
Received By csiegber Date 2004-08-12 Time 15:55 Sent To B
Notes
2004-08-12 00:00:00TO JW DESK/4 SUBMITTALS
 FLOOR 3,POUR #3
 FLOOR 4, POUR 2
 DOORS & HARDWARE
 SPA & POOL EQUIPMENT

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2004-08-04 Cont ID  
Sent By csiegber Date 2004-08-04 Time 11:55 Rev Time 0.00
Received By csiegber Date 2004-08-04 Time 11:55 Sent To B
Notes
2004-08-04 00:00:00TO JW DESK/8 SUBMITTALS
 ARCHIETECTURAL TRIM DETAILS
 SIDEWALK MATERIALS
 DRYWALL PRODUCTS
 POUR #4 FLOOR 2
 SOUTH LOFT SLABS
 POUR#2 FLOOR 3
 POUR #1 FLOOR 4
 PT 21,22,23,24 CALCS

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2004-08-04 Cont ID  
Sent By csiegber Date 2004-08-04 Time 11:53 Rev Time 0.00
Received By csiegber Date 2004-08-04 Time 11:53 Sent To P
Notes
2004-08-04 00:00:00TO KS BOX/2 SUBMITTALS
 BACK FLOW PREVENTORS
 TUB BOXES

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 14:39 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 14:39 Sent To B
Notes
2004-07-21 00:00:00TO JW DESK/2 SUBMITTALS
 REVISED STOREFRONT
 WINDOWS & SLIDERS

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 14:56 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 14:56 Sent To B
Notes
2004-07-19 00:00:00TO JW DESK/5 SUBMITTALS/
 STRUCTURAL STYROFOAM
 KNOX BOX
 BRITE ZINC
 GALV REBAR FOR BALCONIES
 PT 19 & 20 & CALCS 3,5,7,-SOUTH

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 14:52 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 14:52 Sent To FIRE
Notes
2004-07-19 00:00:00TO FIRE/SUMBITTALS
 SPRINKLER HEADS & PIP MATERIAL SAMPLES

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 14:50 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 14:50 Sent To B
Notes
2004-07-19 00:00:00TO JW DESK/4 SUBMITTALS/
 QUAD A PT 11 & 12, POUR #2
 3RD FLR, POUR #1
 QUAD D, ARCADE
 QUAD C & D, LOFTS

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2004-07-09 Cont ID  
Sent By csiegber Date 2004-07-09 Time 16:18 Rev Time 0.00
Received By csiegber Date 2004-07-09 Time 16:18 Sent To  
Notes
2004-07-09 00:00:00TO COMM BD#3

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-07-02 Time 10:35 Rev Time 0.00
Received By csiegber Date 2004-07-02 Time 10:35 Sent To P
Notes
2004-07-02 00:00:00TO KS BOX/SUBMITTAL
 HANGERS PVC,COPPER ETC PIPES

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-07-02 Time 10:35 Rev Time 0.00
Received By csiegber Date 2004-07-02 Time 10:35 Sent To E
Notes
2004-07-02 00:00:00TO DP DESK/SUBMITTAL
 LIGHTING FIXTURES

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-07-02 Time 10:32 Rev Time 0.00
Received By csiegber Date 2004-07-02 Time 10:32 Sent To B
Notes
2004-07-02 00:00:00TO SH DESK/6 SUBMITTALS
 PT 17 & 18
 TRASH CHUTES
 GARAGE STRIPIG PVM & WHEEL STOPS
 TABLE DRAWINGS
 DRYWALL
 EXTERIOR CAST STONE

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 08:53 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 08:53 Sent To B
Notes
2004-06-15 00:00:00TO JW DESK/5SUBMITTALS
 TENANT STORAGE LOCKERS
 QUAD D PT 4,5,POUR #7
 POUR LETTERS FOR PT 4&5,QUAD B
 PT 4,5,6 LETTERS
 BONDING AGENT REINFORCEMENT

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 14:17 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 14:17 Sent To  
Notes
2004-06-11 00:00:00TO COMM BD#6

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2004-06-10 Cont ID  
Sent By csiegber Date 2004-06-10 Time 08:37 Rev Time 0.00
Received By csiegber Date 2004-06-10 Time 08:36 Sent To B
Notes
2004-06-10 00:00:00TO JW DESK/RAISED TRIM REV

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2004-06-09 Cont ID  
Sent By csiegber Date 2004-06-09 Time 13:00 Rev Time 0.00
Received By csiegber Date 2004-06-09 Time 13:00 Sent To P
Notes
2004-06-09 00:00:00TO KS BOX/REV/PLANTER DRAINAGE

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2004-06-07 Cont ID  
Sent By csiegber Date 2004-06-07 Time 10:55 Rev Time 0.00
Received By csiegber Date 2004-06-07 Time 10:55 Sent To B
Notes
2004-06-07 00:00:00TO JW DESK/3 SUBMITTALS
 QUAD B,PT 8&9-POUR LETTERS
 2ND FLOOR SOUTH CALCS
 PT 11 &12 REVISED

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 11:34 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 11:34 Sent To Z
Notes
2004-06-03 00:00:00TO MM REV

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2004-05-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-05-28 Time 16:28 Sent To B
Notes
2004-05-28 00:00:00TO JW DESK/6 SUBMITTALS/STRUCTURAL STYRO
 FOAM - MINERAL WOOL & FIRE CAULK -
 FIRE STOPPING SLEEVES - ROLL UP DOOR -
 STOREFRONT SHOP & CALCS - PT 13 & 14

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2004-05-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 16:27 Rev Time 0.00
Received By csiegber Date 2004-05-28 Time 16:27 Sent To E
Notes
2004-05-28 00:00:00TO DP DESK/ELEC FLOOR BOXES

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2004-05-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 16:26 Rev Time 0.00
Received By csiegber Date 2004-05-28 Time 16:26 Sent To FIRE
Notes
2004-05-28 00:00:00VALVE CABINET

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2004-05-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 16:25 Rev Time 0.00
Received By csiegber Date 2004-05-28 Time 16:25 Sent To B
Notes
2004-05-28 00:00:00TO JW DESK/SUBMITTAL/POUR LETTERS
 PT 8/9,QUAD B/C

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2004-05-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 16:13 Rev Time 0.00
Received By csiegber Date 2004-05-28 Time 16:13 Sent To B
Notes
2004-05-28 00:00:00TO JW DESK/SUBMITTAL POUR LETTER UPPER
 GROUND FLOOR

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 14:28 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 14:28 Sent To P
Notes
2004-05-20 00:00:00TO KS BOX/SUBMITTAL/MOP SINK

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 14:24 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 14:24 Sent To B
Notes
2004-05-20 00:00:00TO JW DESK/5 SUBMITTALS
 PT SIGNED & SEALED SKETCHES PT 4 & 5;
 ALL SIGNED & SEALED POUR LETTER TO DATE;
 FIRE EXT & CABINET;POUR LETTERS QUAD A
 NW RAMP;QUAD A/B,PT 10,UPPER GR FL

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-06 Time 12:03 Rev Time 0.00
Received By csiegber Date 2004-05-06 Time 12:03 Sent To E
Notes
2004-05-06 00:00:00TO DP DESK/SUBMITTAL/SWITCH GEAR

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-06 Time 12:01 Rev Time 0.00
Received By csiegber Date 2004-05-06 Time 12:01 Sent To B
Notes
2004-05-06 00:00:00TO JW DESK/2 SUBMITTALS/PT 8 & 9
 PT 1N, EL 29'6", QUAD B

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:40 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:40 Sent To B
Notes
2004-04-22 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:40 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:40 Sent To B
Notes
2004-04-22 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:38 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:38 Sent To B
Notes
2004-04-22 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:20 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:20 Sent To B
Notes
2004-04-22 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:15 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:14 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 09:39 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 09:39 Sent To M
Notes
2004-04-14 00:00:00TO PK BOX/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 16:29 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 16:29 Sent To B
Notes
2004-04-13 00:00:00TO JW DESK/FLAT ROOFING SYSTEMS W/OUT
 LIGHT WEIGHT CONCRETE

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 16:24 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 16:24 Sent To E
Notes
2004-04-13 00:00:00TO DP DESK/SUBMITTAL/GENERATOR

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 16:21 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 16:21 Sent To B
Notes
2004-04-13 00:00:00TO JW DESK/SUBMITTAL/ROOFING SYSTEMS

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 15:46 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 15:46 Sent To P
Notes
2004-04-13 00:00:00TO KS BOX/SUBMITTAL/BALL VALVE/COPPER
 TUBING

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-04-05 Time 12:13 Rev Time 0.00
Received By csiegber Date 2004-04-05 Time 12:13 Sent To B
Notes
2004-04-05 00:00:00TO JW DESK/SUBMITTAL/
 PLACING BOOM TOWER RESHORING/DESIGN MIX
 ALT/PROPOSED ALTERNATE DRINKING FOUNTAIN
 & INTERIOR ROLLIG DOOR FOR COMM TENANT

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2004-03-31 Cont ID  
Sent By alange Date 2004-03-31 Time 11:10 Rev Time 0.00
Received By alange Date 2004-03-31 Time 11:09 Sent To B
Notes
2004-03-31 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-03-26 Time 11:40 Rev Time 0.00
Received By csiegber Date 2004-03-26 Time 11:40 Sent To B
Notes
2004-03-26 00:00:00TO JW DESK/SUBMITTAL/SHORING FR NW RAMP
 ELONGATION OF PT CABLE/WATER VAPOR

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-03-26 Time 11:37 Rev Time 0.00
Received By csiegber Date 2004-03-26 Time 11:37 Sent To P
Notes
2004-03-26 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2004-03-25 Cont ID  
Sent By shill Date 2004-03-25 Time 08:06 Rev Time 0.00
Received By shill Date 2004-03-25 Time 08:06 Sent To B
Notes
2004-03-25 00:00:00SUBMITTALS TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 09:34 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 09:34 Sent To B
Notes
2004-03-23 00:00:00TO SH DESK/5 SUBMITTALS
 TYPE F DOORS & B DOORS/S.O.D. EL 27 POUR
 #3/WATERPROOFING/MASONARY/PT11,12 SHOPS
 & CALCS

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2004-03-03 Cont ID  
Sent By csiegber Date 2004-03-03 Time 10:21 Rev Time 0.00
Received By csiegber Date 2004-03-03 Time 10:21 Sent To B
Notes
2004-03-03 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 10:53 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 10:53 Sent To B
Notes
2004-02-25 00:00:00TO JW DESK/SHORING EL-25

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2004-02-19 Cont ID  
Sent By shill Date 2004-02-19 Time 09:10 Rev Time 0.00
Received By shill Date 2004-02-19 Time 09:10 Sent To  
Notes
2004-02-19 00:00:00SHORING LETTER & POUR LETTERS TAKEN FROM
 JW DESK, GIVEN TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-13 Time 15:19 Rev Time 0.00
Received By csiegber Date 2004-02-13 Time 15:19 Sent To B
Notes
2004-02-13 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 16:49 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 16:49 Sent To P
Notes
2004-02-11 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 11:38 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 11:38 Sent To E
Notes
2004-02-11 00:00:00TO DP DESK/SUBMITTAL/ELEC SUMP PUMP

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 11:30 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 11:30 Sent To P
Notes
2004-02-11 00:00:00TO KS BOX/SUBMITTAL/PVC PIPE & FITTINGS

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 11:29 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 11:29 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 11:23 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 11:23 Sent To B
Notes
2004-02-11 00:00:00TO JW DESK/SUBMITTAL/WATERPROOFING/BACKS
 HORE RETAINING WALLS/VOLCLAY WATERSTOP/
 SHORING TO EL 15

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-01-09 Cont ID  
Sent By csiegber Date 2004-01-09 Time 10:30 Rev Time 0.00
Received By csiegber Date 2004-01-09 Time 10:29 Sent To B
Notes
2004-01-09 00:00:00TO JW DESK/WATERPROOFING/PRE POUR MTG
 MIN/PT SHOPS & CALCS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-12-09 Cont ID  
Sent By csiegber Date 2003-12-09 Time 16:16 Rev Time 0.00
Received By csiegber Date 2003-12-09 Time 16:15 Sent To B
Notes
2003-12-09 00:00:00TO JW DESK/PA

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-12-03 Cont ID  
Sent By csiegber Date 2003-12-03 Time 15:34 Rev Time 0.00
Received By csiegber Date 2003-12-03 Time 15:34 Sent To B
Notes
2003-12-03 00:00:00TO JW DESK/SUBMITTAL/BOOM TERMITE TRMT
 CONCRETE SUBM

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-11-24 Cont ID  
Sent By csiegber Date 2003-11-24 Time 14:11 Rev Time 0.00
Received By csiegber Date 2003-11-24 Time 14:11 Sent To B
Notes
2003-11-24 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-11-10 Cont ID  
Sent By csiegber Date 2003-11-10 Time 15:00 Rev Time 0.00
Received By csiegber Date 2003-11-10 Time 15:00 Sent To P
Notes
2003-11-10 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-20 Cont ID  
Sent By csiegber Date 2003-10-20 Time 12:18 Rev Time 0.00
Received By csiegber Date 2003-10-20 Time 12:18 Sent To  
Notes
2003-10-20 00:00:00TO COMM BD#5/RESUB ON RACK 610 CLEMATIS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-22 Cont ID  
Sent By csiegber Date 2003-08-22 Time 08:50 Rev Time 0.00
Received By csiegber Date 2003-08-22 Time 08:50 Sent To P
Notes
2003-08-22 00:00:00TO KS - ON TABLE IN FRONT OF DS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 08:09 Rev Time 0.00
Received By alange Date 2003-08-08 Time 08:09 Sent To  
Notes
2003-08-08 00:00:00TO COMM BD #15 PLANS ON BOTTOM SHELF
 NEAR MEETING ROOMALANGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-25 Time 15:12 Rev Time 0.00
Received By shernand Date 2003-04-25 Time 15:12 Sent To Z
Notes
2003-04-25 00:00:00REMOVED FROM BOARD, GAVE TO ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-20 Cont ID  
Sent By sthyng Date 2003-03-20 Time 16:32 Rev Time 0.00
Received By sthyng Date 2003-03-20 Time 16:32 Sent To  
Notes
2003-03-20 00:00:00COMM BOARD #4
 2 ROLLS, 1 BOX, 1 ADD'L BINDER

Review Stop M MECHANICAL (A/C)
Rev No 21 Status P Date 2006-10-25 Cont ID  
Sent By hmoser Date 2006-10-25 Time 19:20 Rev Time 0.00
Received By hmoser Date 2006-10-25 Time 19:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 20 Status P Date 2006-01-25 Cont ID  
Sent By hmoser Date 2006-01-25 Time 08:16 Rev Time 0.00
Received By hmoser Date 2006-01-25 Time 08:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 19 Status P Date 2006-01-04 Cont ID  
Sent By pkrauss Date 2006-01-04 Time 07:12 Rev Time 0.00
Received By pkrauss Date 2006-01-04 Time 07:12 Sent To  
Notes
2006-01-04 00:00:00AS BUILT DRAWINGS

Review Stop M MECHANICAL (A/C)
Rev No 18 Status P Date 2005-12-01 Cont ID  
Sent By hmoser Date 2005-12-01 Time 15:11 Rev Time 0.00
Received By hmoser Date 2005-12-01 Time 15:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 17 Status P Date 2005-07-28 Cont ID  
Sent By hmoser Date 2005-07-28 Time 16:29 Rev Time 0.00
Received By hmoser Date 2005-07-28 Time 16:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 16 Status N Date 2005-07-12 Cont ID  
Sent By hmoser Date 2005-07-12 Time 09:36 Rev Time 0.00
Received By hmoser Date 2005-07-12 Time 09:36 Sent To P
Notes
2005-07-12 00:00:00SHOP DROWINGS

Review Stop M MECHANICAL (A/C)
Rev No 15 Status F Date 2005-07-09 Cont ID  
Sent By hmoser Date 2005-07-09 Time 10:53 Rev Time 0.00
Received By hmoser Date 2005-07-09 Time 10:51 Sent To  
Notes
2005-07-09 00:00:00PLAN DENIED
 1) PLEASE SHOW RETURN AIR IN BEDROOMS ON
 PLAN FOR SUITES
 C,D,E,H,J,L,L-05,L-08,L-09,M-01,M-38,
 N-03,S-130,U-134 PER SECTION 601.4FBC
 (M)2001
 2) PLEASE SHOW HOW RETURN AIR IS GETTING
 BACK TO A/C FROM SUITES BY SHADING IN
 RETURN AIR PLENUMS.
 3) PLEASE HAVE MANUFACTURES INSTRUCTIONS
 ON THE LENGTH OF THE EXHAUST FOR THE
 GENERATOR FOR FINAL INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date   Cont ID  
Sent By shill Date 2005-05-17 Time 14:48 Rev Time 0.00
Received By hmoser Date 2005-05-10 Time 16:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date   Cont ID  
Sent By   Date 2005-04-04 Time   Rev Time 0.00
Received By hmoser Date 2005-04-04 Time 08:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2005-03-23 Cont ID  
Sent By pkrauss Date 2005-03-23 Time 14:52 Rev Time 0.40
Received By pkrauss Date 2005-03-23 Time 14:51 Sent To  
Notes
2005-03-23 00:00:00SUBMITTAL - FIRE STOP DETAIL PER H.
 MOSERS REQUEST
 SUBMITTAL -STACKABLE WASHER/DRYER

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2005-01-27 Cont ID  
Sent By pkrauss Date 2005-01-27 Time 16:40 Rev Time 0.40
Received By pkrauss Date 2005-01-27 Time 16:40 Sent To  
Notes
2005-01-27 00:00:00SUBMITTAL:
 FUEL OIL PIPING - SEE COMMENTS BY
 ENGINEER AS TO LOCATION OF FUEL PIPING.
 RETURN AIR GRILLES

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2005-01-27 Cont ID  
Sent By pkrauss Date 2005-01-27 Time 07:01 Rev Time 1.30
Received By pkrauss Date 2005-01-27 Time 07:01 Sent To  
Notes
2005-01-27 00:00:00SUBMITTALS:
 ACCESS PANELS, CONDENSING UNIT STANDS,
 AHU STANDS, DUCTWORK MATERIALS & GEN
 SHROUD, DUCT INSULATION, BATH EXHAUST
 FANS, PIPING SUBMITTALS.
  
 PROVISO:
 CONDENSING UNIT STANDS SHALL COMPLY
 WITH THE 2001 FBC 1511.7 FOR CLEARANCE
 REQUIREMENTS BETWEEN THE ROOF SURFACE &
 THE BOTTOM OF THE SUPPORT RAIL.
  
 PVC TRAPS ARE NOT TO BE USED IN PLENUMS
 PER 2001 FBC(M)602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date   Cont ID  
Sent By   Date 2005-01-19 Time   Rev Time 0.00
Received By hmoser Date 2005-01-19 Time 09:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2004-11-22 Cont ID  
Sent By pkrauss Date 2004-11-22 Time 13:30 Rev Time 0.40
Received By pkrauss Date 2004-11-22 Time 13:30 Sent To  
Notes
2004-11-22 00:00:00SUBMITTAL FOR THE INSULATION FOR THE
 MUFFLER EXHAUST PIPING.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2004-11-16 Cont ID  
Sent By pkrauss Date 2004-11-16 Time 16:58 Rev Time 4.00
Received By pkrauss Date 2004-11-09 Time 17:42 Sent To  
Notes
2004-11-16 00:00:00REVISED PLAN SHEETS
 M-2.2,M-2.4,M-2.8,M-2.25,M-2.27, M-2.27,
 M-5.2, M-7.2.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2004-08-10 Cont ID  
Sent By pkrauss Date 2004-08-09 Time 16:06 Rev Time 2.50
Received By pkrauss Date 2004-08-09 Time 16:06 Sent To  
Notes
2004-08-09 00:00:00DENIED:
 1.PLAN SHEET M-2.4, CLARIFY INTAKE TO
 THE ELECTRICAL ROOM, WAS THE DUCT
 EXTENDED TO AN EXTERIOR WALL?PLEASE
 CLARIFY RATING OF THIS WALL.
  
 2.THANK YOU FOR THE SUMMARY OF
 CHANGES SUBMITTED WITH THE REVISED
 PLANS.WILL THESE BE CHANGES INDICATED
 ON THE SUBMITTAL LETTER BE REVISION #11?
  
 PLEASE NOTE, CHANGES MADE TO THE PLANS
 PROIR TO PERMIT ARE NOT CONSIDERED
 "REVISIONS".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-04-26 Cont ID  
Sent By pkrauss Date 2004-04-26 Time 09:37 Rev Time 1.00
Received By pkrauss Date 2004-04-26 Time 09:36 Sent To  
Notes
2004-04-26 00:00:00SUBMITTALS/RTU'S/SPLIT SYSTEMS/GRILLES
 DIFFUSERS & LOUVERS/FANS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-11-21 Cont ID  
Sent By pkrauss Date 2003-11-21 Time 15:45 Rev Time 7.00
Received By pkrauss Date 2003-11-21 Time 15:45 Sent To  
Notes
2003-11-21 00:00:00APPROVED PER HAROLD MOSER 11-21-03

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-11-13 Cont ID  
Sent By pkrauss Date 2003-11-13 Time 10:47 Rev Time 2.30
Received By pkrauss Date 2003-11-13 Time 08:13 Sent To  
Notes
2003-11-13 00:00:00DENIED:
 PLEASE NOTE THE FOLLOWING INFORMATION
 NOT ANSWERED FROM PREVIOUS REVIEW BY
 HAROLD MOSER DATED 9-22-03.
  
 #1BALANCED AIR RETURN - PLEASE NOTE
 PLANS DO NOT INDICATE ANY SIZE FOR THE
 TRANSFER OR RETURN AIR GRILLES.PLEASE
 SEE THE ATTACHED FOR PROPER SIZING.
 INDICATE SIZING ON PLAN.
  
 #3 & 5 FRESH AIR FROM RTU-1, PLEASE NOTE
 THE LOCATION OF THE FRESH AIR SHALL BE
 RECIRCULATED INTO THE SYSTEM.PLEASE
 EXPLAIN HOW THIS COMPLIES WITH ASHRAE
 62-89 SECTION 6.1.3.2 & 6.1.3.3.
  
 REVIEW BY PATTY KRAUSS:
 CLARIFY THE FOLLOWING INFORMATION:
 1. PLAN SHEET M-2.3 O.A. SHALL HAVE A
 10 FT SEPARATION FROM NOXIOUS EXHAUST AS
 PER 2001 FBC(M) 401.5.1.
  
 2.PLAN SHEET M-2.6 PLEASE CLARIFY
 O.A. LOUVER INTO RETAIL SPACE #4 & 5,
 WILL THIS BE USED FOR FUTURE O.A. WILL
 IT BE DUCTED? SEE COMMENT #3 ABOVE.
  
 3.PLAN SHEET M-2.10 E/A DUCT UP TO REF
 12 WHAT WILL THIS BE FOR TOILET & DRYER
 EXHAUST? DETAILS INDICATE TOILET & DRYER
 THRU THE UNIT TO AN OUTSIDE WALL (M-4.1)
  
 4.PLAN SHEET M-3.1 GENERATOR EXHAUST
 SHALL BE A MINIMUM OF 10 FT ABOVE THE
 ADJOINING GRADE.
  
 5.PLAN SHEET M-4.1 HVAC GENERAL NOTES
 FURNISH & INSTALL TRANSFER GRILLES &
 RETURN AIR CENTERED ABOVE THE BATHROOM
 DOORS.AIR FROM BATHROOM AREA SHALL NOT
 BE RECIRCULATED EXHAUST ONLY PER 2001
 FBC(M) TABLE 403.3.PLEASE SEE ATTACHED
 FOR PROPER SIZING OF TRANSFER GRILLES
 AND RETURN AIR DUCTS. INDICATE DUCT &
 GRILLE SIZES AND LOCATIONS ON PLANS.
  
 6.PLEASE PROVIDE O.A. CALCULATIONS FOR
 THE COMMON AND RESIDENTIAL AREAS AS PER
 2001 FBC(M) TABLE 403.3 & ASHRAE 62-89.
  
 7.PLEASE NOTE O.A. & EXHAUST AIR FROM
 THE EMERGENCY GENERATOR RM, PUMP RM,
 SWITCHGEAR RM & ELEC RM IS ALL TAKEN
 FROM THE GARAGE AREA.
  
 8.PROVIDE ENERGY CALCULATIONS.
  
 9.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE EMERGENCY GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-09-30 Cont ID  
Sent By hmoser Date 2003-09-22 Time 18:04 Rev Time 3.00
Received By hmoser Date 2003-09-22 Time 18:03 Sent To  
Notes
2003-09-22 00:00:00PLAN DENIED
 1) REFER TO SECTION 601.4 BALANCED
 RETURN AIR (NOTE #12)
 2) CAN NOT EXHAUST IN TO WALK WAY M-2.3
 3) CAN NOT BRING IN FRESH AIR FROM
 LOADING DOCK.
 4) GSEF#3 RISER AND PLAN DO NOT MATCH
 5) NEED FRESH AIR FOR GYMNAIIUM.FRESH
 AIR CAN NOT COME FROM GARAGE OR
 LOADING DOCK.
 6) NO EQUIPMENT SCHEDULE FOR RTU# 6,8,9
 10,11,12
 PLAN REVIEW BY HAROLD MOSER
 (561)805-7732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-10 Cont ID  
Sent By hmoser Date 2003-04-26 Time 11:02 Rev Time 8.00
Received By hmoser Date 2003-04-26 Time 11:02 Sent To  
Notes
2003-04-26 00:00:00PLAN DENIED
 1) CLARIFY FIRE PROTECTION BETWEEN
 FLOORS FOR REFRIGERANT LINES
 2) NO SHAFTS FOR EXHAUST FANS ON PLANS
 FOR MODEL A & B
 3) NEED MANUFACTURES INSTALLATION
 TNSTRUCTION FOR DRYERS AND BUSTER
 FANS
 4) SHOW LOCATION OF CONDENSATE LINE FOR
 W.A/C 1,2,3 PAGE M 2.8
 5) FRESH AIR CAN'TCOME FROM GARAGE OR
 OTHER CONDITION SPACE.W.A/C 1,2,3
 6) NEED TO HAVE A MEETING ON SMOKE
 CONTROL WITH MECHANICAL & FIRE
 PLAN REVIEW BY HAROLD MOSRE
 (561)805-6732

Review Stop P PLUMBING
Rev No 32 Status P Date 2007-03-17 Cont ID  
Sent By kstevens Date 2007-03-17 Time 07:52 Rev Time 0.00
Received By kstevens Date 2007-03-17 Time 07:52 Sent To  
Notes
2007-03-17 07:58:18AS-BUILTS STAMPED AND RETURNED TO CONTRACTOR. SHTS
 P-2.3, P-2.10, P-4.3, P-4.4, P-4.6, P-4.7, P-4.9,
 P-4.10, P-4.13 THRU P-4.18, P-5.1 THRU P-5.3, P-5.3.1,
 P-5.3.2, P-5.4. THE FILE PLANS WERE NOT ON FILE AT THIS
 TIME. NO PLANS TO COMPARE TO.

Review Stop P PLUMBING
Rev No 31 Status F Date 2006-11-27 Cont ID  
Sent By kstevens Date 2006-11-27 Time 07:58 Rev Time 0.00
Received By kstevens Date 2006-11-25 Time 23:38 Sent To  
Notes
2006-11-25 23:42:59REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P-2.3 AAV NOT APPROVED WITH OUT A RELIEF VENT.
 SECTION 917.3.2.
  
 2. SHT P-2.10 REVISION 22 BY L/22 INDICATES A 4"
 TERRACE OVERFLOW STORM DRAIN (TYPICAL). NO OVERFLOW
 DRAIN FOUND. PLEASE CLARIFY. SECTION 106.1.1.
  
 3. SHT P-4.3 DETAILS 4 & 6. UR-1 & UR-4 GT NOT VENTED.
 SECTION 901.2.1.
  
 4. SHT P-4.4 DETAILS 4 & 6. UR-2 SHOWER IS NOT VENTED,
 AND UR-3 GT NOT VENTED. SECTION 901.2.1.
  
 5. SHT P-4.6 DETAILS 4 & 6. UR-2 & UR-4 SHOWER NOT
 VENTED. SECTION 901.2.1.
  
 6. SHT P-4.7 DETAIL 4. UR-2 W/M NOT VENTED. SECTION
 901.2.1.
  
 7. SHT P-4.9 DETAIL 6. UR-2 GT NOT VENTED. SECTION
 901.2.1.
  
 8. SHT P-4.10 DETAIL 4. UR-1 SHOWER NOT VENTED. SECTION
 901.2.1.
  
 9. SHT P-4.13 DETAIL 6. UR-1 W/M & KS NOT VENTED.
 SECTION 901.2.1.
  
 10. SHT P-4.14 DETAIL 4. W/M & KS NOT VENTED AND THE
 SHOWER IS NOT VENTED. SECTION 901.2.1.
  
 11. SHT P-4.15 DETAIL 4. W/M & KS NOT VENTED. SECTION
 901.2.1.
  
 12. SHT P-4.16 DETAILS 4 & 6. W/M & KS NOT VENTED.
 SECTION 901.2.1.
  
 13. SHT P-4.17 DETAIL 4. W/M & KS NOT VENTED, AND
 SHOWER NOT VENTED. UPPER FLOOR ALL FIXTURES NOT VENTED.
 SECTION 901.2.1.
  
 14. SHT P-4.18 DETAIL 5. KS NOT VENTED. SECTION
 901.2.1.
  
 15. SHT P-5.1 THRU P-5.3, P-5.3.1, P-5.3.2 VENT STACK
 SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK AT OR
 BELOW THE LOWEST BRANCH LINE. SECTION 903.4.
  
 P-5.4 CONST. NOTES #4 BLACK IRON PIPE IS NOT APPROVED
 FOR WATER DISTRIBUTION. TABLE 605.5.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 30 Status P Date 2006-11-25 Cont ID  
Sent By kstevens Date 2006-11-25 Time 23:34 Rev Time 0.00
Received By kstevens Date 2006-11-25 Time 23:34 Sent To  
Notes
2006-11-25 23:38:33REVISION FINAL AS BUILTS. THE FOLLOWING SHEETS ARE
 APPROVED.
 P-0.1, P-1.2, P-1.3, P-2.1, P-2.2, P-2.4 THRU P-2.9,
 P-2.11 THRU P-2.28, P-4.1, P-4.2, P-4.5, P-4.8, P-4.11,
 P-4.12, P-5.5, P-5.6, P-6.1 & P-7.1

Review Stop P PLUMBING
Rev No 29 Status P Date 2006-04-06 Cont ID  
Sent By kstevens Date 2006-01-03 Time 15:20 Rev Time 0.00
Received By kstevens Date 2005-12-29 Time 16:58 Sent To  
Notes
2006-04-06 00:00:00REVISION OK AS BUILTS
  
 SHTS P-1.2, P-1.3, P-2.1, P-2.2, P-2.4
 THRU P-2.12, P-2.25, P-4.10, P-4.14 THRU
 P-4.18, P-4.1, P-4.2, P-4.4, P-5.5,
 P-5.6, P-6.1

Review Stop P PLUMBING
Rev No 28 Status F Date 2005-08-04 Cont ID  
Sent By kstevens Date 2005-08-04 Time 07:54 Rev Time 7.50
Received By kstevens Date 2005-08-03 Time 18:55 Sent To  
Notes
2005-08-04 00:00:00REVISION DENIED/OK
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P-1.2 REVISIONS 1, 13, 17 NOT
 FOUND ON REVISED SHEET. MANY CHANGES TO
 SHEET NOT CLOUDED OR NUMBERED. INDICATE
 ALL REVISIONS TO SHEET BY CLOUDING AND
 NUMBERING. SECTION 104.2.1.
 2. SHT P-1.3 REVISION 1 DESCRIPTION
 UNCLEAR. REVISIONS 11 & 17 NOT FOUND.
 MANY CHANGES TO SHEET NOT CLOUDED OR
 NUMBERED. INDICATE ALL REVISIONS TO
 SHEET BY CLOUDING AND NUMBERING. SECTION
 104.2.1.
 3. SHT P-2.1 NOTE TO CONTRACTOR READS
 "GAS PIPING SHALL BE WELDED SCHEDULE 40
 BLACK STEEL". PRIOR TO ISSUING THE
 PERMIT & PLANS, THE ENGINEER INDICATED
 THAT THE GAS PIPING WILL BE SCREW PIPE
 AND NOT WELD PIPE. PLEASE CHANGE THIS ON
 THE NOTE. - ORIGINAL ISSUED SET OF PLANS
 HAD MEASURMENTS FOR EACH SECTION OF GAS
 PIPE HAND DRAWN BY THE ENGINEER. THESE
 MEASURMENTS SHALL BE ON THE REVISED
 SHEET. SOME CHANGES TO SHEET ARE NOT
 CLOUDED OR NUMBERED. INDICATE ALL
 REVISIONS TO SHEET BY CLOUDING AND
 NUMBERING. SECTION 104.2.1.
 4. SHTS P-2.9 AND P-2.10 REVISION 1 NOT
 FOUND, (P-2.9). GIVE A DISCRIPTION OF
 WHAT REVISION 20 IS FOR. LINES SHOWN DO
 NOT CONNECT TO ANY SYSTEM, NO PIPE SIZES
 SHOWN. WHAT IS THE INTENT OF THESE
 LINES? SECTION 104.2.1. SECONDARY ROOF
 DRAINS ARE NOT SHOWN FOR THIS AREA OF
 THE DECK AS REQUIRED IN SECTION 1107.
 PLEASE INDICATE THE LOCATION. SECTION
 104.2.1.
 5. SHT P-2.11 INDICATES 4" PATIO
 OVERFLOW DRAINS FOR ONE SET OF LINES
 ADJACENT TO THE MATCH LINE. IS THIS THE
 REQUIREMENT FOR ALL LINES SHOWN ON THIS
 SHEET AS REVISION 20? IS THIS THE
 REQUIREMENT FOR ALL SHEETS SHOWING THESE
 LINES? IF SO PLEASE INDICATE IN SOME WAY
 TO CLARIFY THESE COMMENTS. SECTION
 104.2.1.
 6. SHTS P-2.11, P-2.12, THESE AREAS
 REQUIRED SECONDARY ROOF DRAINS. PLEASE
 SHOW THE LOCATION OF SECONDARY ROOF
 DRAINS PER SECTION 1107.
 7. SHT P-4.1 OK
 8. SHT P-4.2 MAXIMUM 8' FROM TRAP TO
 VENT PER TABLE 906.1 - SCALES OUT TO
 ABOUT 10' ON DETAIL 1.
 9. SHT P-4.3 OK
 10. SHT P-4.4 OK
 11. SHT P-4.5 OK
 12. SHT P-4.6 OK
 13. SHT P-4.7 OK
 14. SHT P-4.8 OK
 15. SHT P-4.9 OK
 16. SHT P-4.10 MAXIMUM 8' FROM TRAP TO
 VENT PER TABLE 906.2 - SCALES OUT TO
 ABOUT 11' ON DETAIL 1. - CHANGE TO FLOOR
 PLAN SHALL BE REFLECTED BY A CHANGE TO
 THE SANT. RISER DIAGRAM. SECTION
 104.2.1.
 17. SHT P-4.11 OK
 18. SHT P-4.12 OK
 19. SHT P-4.13 REVISION 1 NOT FOUND.
 SECTION 104.2.1.
 20. SHT P-4.14 REVISION 1 NOT FOUND.
 SECTION 104.2.1.
 21. SHT P-4.15 REVISION 1 NOT FOUND.
 SECTION 104.2.1.
 22. SHT P-4.16 MAXIMUM 8' FROM TRAP TO
 VENT PER TABLE 906.2. - SCALES OUT TO
 ABOUT 11' ON DETAIL 2.
 23. SHT P-4.17 HAND DRAWN CHANGE TO
 SHEET DATED 11-19-03 HAVE NOT BEEN
 CHANGED AND ARE SHOWN AS DRAWN
 ORIGINALLY. THESE WERE CODE COMPLIANCE
 CHANGES AND SHALL BE REFLECTED ON THIS
 SHEET AS REQUIRED AT TIME PERMIT ISSUED.
 NO REVISION SHOWN CHANGING DETAILS 1 AND
 4 AT THE KITCHEN SINK FOR THE LOCATION
 OF THE AAV. SECTION 104.2.1.
 24. SHT P-4.18 OK
 ALL OK SHEETS DATE STAMPED AND RETURNED
 WITH DENIED SHEETS AND WILL NOT BE
 REQUIRED TO BE RESUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 27 Status P Date 2005-07-25 Cont ID  
Sent By jleech Date 2005-07-25 Time 10:04 Rev Time 1.50
Received By jleech Date 2005-07-25 Time 10:04 Sent To  
Notes
2005-07-25 00:00:00PLUMBING PRODUCT SUBMITALS ONLY

Review Stop P PLUMBING
Rev No 26 Status P Date 2005-06-29 Cont ID  
Sent By jleech Date 2005-06-29 Time 10:43 Rev Time 0.75
Received By jleech Date 2005-06-29 Time 10:43 Sent To  
Notes
2005-06-29 00:00:00PRODUCT SUBMITAL CHANGING KITCHEN SINK
 MANUFACTOR.

Review Stop P PLUMBING
Rev No 25 Status P Date 2005-06-21 Cont ID  
Sent By pschmitz Date 2005-06-21 Time 11:00 Rev Time 0.00
Received By pschmitz Date 2005-06-21 Time 10:59 Sent To PC
Notes
2005-06-21 00:00:00LETTER ON FILE:
 RIGHTWAY PLUMBING WORKING UNDER
 SUPERVISION OF MICKEYS PLUMBING,
 WHITING TURNER PAYING THEM DIRECTLY.

Review Stop P PLUMBING
Rev No 24 Status P Date 2005-05-28 Cont ID  
Sent By kstevens Date 2005-05-28 Time 10:00 Rev Time 0.25
Received By kstevens Date 2005-05-28 Time 10:00 Sent To  
Notes
2005-05-28 00:00:00SUBMITTAL FOR UNDERCOUNTER LAV OK

Review Stop P PLUMBING
Rev No 23 Status F Date 2005-03-23 Cont ID  
Sent By kstevens Date 2005-03-23 Time 18:00 Rev Time 15.00
Received By kstevens Date 2005-02-19 Time 11:51 Sent To  
Notes
2005-03-23 00:00:00REVISION DENIED
  
 A) THE FOLLOWING SHEETS SUBMITTED FOR
 REVISION HAVE BEEN DENIED.
 SHTS SUBMITTED ON 6/8/4 P-2.2
 SHTS SUBMITTED ON 2/7/5 P-1.2, P-1.3,
 P-2.2, P-2.6, P-5.1, P-5.3.1, P-5.3.2, &
 P-5.5
 B) THE FOLLOWING ARE THE COMMENTS FOR
 THOSE DENIED SHEETS.
 1) SHT P-1.2 8" SANT. @ 1459 DFU @
 1/16"/FT NOT APPROVED. TABLE 710.1 -
 SR32 NOT SHOWN ON BLDG. SANT. DRAIN.
 2) SHT P-1.3 10" (10830SF) INTO CATCH
 BASIN COL. LINE 12/N-O PICKS UP 4
 BALCONY DRAINS @ 1190SF. PLEASE INDICATE
 WHERE THE OTHER 9640SF ENTER THE STORM
 LINE? SECTION 104.2.1.
 3) SHT P-2.2 NOTE ON SHEET STATES: "GAS
 PIPING TO BE WELDED SCHEDULE 40 BLACK
 STEEL". PREVIOUS REVISION AND
 CONVERSATION WITH THE ENGINEER INDICATED
 THAT THE PIPING WILL BE SCREW PIPE.
 PLEASE CLARIFY. IS THIS A REVISION
 CHANGING TO WELD PIPE? SECTION 104.2.1.
 4) SHT P2.6 INDICATE THE SLOPE OF THE
 SANITARY FROM THE CLEANOUT AT COL. LINE
 10/U TO COL. LINE 10/O. MAXIMUM 1400 DFU
 FOR 8" PIPE @ 1/16"/FT. TABLE 710.1-
 STORM PIPING, 12" REQUIRED AT 25,280SF.
 MAXIMUM 18,400SF ON 10" PIPE. TABLE
 1106.3.
 5) SHT P-5.1 RISERS SR1, SR2, SR3, &
 SR5. CHANGES FAXED FROM RICHARD TAVERES
 ON MARCH 11, 2005 SHALL BE REVISED ON
 THESE RISERS. - ALSO ALL WASTE STACKS
 THAT HAVE HAD THE AIR ADMITTENCE VALVES
 REMOVED SHALL REVISE RISERS TO REMOVE
 THE RELIEF VENTS THAT WILL NOT BE
 REQUIRED. (EXAMPLE SR3, & SR4 W/M &
 KITCHEN SINK RISERS). SEC 104.2.1.
 6) SHT P-5.3.1 SR 66, SR67, SR87, SR91,
 SR92, & SR93 SHALL BE REVISED TO REFLECT
 THE CHANGES FAXED FROM R. TAVERES 3/11/5
 AND REMOVE ALL RELIEF VENTS FROM RISERS
 FOR THE W/M AND KITCHEN SINKS WHERE THE
 AAV'S HAVE BEEN REMOVED. SEC 104.2.1.
 7) SHT P-5.3.2 SR123, & SR125 REVISE
 SHEET TO REFLECT FAXED CHANGED FROM R.
 TAVERES 3/11/5 AND ALL WASTE STACKS FOR
 THE KITCHEN SINKS AND W/M THAT HAVE
 DELETED THE AAV'S. NO RELIEF VENTS
 REQUIRED. SECTION 104.2.1.
 8) SHT P-5.5 8"(1459 DFU) DOWNSTREAM OF
 SR7 SHALL BE INCREASED TO 10" OR RUN AT
 1/8"/FT SLOPE. TABLE 710.1
 9) SHT P-5.5 PIPE LENGTHS FOR GAS LINES
 TO RETAIL #1 & #2 REQUIRED. (THESE WERE
 ON THE STAMPED SET OF PLANS AT THE TIME
 THE PERMIT WAS ISSUED). SECTION 104.2.1.
 10) SHT P-5.5 6" PIPE BETWEEN SR110 &
 SR107 SHALL BE INCREASED TO 8" PIPE OR
 SLOPED AT 1/4"/FT THE ENTIRE LENGTH OF
 THE RUN. TABLE 710.1 & SEC 704.1.
 11) SHT P-5.5 8" DOWNSTREAM OF SR90
 SHALL BE INCREASED TO 10" OR ENTIRE
 LENGHT OF RUN TO BE RUN AT 1/8"/FT.
 TABLE 710.1 & 704.1.
 12) SHT P-5.5 12" PIPE (4078 DFU) TO
 CONNECTION AT SEWER TO RUN AT 1/8"/FT OR
 INCREASED TO 15" PIPE. TABLE 710.1 &
 704.1.
 C) THE REVISIONS FOR THE FOLLOWING
 SHEETS HAVE BEEN APPROVED:
 DATED 6/8/4 -SHTS P-2.3, P-2.9, P-4.1
 THRU P-4.12, P-4.18, P-5.4 & P-6.1
 DATED 2/7/5 - SHTS P-2.4, P-2.5, P-2.7,
 P-4.1 THRU P-4.12, P-4.18, P-5.2, P-5.3
 DATED 10/1/4 SHT P-5.6
 TWO COPIES OF THESE REVISIONS WITH DATE
 STAMP SHALL BE RETURNED - ONE COMPLETE
 SET OF PLANS WITH RED LINE MARKINGS WILL
 BE RETAINED FOR COMPARISON AND FILE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 22 Status P Date 2005-02-05 Cont ID  
Sent By pschmitz Date 2005-02-05 Time 09:24 Rev Time 0.00
Received By pschmitz Date 2005-02-05 Time 09:25 Sent To PC
Notes
2005-02-05 00:00:00DOMESTIC WATER PUMPS, SUBMITTAL.

Review Stop P PLUMBING
Rev No 21 Status P Date 2005-02-05 Cont ID  
Sent By pschmitz Date 2005-02-05 Time 07:05 Rev Time 0.00
Received By pschmitz Date 2005-02-05 Time 07:04 Sent To PC
Notes
2005-02-05 00:00:00HALF BATH FAUCET SUBMITALS

Review Stop P PLUMBING
Rev No 20 Status F Date 2004-12-27 Cont ID  
Sent By kstevens Date 2004-12-27 Time 18:09 Rev Time 0.33
Received By kstevens Date 2004-12-27 Time 18:09 Sent To  
Notes
2004-12-27 00:00:00SUBMITTAL DENIED FOR PROPOSED PAN FOR
 ELECTRIC ROOM/VAULT. MORE INFORMATION IS
 REQUIRED. PLEASE INDICATE SIZE AND USE
 OF PIPE PAN IS MADE FOR. PLEASE SHOW ALL
 MEASUREMENTS FOR PAN. LENGTH, WIDTH,
 HEIGHT. DRAIN CAN NOT CAUSE A NUISANCE
 BY DRAINING INTO A STAIRWAY OR WALKWAY.
  
 SUBMITTAL DENIED FOR TRENCH DRAINS.
 PLEASE SUBMIT MORE INFORMATION FROM THE
 MANUF. SHOWING APPROVAL AND OR STANDARDS
 WHICH THE TRENCH DRAINS MEET. LOBBY
 TRENCH DRAINS DO NOT INDICATE WHO MANUF.
 THE DRAINS AND IT SEEMS LIKE THE
 SPECIFICATIONS ARE GENERAL
 SPECIFICATIONS THAT ARE REQUIRED TO BE
 MET, BUT DOES NOT INDICATE THAT THE
 TRENCH DRAINS ARE MEETING THE
 STANDARDS.
 THE TRENCH DRAINS FOR THE POOL AREA DO
 NOT SEEM TO BE COMPLETE. ONE PAGE STATES
 MATERALS AND STANDARDS, BUT NO STANDARDS
 ARE REFERED TO.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 19 Status P Date 2004-12-27 Cont ID  
Sent By kstevens Date 2004-12-27 Time 18:07 Rev Time 0.50
Received By kstevens Date 2004-12-27 Time 18:06 Sent To  
Notes
2004-12-27 00:00:00SUBMITTAL OK FOR INSULATION: TYPE A
 JOHNS MANVILLE MICRO LOK & ARMAFLEX

Review Stop P PLUMBING
Rev No 18 Status P Date 2004-11-27 Cont ID  
Sent By kstevens Date 2004-11-27 Time 13:32 Rev Time 0.45
Received By kstevens Date 2004-11-27 Time 13:32 Sent To E
Notes
2004-11-27 00:00:00SUBMITTAL FOR THE MISC. PLUMBING - WATER
 HAMMER ARRESTORS, TRAP PRIMERS, & VACUUM
 BREAKERS OK
 SUBMITTAL FOR THE STEAM UNIT OK
 SUBMITTAL FOR THE 1/2 BATH FAUCET NOT
 APPROVED. NO APPROVAL OR STANDARD
 MANUFACTURED TO SHOWN ON SUBMITTAL
 KSTEVENS

Review Stop P PLUMBING
Rev No 17 Status F Date 2004-11-06 Cont ID  
Sent By kstevens Date 2004-11-06 Time 08:41 Rev Time 7.00
Received By kstevens Date 2004-11-06 Time 08:40 Sent To  
Notes
2004-11-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
  
 1) SHT P-1.2 UNABLE TO LOCATE REVISION
 NUMBER ONE. MANY CHANGES ON PLANS WITH
 NO CLOUDS OR REVISION NUMBERS - CLOUD
 AND NUMBER ALL REVISIONS SUBMITTED FOR
 REVIEW. SECTION 104.2.1
 2) SHT P-1.3 10" (10,830 INDICATE SF FOR
 ALL PIPING UPSTREAM OF 10" BETWEEN COLS.
 J & S AT COL. 14. - NO REVISION NUMBER
 FOR CLOUD AT COLS. 1.1 THRU 7.1 BETWEEN
 COLS. T.1 & U.4. SHOW REVISION NUMBER.
 SECTION 104.2.1
 3) SHT P2.2 NOTE TO CONTRACTOR: ENGINEER
 INDICATED THAT GAS PIPING WAS TO BE
 SCREW PIPING. NOTE STATES WELDED PIPE.
 PLEASE CLARIFY. SECTION 104.2.1
 4) REMOVE ALL SHEETS NOT PART OF THE
 REVISION. DO NOT SUBMIT VOIDED SHEETS.
 SECTION 1014.2.1.3
 5) SHT P-2.4 INDICATE WHAT BLDG DEPT
 COMMENTS GENERATED REVISIONS 1 & 13.
 REVISION 11 & 12 WERE NOT FOUND.
 ORIGNIAL PERMIT STAMPED SET OF PLANS ALL
 READY HAS REVISIONS 1 & 13. PLEASE
 CLARIFY. SECTION 104.2.1
 6) SHT P-2.5 DOWNSTREAM OF SR/46 SHOWS
 202 DFU, 4' PIPE, THEN SR/48 ADDS 33 DFU
 FOR 193 DFU. PLEASE CLAARIFY. DOWNSTREAM
 OF SR/49 TOTAL IS 277 (193 & 44). PLEASE
 CLARIFY. PLEASE RECHECK ALL DFU'S IN THE
 SYSTEM. - PREVIOUS REVISIONS 11 & 13 ON
 THE PERMIT STAMPED SET OF PLANS. PLEASE
 CLARIFY. SECTION 104.2.1
 7) SHT P-2.6 SUBMIT BLDG DEPT COMMENTS
 THAT RESULTED IN REVISIONS 1 & 13. THESE
 NUMBERS WERE ON STAMPED SET OF PLANS.
 PLEASE CLARIFY. - THERE ARE MORE
 REVISIONS TO THE STAMPED SET OF PLANS
 THAT ARE NOT CLOUDED OR NUMBERED.
 SECTION 104.2.1
 8) SHTS P-4.4 & P-5.1 RISER UR-3 TUB NOT
 VENTED ON THE RISER OR ON THE FLOOR
 PLAN
 SECTIONS 104.2.1/901.2.1
 9) SHT P-5.2 VENTING CHANGES NOT CLOUDED
 OR NUMBERED. INDICATE COMMENTS REFERRED
 TO FOR REV'S 1 & 13. RISERS DO NOT
 REFLECT THE CHANGES FROM COMMENT #11
 FROM THE PREVIOUS REVISION REVIEW. -
 THIS COMMENT FOR SHEETS P-5.3, P-5.3.2,
 ALSO. SHT 104.2.1
 10) SHT P-5.5 REVISIONS WITH NO CLOUD OR
 NUMBER ON SANT. LINE FROM SR/192 TO
 SANT
 DOWNSTREAM OF GREASE INTERCEPTOR, AND 2
 AREAS OF RISER DO NOT REFLECT FLOOR PLAN
 AT SR/128 & AT SR/6 & SR/7 (SEE SHT
 P-2.4) - 8"(1471 DFU), 12 FROM (3975
 DFU) THRU 12" (4269 DFU) SHALL BE
 MINIMUM 1/8" PER FT. SLOPE. INDICATE ON
 PLANS. SECTION 104.2.1. - SHOW LENGTH OF
 PIPE FOR GAS ISOMETRIC MISSING FROM
 STAMPED SET OF PLANS.
 11) SEE ATTACHED SHEET FROM PREVIOUS
 REVISION REVIEW. SOME COMMENTS WERE NOT
 ADDRESSED AND STILL APPLY.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 16 Status P Date 2004-10-23 Cont ID  
Sent By pschmitz Date 2004-10-23 Time 13:08 Rev Time 0.00
Received By pschmitz Date   Time   Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 15 Status P Date 2004-10-16 Cont ID  
Sent By pschmitz Date 2004-10-16 Time 07:55 Rev Time 0.60
Received By pschmitz Date   Time   Sent To  
Notes
2004-10-16 00:00:00SUBMITTAL OK
 WASHING MACHINE VALVE BOX.

Review Stop P PLUMBING
Rev No 14 Status P Date 2004-08-07 Cont ID  
Sent By pschmitz Date 2004-08-07 Time 10:05 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2004-08-07 00:00:002 SUBMITTALS, PLUMBING,B/F;TUB BOXES.

Review Stop P PLUMBING
Rev No 13 Status F Date 2004-08-07 Cont ID  
Sent By kstevens Date 2004-08-07 Time 08:03 Rev Time 10.75
Received By kstevens Date 2004-08-06 Time 18:51 Sent To  
Notes
2004-08-07 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
  
 1) THESE REVISIONS ARE SHOWING NEW REV-
 ISION NUMBERS AND THESE REVISION PLANS
 ARE NOT CHECKED FOR PREVIOUS REVISIONS
 THAT MAY OR MAY NOT HAVE BEEN OMITTED OR
 RETAINED. SECTION 104.2.1
 2) SEPARATE PERMIT REQUIRED FOR FOUNTAIN
 SHOWN ON SHEETS F1 & F2.
 3) SHT A-3-2AB MISLABELED AS A-3-2AE.
 SECTION 104.2.1
 4) SHEET AFTER A-3-4BC HAS NO SHEET NUM-
 BER AND FIXTURES HAVE BEEN DELETED. NO
 W/C OR LAV SHOWN. SECTION 104.2.1
 5) SHT A-3-4CD INDICATE DEPTH OF DRYWELL
 SECTION 104.2.1.
 6) NUMEROUS ARCHITECTURAL SHEETS HAVE
 WHITE OUT DELETING BATHROOM TYPE AND "B"
 WRITTEN IN. THIS IS NOT APPROVED. MAKE
 ALL CHANGES WITH NEW SHEETS SIGNED/SEAL-
 ED & DATED BY ARCHITECT OF RECORD. SECT-
 ION 104 104.2.1.3.
 7) SHT A-4.18 BATHROOM TYPE IS NOT SHOWN
 AS REQUIRED BY FHA DESIGN MAN. REQUIRE-
 MENT #7B
 8) SHTS P-2.4 & P-5.5 FLOOR DRAIN ADDED
 TO TRASH ROOM SHT P-2.4 IS NOT SHOWN ON
 THE BLDG. SANT. RISER DIAGRAM SHT P-5.5
 SECTION 104.2.1
 9) SHTS P-2.5, P-5.5 & P-5.6, BLDG. SANT
 RISER DIAGRAM DOES NOT REFLECT CHANGES
 IN FLOOR PLAN. ALSO RISER SR/58 IS NOT
 SHOWN ON BLDG. SANT. RISER. - BLDG.
 STORM RISER DOES NOT REFLECT CHANGES OF
 SHT P-2.5, MISSING PIPE SIZES, SQUARE
 FOOTAGE, AND LAYOUT CHANGES. SEC 104.2.1
 10) SHTS P-2.6, P-5.5 & P-5.6 RISERS DO
 NOT REFLECT CHANGES IN FLOOR PLAN. PIPE
 SIZES, SQUARE FOOTAGE, LAYOUT CHANGES.
 SECTION 104.2.1.
 11) SHTS P-4.1 THRU P-4.18 & SHTS P-5.1,
 P-5.2, P-5.3, P-5.3.1, & P-5.3.2. UNIT
 TYPES WASTE & VENT RISERS SHOW BRANCH
 LINES TO FIXTURES CONNECTING TO THE
 STACK ON THE SAME FLOOR AS THE FIXTURES.
 (WASTE STACK) - BUT RISER DIAGRAMS SHOW
 CONNECTIONS TO THE STACK ON THE FLOOR
 BELOW CREATING AN "S" TRAP NOT APPROVED
 BY SECTION SECTION 1002.3. PLEASE CLARI-
 FY. SECTION 104.2.1
 12) SHT P-5.6 SIZE PIPE FRON TRENCH
 DRAINS TO DRAINAGE STRUCTURE AND SHOW
 TOTAL SQUARE FEET. SECTION 104.2.1
 ALSO THE OTHER 3 REVISION AREAS HAVE NO
 CHANGES FROM PREVIOUS REVIEW DATED
 2-12-4.
 13) SHT P-5.5 GAS ISOMETRICS - MEASURE-
 MENTS FOR CUT SECTIONS OF PIPE WERE DE-
 LETED FROM STAMPED SET OF PLANS. THESE
 MEASUREMENTS ARE REQUIRED ON PLANS.
 SECTION 104.2.1 AND FUEL GAS CODE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 12 Status P Date 2004-07-17 Cont ID  
Sent By pschmitz Date 2004-07-17 Time 08:34 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2004-07-17 00:00:00HANGER SUBMITTAL, PVC,COPPER ETC..
 PIPES.

Review Stop P PLUMBING
Rev No 11 Status N Date 2004-06-23 Cont ID  
Sent By kstevens Date 2004-06-23 Time 16:03 Rev Time 2.00
Received By kstevens Date 2004-06-23 Time 09:33 Sent To  
Notes
2004-06-23 00:00:00MEETINGS WITH B. STAPLES, JIM WHITMER
 JIM WHITMER, DEWEY PALMER, LUIS MARTINEZ
 KATHY CORDES & REPRESENTATIVE OF BAP.

Review Stop P PLUMBING
Rev No 10 Status P Date 2004-06-08 Cont ID  
Sent By jleech Date 2004-06-08 Time 17:27 Rev Time 1.50
Received By jleech Date 2004-06-08 Time 17:27 Sent To  
Notes
2004-06-08 00:00:00PLUMBING SUBMITTALS OK.

Review Stop P PLUMBING
Rev No 9 Status F Date 2004-04-03 Cont ID  
Sent By kstevens Date 2004-04-03 Time 12:11 Rev Time 2.50
Received By kstevens Date 2004-04-03 Time 12:10 Sent To  
Notes
2004-04-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 USA9201 SERIES FORGED BRASS BALL VALVE
 NOT APPROVED. NO APPROVAL OR STANDARD
 REFERENCE SHOWN ON SHEET.
  
 NEW SHEET FOR VICTAULIC CTS COPPER
 TUBING GROOVED SYSTEM 22.01 REQUIRED.
 INFORMATION COVERED UP WHEN SHEET COPIED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 8 Status P Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-26 Time 11:37 Rev Time 1.00
Received By kstevens Date 2004-03-01 Time 09:21 Sent To  
Notes
2004-03-01 00:00:00SUBMITTAL APPROVED - STRUCTURE PENETRAT-
 IONS SEALANT (CARLISLE)

Review Stop P PLUMBING
Rev No 7 Status P Date 2004-02-23 Cont ID  
Sent By kstevens Date 2004-02-23 Time 13:07 Rev Time 1.00
Received By kstevens Date 2004-02-23 Time 13:07 Sent To  
Notes
2004-02-23 00:00:00PASSED PROVISO - FIRE PIPING TO BE CPVC
 AND VICTAULIC - NO THREAS OIL - REVISION
 OK SHTS P1.3 & P5.6

Review Stop P PLUMBING
Rev No 6 Status P Date 2004-02-23 Cont ID  
Sent By kstevens Date 2004-02-23 Time 13:05 Rev Time 0.25
Received By kstevens Date 2004-02-23 Time 13:05 Sent To  
Notes
2004-02-23 00:00:00SUBMITTAL PASSED WITH PROVISO: FIRE
 PIPING TO BE CPVC OR VICTAULIC - NO
 THREAD OIL (LETTER FROM R J KNOEDLER)

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-02-17 Cont ID  
Sent By kstevens Date 2004-02-17 Time 16:46 Rev Time 1.25
Received By kstevens Date 2004-02-17 Time 16:46 Sent To  
Notes
2004-02-17 00:00:00SUBMITTALS OK - PVC PIPE AND FITTINGS
 BASEMENT SUMP PUMP

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-11-21 Cont ID  
Sent By dpalmer Date 2004-02-12 Time 07:01 Rev Time 1.50
Received By kstevens Date 2003-11-21 Time 15:21 Sent To  
Notes
2003-11-21 00:00:00 
  
  
 SEPARATE PERMITS REQUIRED FOR: IRRIGAT-
 ION, GAS, GREASE TRAPS, & POOL

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-11-13 Cont ID  
Sent By kstevens Date 2003-11-13 Time 14:42 Rev Time 16.00
Received By kstevens Date 2003-11-13 Time 14:29 Sent To  
Notes
2003-11-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 CITY WPB CODE
  
 A) THE FOLLOWING COMMENTS FROM THE FIRST
 AND SECOND REVIEWS HAVE NOT BEEN ADD-
 RESSED OR ANSWERED SUFFICIENTLY. THE
 NUMBER OF THE COMMENT FROM THE FIRST
 REVIEW WILL BE USED FOR CLAIRITY.
 7) SHT A-401 DETAIL #1 CLEAR FLOOR SPACE
 REQUIRED FOR ALL FIXTURES PER FHA DESIGN
 MANUAL PAGE 7.43. (ALL UNITS) "THE CLEAR
 FLOOR SPACE DIMENSIONS ARE TO BE APPLIED
 OR SUPERIMPOSED OVER A PLAN DURING THE
 DESIGN PROCESS TO DETERMINE IF SPACE RE-
 QUIREMENTS AT TOILETS ARE BEING MET.
 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS.
 TOILET ROOMS SHALL COMPLY WITH 11-4.22.
 ALL UNITS SHALL HAVE A DRINKING FOUNTAIN
 PER TABLE 403.1. ALSO SEE 410.1. - THE
 TYPE OF OWNERSHIP DOES NOT DETERMINE IF
 REQUIREMENTS ARE TO BE MET, BUT RATHER
 THE OCCUPANCY OF THE UNIT THAT DETERMINE
 ACCESSIBILITY AND MINIMUM FACILITIES.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. SOME LENGTH MISSING FROM
 RISER DIAGRAM. 104.2.1
 B.SHTS P-2.1 & P-2.2 INDICATE A 2 LB.
 SYSTEM, BUT SHT P-5.5 STILL INDICATES A
 7" W/C. PLEASE CLAIRFY. 104.2.1
 22) SHT P-4.2 SANT. RISER DOES NOT REFL-
 LECT THE FLOOR PLAN AND SHOWER IS NOT
 VENTED. (H/10). 901.2.1
 23) SHT P-4.4 FLOOR PLAN TO REFLECT THE
 SANT. RISER DIAGRAM AT TUB BATH. 104.2.1
 33) SHT P-4.18 SANT RISER AND FLOOR PLAN
 THE KITCHEN SINK SHALL NOT DRAIN INTO
 THE WET VENT FOR THE BATHROOM GROUP.
 SECTION 909.1
 ---COMMENTS FROM SECOND REVIEW
 THE NUMBERS WILL REMAIN THE SAME FOR
 CLAIRITY.
 6B) SHTS P-2.1 & P-5.2 RISERS 27 THRU 41
 AT COL. LINE 8 SHOWS 300 DFU'S ON FLOOR
 PLAN, BUT 370 DFU'S ON RISER. PLEASE
 CLAIRFY. (RISER 38 NOT SHOWN ON FLOOR
 PLAN, BUT IS SHOWN ON THE SANT. RISER
 DIAGRAM). 104.2.1
 9B) SHTS P-2.3 & P-5.5, 8" SHOWS 1298
 DFU ON FLOOR PLAN BUT NOT RISER SHOWS
 1365 DFU. RISER AND FLOOR PLAN SHALL RE-
 FLECT. PLEASE CLAIRFY. 104.2.1
 10B) SHTS P-2.4 & P-5.5 RISER DOES NOT
 REFLECT THE FLOOR PLAN. BRANCH TO TOILET
 ROOMS CONNECT TO DRAIN AFTER SR128 ON
 THE FLOOR PLAN, BUT PRIOR TO SR 128 ON
 THE RISER DIAGRAM. PLSE CLAIRFY 104.2.1
 11B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS
 8" @ 9450 SF, BUT RISER SHOWS 10" @
 9450 SF. PIPE SIZES MUST CORRELATE.
 15B) SUBMIT STORM RISERS, SHOW OFFSETS,
 PIPE SIZES, SQUARE FOOOTAGE ECT. THE
 HORIZONTAL STORM DRAIN IS SHOWN BUT THE
 VERTICAL STORM RISERS ARE NOT SUBMITTED.
 104.2.1
 19B) SUBMIT CALCULATIONS FOR RWL'S LARG-
 ER THAN 8". TABLE 1106.2 ONLY ADDRESSES
 PIPE SIZE TO 8". 104.2.1 - THIS WILL BE
 REQUIRED FOR PERMIT.
 25B) SHT P-4.3 TUB NOT VENTED, B/11 AND
 ALL AAV'S REQUIRES ACCESS, AND VENTILA-
 TION. 917.5
 26B) SHT P-4.5 TUB NOT VENTED AND RISER
 DOES NOT REFLECT THE FLOOR PLAN. UR-1
 HORIZONTAL DRY VENT NOT ALLOWED. 905.3
 THIS VENT IS NOT REQUIRED. UR-3. 104.2.1
 AAV REQUIRES ACCESS AND VENTILATION.
 917.5. "S" TRAP ON LAV (NO VENT) 1002.3
 (5) - SEE RED LINES
 27B) SHT P-4.6 SHOWER NOT VENTED, ACCESS
 & VENTILATION REQUIRED FOR AAV, NO HORI-
 ZONTAL DRY VENTS NOT ALLOWED.
 28B) SHT P-4.7 ACCESS AND VENTILATION
 REQUIRED FOR AAV, RISER DOES NOT REFLECT
 THE FLOOR PLAN.
 29B) SHT P-4.9 ACCESS AND VENTILATION
 REQUIRED FOR AAV'S. 917.5
 30B) SHT P-4.10 SHOWER NOT VENTED L-05
 901.2.1
 31B) ACCESS AND VENTILATION REQUIRED FOR
 AAV'S 917.5
 32B) SHT P-4.13 TUB NOT VENTED U-1
 33B) SHT P-4.14 SHOW VENT ON FLOOR PLAN
 104.2.1
 34B) SHT P-4.15 SHOWER NOT VENTED, AND
 VENT NOT REQUIRED ON TUB.
 35B) SHT P-4.17 ACCESS AND VENTILATION
 REQUIRED FOR AAV. HORIZONTAL DRY VENT
 NOT ALLOWER FOR SHOWER. 905.3
 36B) THE RELIEF VENTS REQUIRED BY SEC
 917.3.2 FOR FLOORS 2, 3, & R SHALL BE
 TIED INTO THE BRANCH LINES FOR THESE
 FLOORS. THE VENT LINES SHALL BE SHOWN
 ON THE RISERS. SEE EXAMPLE ON SR/20
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-09-13 Cont ID  
Sent By csiegber Date 2003-11-10 Time 15:00 Rev Time 27.00
Received By kstevens Date 2003-08-20 Time 18:26 Sent To  
Notes
2003-09-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 CITY WPB CODE
  
 A) FOLLOWING COMMENTS FROM THE FIRST RE-
 VIEW HAVE NOT BEEN ADDRESSED OR ANSWERED
 SUFFICIENTLY. THE NUMBER OF THE COMMENT
 FROM THE FIRST REVIEW WILL BE USED FOR
 CLAIRTY.
 7) SHT A-4.01 DETAIL #1 CLEAR FLOOR
 SPACE REQUIRED FOR ALL FIXTURES PER FHA-
 DESIGN MANUAL PAGE 7.43 (ALL UNITS).
 12) SHT A-2.11 SCUPPER DETAIL, SUBMIT
 INFO. FOR SCUPPERS SHOW ALL MEASUREMENTS
 & INDICATE SLOPEAT THE BOTTOM OF THE
 TRENCH IF ANY. SHOW LONGEST TRENCH MEAS-
 UREMENT. SECTION 104.2.1
 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS.
 TOILET ROOMS SHALL COMPLY WITH 11-4.22.
 ALL UNITS SHALL HAVE A DRINKING FOUNTAIN
 PER TABLE 403.1. (ALSO SEE 410.1)
 14) SUBMIT WORKSHEET FROM R. COMPO FOR
 GREASE INTERCEPTOR. ORD. 2938-96
 16) SHTS P2.1/P2.2 SEPARATE GAS PERMIT
 REQUIRED. THE FOLLOWING INFORMATION IS
 REQUIRED PRIOR TO PERMIT ISSUANCE.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - RISER NOT SUBMITTED IN
 ISOMETRIC FORM & ALL CUT SECTIONS OF
 PIPE LENGTHS NOT SHOWN.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 - INDICATE IF PIPE WILL BE WELDED OR
 SCREW PIPE. IF WILDED PIPE, WELDERS
 CERTIFICATE, AND PICTURE I.D. WILL BE
 REQUIRED WITH THE WELDING PROCEDURE BE-
 FOR STARTING.
 PLANS INDICATE 7" W.C.TABLES IN FBC-2001
 FUEL GAS SHOW MINIMUM GAS PRESSURE AT
 14" W.C. PLEASE VERIFY THE DELIVERY
 PRESSURE WITH GAS PROVIDER. PROVIDE
 TABEL USED FOR SIZING GAS PIPE. SUGGEST
 A 2 LB SYSTEM BE USED AS THE PIPE SIZE
 IS NOT SUFFICIENT FOR 1/2 LB PRESSURE.
 21) SHT P-4.1 KITCHEN SINK SHALL NOT
 DRAIN INTO THE WET VENT OF THE BATHROOM
 GROUP. SECTION 909.1.
 22) SHT P-4.2 SANT. RISER DOES NOT RE-
 FLECT THE FLOOR PLAN AT TUB & SHOWER.
 SHOWER NOT VENTED. SECTION 901.2.1
 23) SHT P-4.4 SANT. RISER DOES NOT RE-
 FLECT THE FLOOR PLAN. TUB NOT VENTED,
 SHOWER NOT VENTED. 104.2.1 - 901.2.1
 31) SHTS FOR ALL UNITS, WATER HAMMER
 ARRESTORS REQUIRED AT ICE MAKER LINE.
 SECTION 604.9
 33) SHT P-4.18 SANT. RISER KITCHEN SINK
 SHALL NOT DRAIN INTO WET VENT FOR BATH-
 ROOM GROUP. SECTION 909.1
 34) SHT P-5.1 RISER SR4 N/203/19 DFU NOT
 ADDED TO TOTAL FOR RISER.
 37) SHT P-5.4 DETAIL #1 RPZ BACKFLOW TO
 BE MAX. 4' ABOVE FLOOR FOR SERVICING AND
 TESTING.
 40) SHT P-5.5 INDICATES DETAIL FOR
 GREASE TRAP ON SHT P-7.1, BUT NO DETAIL
 FOUND. PROVIDE DETAIL.
 42) SHT P-5.5 DFU'S FROM GREASE TRAP NOT
 ADDED TO SYSTEM. RECALCULATE DFU'S. SHOW
 SLOPE OF PIPE ON RISER DIAGRAM.
 49) SHT P-5.6 PLEASE INDICATE MATERIAL
 FOR RELIEF VALVE & EMERGENCY PAN DRAIN
 RISERS. RESPONSE ON DETAIL #4 CALLS FOR
 CAST IRON DRAIN FOR HEATER PANS. PLEASE
 NOTE THAT MINIMUM SIZE FOR CAST IRON IS
 2". PLEASE CLAIRFY.
 52) SHT P-7.1 AIR CHAMBER DETAIL. AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DELETE
 DETAIL.
 ********NEW COMMENTS*********
 1B) SHT P-1.2 COL. LINE 2/F NO CHANGE
 NOTED. CLO. LINE 2/K REVISION NOT CLOUD-
 ED. 104.2.1
 2B) SHT P-1.2 COL. LINE 11/R.2 SQUARE
 FOOTAGE DIFFERENT FROM RISER. PLEASE
 CLAIRFY 104.2.1
 3B) SHT P-1.2 15" STORM (58,220 SF) IN-
 DICATE SLOPE OF PIPE FOR HORIZONTAL OFF-
 SET. (SHT P1.3 INDICATES 54,570 SF,
 RISER SHT P5.6 INDICATES 63,464 SF BUT
 ADDS UP TO 64,689 SF. PLEAS CLAIRFY.
 PLEASE CHECK ALL SQUARE FOOTAGE FOR
 STORM PIPING. FLOOR PLAN AND RISERS FOR
 NOT REFLECT.104.2.1
 4B) SHTS P-1.3 & P-5.5 FLOOR PLAN & SANT
 RISER DIAGRAM. LOCKING VALVE FOR FOUNT-
 AIN POOL DRAINAGE NOT SHOWN ON FLOOR
 PLAN. 104.2.1
 5B) SHTS P=2.1 & P-5.6 6" RWL ON FLOOR
 PLAN SHOWS 6,150 SF - RISER SHOWS 6,750
 SF. PLEASE CLAIRFY.
 6B) SHTS P-2.1 & P-5.2 RISERS 27 THRU 41
 AT COL. LINE 8 SHOW 300 DFU'S ON FLOOR
 PLAN, BUT 370 DFU'S ON RISER. PLEASE
 CLAIRFY. 104.2.1
 7B) SHT P-2.2 POOL DRAIN LINE SHALL
 CONNECT TO STORM.
 8B) SHT P-2.2 SHUT OFF VALVE REQUIRED
 FOR BLDG WATER SERVICE. 606.1(2)
 9B) SHTS P-2.3 & P-5.5 8" SHOWS 1298 DFU
 ON FLOOR PLAN, BUT 1321 DFU ON RISER.
 PLEASE CLAIRFY. 104.2.1
 10B) SHTS P-2.4 & P-5.5 RISER DOES NOT
 REFLECT THE FLOOR PLAN. BRANCH TO TOILET
 ROOMS CONNECT TO DRAIN AFTER SR128 ON
 THE FLOOR PLAN, BUT PRIOR TO SR128 ON
 RISER DIAGRAM. PLEASE CLAIRFY. 104.2.1
 11B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS
 8" @ 10,050 SF, BUT RISER SHOWS 10" @
 9,450 SF. PLEASE CLAIRFY. 104.2.1
 12B) SHTS P-2.4 & P-5.6 FLOOR PLAN SHOWS
 1-1/2" CONDENSATE. NOT SHOWN ON RISER.
 PLEASE CLAIRFY. 104.2.1
 13B) SHTS P-2.5 & P-5.6 FLOOR PLAN SF &
 RISER SF DO NOT REFLECT.104.2.1
 14B) SHT P-2/5 SHOWS 4" RWL SHOWS 3,300
 SF UP, BUT 6" RWL DOWN AT 2,7OO SF.
 PLEASE CLAIRFY. 6" REQUIRED ON HORIZON-
 TAL OFFSETS. TABLE 1106.3 - 104.2.1
 15B) SUBMIT STORM RISERS. SHOW OFFSETS,
 PIPE SIZES, SQUARE FOOTAGE ECT.
 16B) SHT P-2.5 BATHROOM GROUPS SR48 & 49
 NOT SHOWN ON FLOOR PLAN. 104.2.1
 17B) SHT P-2.5 SR 28 NOT SHOWN ON FLOOR
 PLAN. 104.2.1
 18B) SHTS P-2.6 & P-5.6 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. POOL AREA
 TRENCH DRAINS NOT SHOWN. 104.2.1
 19B) SUBMIT CALCULATION FOR RWLS LARGER
 THAN 8". TABLE 1106.2 ONLY ADDRESSES
 PIPE SIZE TO 8" 104.2.1.2
 20B) SHTS P-2.6 & P-5.3 FLOOR PLAN SHOWS
 SR72 WITH 42 DFU'S AND RISER SHOWS 14
 DFU'S. PLEASE CLAIRFY. 104.2.1
 21B) SHT P-2.6 ACCUMULATIVE DFU'S APPEAR
 TO BE INCORRECT AFTER SR73. PLEASE RE-
 CALCULATE. 104.2.1
 22B) SHT P-2.8 COL LINE 3 BETWEEN COL'S
 C & D, A 6" RWL IN 8" CMU WALL NEXT TO
 STAIRWAY. PLEASE INDICATE HOW 2 HOUR
 FIRE RATING WILL BE MAINTAINED. S-704
 23B) SHT P-2.8 SIZE SANT PIPE FOR SR9,
 SR10, & SR11. TABLE 710.1(2)
 24B) SHTS P-2.9, P-2.10, P-2.11, & P-2.
 12, SANITARY RISER DIAGRAM LOCATIONS NOT
 SHOWN. 104.2.1
 25B) SHT P-4.3 TUB NOT E/03 & TUB AND
 LAV NOT VENTED B/11 901.2.1
 26B) SHT P-4.5 FIXTURES NOT VENTED AND
 RISER DOES NOT REFLECT FLOOR PLAN.
 901.2.1 - 104.2.1
 27B) SHT P-4.6 TUB NOT VENTED AND DOES
 NOT REFLECT FLOOR PLAN. 901.2.1/104.2.1.
 28B) SHT P-4.7 TUB NOT VENTED. W/M SHALL
 NOT DRAIN THROUGH BATHROOM FIXTURES.
 901.2.1/909.1
 29B) SHT P-4.9 TUB NOT VENTED. A-13 SEC.
 901.2.1
 30B) SHT P-4.10 SHOWER NOT VENTED. L-05
 901.2.1
 31B) SHT P-4.12 TUB NOT VENTED. A-17
 901.2.1
 32B) SHT P-4.13 TUB NOT VENTED. U-1
 901.2.1 - KITCHEN SINK & WASH MACHINE
 SHALL NOT DRAIN THROUGH BATHROOM GROUP
 R1(S). 909.1
 33B) SHT P-4.14 SHOWER NOT VENTED. S1(S)
 901.2.1
 34B) SHT P-4.15 TUB NOT VENTED. T1
 901.2.1
 35B) SHT P-4.17 SHOWER NOT VENTED. S1(N)
 901.2.1. CLAIRFY #10 AND TWO LINES ON
 RISER DIAGRAM UPPER LEVEL. AN AAV IS
 SHOWN UNDER SINK WITH ANOTHER IN WALL??
 S1(N)
 36B) ALL SANITARY RISER DIAGRAMS. THE
 HORIZONTAL BRANCH DRAIN SHALL COMFORM
 TO SECTION 917.3.1 OR 917.3.2. SECTION
 917.3. THE HORIZONTAL BRANCH SHALL BE
 PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK, OR A STACK VENT
 OR EXTEND OUTDOORS TO THE OPEN AIR.
 37B) ONE SET OF MECHANICAL PLANS HAS RED
 LINE INFORMATION. THIS MAY ASSIST IN
 EXPLAINING LOCATION & COMMENTS. RETURN
 WITH COMMENT RESPONSE WHEN RESUBMITTING
 FOR PLAN REVIEW TO HELP EXPEDITE REVIEW.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-10 Cont ID  
Sent By kstevens Date 2003-04-09 Time 17:55 Rev Time 23.50
Received By kstevens Date 2003-04-07 Time 18:46 Sent To  
Notes
2003-04-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 CITY WPB CODE
  
 1) SHT C2.1 CONTROL STRUCTURE, SHOWS 15"
 INLET FROM RAIN WATER LEADERS, BUT NO
 INLET FROM EXFILTRATION TRENCH. PLEASE
 CLAIRFY.
 2) SHT C2.1 DRAINAGE STRUCTURE, SHOWS
 24" FROM CONTROL STRUCTURE & 18" TO THE
 TRENCH. PLEASE CLAIRFY.
 3) SHT C-2.0 EMERGNECY OVERFLOW FROM THE
 CONTROL STRUCTURE DRAINS BY SUMP VAULT.
 THE SUMP PUMP THEN DRAINS TO CONTROL
 STRUCTURE. PLEASE CLAIRFY
 4) SHT L-5.1 RAIN SENSOR REQUIRED. ALSO
 SEPARATE IRRIGATION PERMIT REQUIRED.
 5) SHT L-5.4 RPZ BACKFLOWS ARE REQUIRED
 FOR EXTERNAL IRRIGATION.
 6) SHT F1 BACKWASH SHALL DRAIN TO SANT.
 7) SHT A-4.01 DETAIL #1 CLEAR FLOOR
 SPACE REQUIRED FOR ALL FIXTURES PER FHA-
 DESIGN MANUAL PAGE 7.43 (ALL UNITS)
 8) SHT A-4.01 DETAIL #4 LAV ELEVATION,
 MAXIMUM 34" TO LAV PER FHA DESIGN MANUAL
 PAGE 7.52 (ALL UNITS)
 9) SHT A-4.01 DETAIL #5 TUB BACKING, PER
 FHA DESIGN MANUAL PAGE 6.9 (ALL UNITS)
 10) SHT A-4.01 DETAIL #6, SHOW SIDE RE-
 INFORCEMENT PER FHA DESIGN MANUAL PAGE
 6.5 (ALL UNITS)
 11) SHT A-4.01 DETAILS REFER TO SHT A-XX
 BUT SHT A-XX NOT FOUND. PLEASE CLAIRFY.
 12) SHT A-10.02 DETAIL #2 SCUPPER, SHOW
 WIDTH & HEIGHT. SCUPPER SHALL BE INSTALL
 ED PER SECTION 1503.4.2. SHOW HEIGHT
 TO FLOW LINE OFF ROOF
 13) PLEASE IDENTIFY ALL WORK/LIVE LOFTS.
 TOILET ROOMS SHALL COMPLY WITH 11-4.22.
 ALL UNITS SHALL HAVE A DRINKING FOUNTAIN
 PER TABLE 403.1. (ALSO SEE 410.1)
 14) SHT P-1.2 GREASE TRAPS TO BE SIZED
 BY RODNEY COMPO, ENVIRONMENTAL COMPLIAN-
 CE. UTILITY ORD #2938-96. PLEASE CONTACT
 @ (561) 837-4074.
 15) SHT P-1.3 15" STORM @ 53,900 SQ. FT.
 SHALL BE RUN AT A MINIMUM OF 1/4" PER FT
 PLEASE INDICATE ON PLANS.
 16) SHTS P2.1/P2.2 SEPARAGE GAS PERMIT
 REQUIRED. THE FOLLOWING INFORMATION IS
 REQUIRED PRIOR TO PERMIT ISSUANCE.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). (REQUIRED AT BUILDOUT)
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. (REQD AT BUILDOUT)
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506. (REQD. AT BUILD0UT)
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2. (IF LP)
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H). (IF LP)
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (REQD AT
 BUILDOUT)
 PLEASE PROVIDE THE TABLE THAT WAS USED
 TO SIZE PIPE FOR 8500 CFH @ 500 FEET.
 PLEASE INDICATE WHO PROVIDES TABLE REF-
 ERENCED. (TABLE NEEDS TO BE APPROVED)
 ---SUGGESTION--- A 2LB SYSTEM OR A 5LB
 SYSTEM WILL ENABLE THE SYSTEM TO USE A
 SMALLER SIZE SUPPLY PIPE--------
 17) SHT P-2.2 6" RPZ BACKFLOW PREVENTER
 SHALL BE LOCATED A MAXIMUM OF 4 FT ABOVE
 THE FLOOR FOR SERVICING AND TESTING.
 18) SHT P-2.4 CONDENSATE IS NOT ALLOWED
 TO DRAIN INTO SANITARY SYSTEM. CITY CODE
 90-125(B)(5).
 19) SHTS P-2.25/.26/.26/.28 & A-2.11
 SUBMIT CALCULATIONS FOR PRIMARY AND SEC-
 ONDARY ROOF DRAINS. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS. SHOW
 ALL AREA OF ROOFS THAT DRAIN DOWN ON THE
 ROOF FROM ABOVE. SHOW LOCATION OF ALL
 SECONDARY OVERFLOW DRAINS OR SCUPPERS.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 20) SHT P-2.8 CONDENSATE SHALL RUN SEP-
 ARATELY OUT OF BLDG OR TO CATCH BASINS.
 PLEASE PROVIDE SEPARATE CONDENSATE IS0-
 METRIC RISER. SHOW BLDG COND. DRAIN AND
 ALL RISERS AND INDICATE LOAD AS IT ACCU-
 MULATES.
 21) SHT P-4.1 SANITARY RISER DOES NOT
 REFLECT THE FLOOR PLAN. KITCHEN SINK
 SHALL NOT DRAIN INTO THE WET VENT OF THE
 BATHROOM GROUP. 909.1 - THE KITCHEN SINK
 SHALL DRAIN DOWNSTREAM OF THE BATHROOM
 GROUP. - TUB NEEDS TRAP.
 22) SHT P-4.2 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN. H/10 & J/12
 23) SHT P-4.4 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN. C-21
 24) SHT P-4.6 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN. P/36
 25) SHT P-4.7 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN. N/03
 26) SHT P-4.7 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN. F/28 - KITCHEN SINK
 SHALL NOT DRAIN THROUGH WET VENTED BATH-
 ROOM GROUP 909.1. KIT. SINK SHALL DRAIN
 DOWNSTREAM OF BATHROOM GROUP.
 27) SHT P-4.9 SANT RISER DOES NOT RE-
 FLECT FLOOR PLAN.WASH MACHINE & KIT.
 SINK SHALL DRAIN DOWNSTREAM OF BATHROOM
 GROUP. 909.1D/28 - D/36
 28) SHT P-4.9 SANT. RISER DOES NOT RE-
 FLECT FLOOR PLAN A13. NO SANT LINE TO
 WATER CLOSET ON FLOOR PLAN.
 29) SHT P-4.12 NO SANITARY LINE TO WATER
 CLOSET ON LOWER FLOOR PLAN.
 30) SHT P-4.16 WATER RISER DOES NOT RE-
 FLECT FLOOR PLAN.
 31) SHTS FOR ALL UNITS, WATER HAMMER
 ARRESTOR REQUIRED AT ICE MAKER LINE IN
 ALL UNITS. PLEASE REVISE.
 32) SHT P-4.17 SANT. RISER DOES NOT RE-
 FLECT THE FLOOR PLAN.
 33) SHT P-4.18 SANT. RISER 909.1 KITCHEN
 SINK SHALL NOT DRAIN INTO WET VENT FOR
 BATHROOM GROUP.
 34) SHT P-5.1 RISER SR4 N/203/(19) DFU
 NOT ADDED TO TOTAL FOR RISER.
 35) SHT P-5.3 RISER SR15 SHOWS 123 DFU,
 ACTUALLY 133 DFU.
 36) SHT P-5.4 DETAIL #5 PLEASE SHOW SIZE
 OF SUPPLY TO URNAL.
 37) SHT P-5.4 DETAIL #1 RPZ BACKFLOW TO
 BE MAX. 4' ABOVE FLOOR FOR SERVICING AND
 TESTING.
 38) SHT P-5.4 DETAIL #1 RPZ BACKFLOW RE-
 QUIRED FOR FOUNTAIN WATER SERVICE.
 39) SHT P-5.5 RISERS #'S 39, 40, 41, 42,
 43, 44, & 45 NOT FOUND. PLEASE SUBMIT
 INFORMATION ON THESE RISERS.
 40) SHT P-5.5 INDICATES DETAIL FOR
 GREASE TRAP ON SHT P-7.1, BUT NO DETAIL
 WAS FOUND. SEE ATTACHED SHEET FOR APP-
 ROVED GREASE TRAP DETAIL. SUBMIT ON PLAN
 NOTE 2-WAY CLEAN OUTS REQD. ENTERING &
 EXITING EACH GREASE TRAP.
 41) SHT P-5.5 CORRECT ALL AREAS WHERE
 RED LINED. SHOW ALL PIPE SIZES AND DFU
 NOT SHOWN.
 42) SHT P-5.5 DFU'S FROM GREASE TRAP NOT
 ADDED TO SYSTEM. RECALCULATE DFU'S. SHOW
 SLOPE OF PIPE ON RISER DIAGRAM.
 43) SHT P-5.6 CONDENSATE RISER SHALL NOT
 TERMINATE IN A/C ROOM IF USED AS A PLEN-
 UM.
 44) SHT P-5.6 6" @ 6150 SQ FT NOT APP-
 ROVED. MINIMUM OF 1/4" PER FT OR LARGER
 SIZE PIPE. PLEASE SHOW SLOPE OR INCREASE
 PIPE SIZE.
 45) SHT P-5.6 5" REQUIRED @ 1950 SQ FT.
 46) SHT P-5.6 SHOW AREA DRAINED AT 4"
 TRENCH DRAINS ON RISER DIAGRAM.
 47) SHT P-5.6 SHOW PIPE SIZE FOR ENTRY
 TRENCH DRAINS ON RISER.
 48) SHT P-5.6 STORM ISOMETRIC, 15" PIPE
 DRAINING 61,089 SQ FT SHALL BE MINIMUM
 OF 1/4" PER FOOT. PLEASE INDICATE ON
 RISER.
 49) SHT P-5.6 PLEASE INDICATE MATERIAL
 FOR RELIEF VALVE & EMERGENGY PAN DRAIN
 RISERS. (PVC NOT APPROVED)
 50) SHT P-6.1 CONDENSATE SHALL RUN SEP-
 ARETELY. (SEE COMMENT #20)
 51) SHT P-6.1 PLUMBING FIXTURE SCHEDULE,
 HANDICAP WATER CLOSET TO BE 17" TO 19"
 TO SEAT. 11-4.16.3
 52) SHT P-6.1 PLUMBING FIXTURE SCHEDULE,
 6" ROOF DRAIN, VENT NOT REQUIRED. TRAP
 NOT APPROVED.
 SHT P7.1 AIR CHAMBER DETAIL, AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE DE-
 TAIL.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 8 Status P Date 2006-11-27 Cont ID  
Sent By astelly Date 2006-11-27 Time 15:21 Rev Time 0.00
Received By astelly Date 2006-11-27 Time 15:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 7 Status P Date 2005-01-20 Cont ID  
Sent By aaponte Date 2005-01-20 Time 16:29 Rev Time 0.00
Received By aaponte Date 2005-01-20 Time 16:29 Sent To  
Notes
2005-01-20 00:00:00PROVISO: ARCHITECTURAL DRAWINGS SHALL BE
 MODIFIED REFLECTING CHANGES APPROVED ON
 C-1.1 AND L-2.3.

Review Stop Z ZONING
Rev No 6 Status F Date 2004-12-01 Cont ID  
Sent By jroach Date 2004-12-01 Time 17:06 Rev Time 0.00
Received By jroach Date 2004-12-01 Time 17:06 Sent To  
Notes
2004-12-01 00:00:0012/1/04 - PER A. APONTE - FAILED
  
 1) STEPS ON DATURA STREET ARE
 ENCROACHING INTO SIDEWALK.SIDEWALKS
 MUST BE EIGHT (8) FEET IN CLEAR WIDTH.
 SEE ARTICLE IV, SECTION 94-107(B)(7) OF
 THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 JOHN ROACH, PLANNER (561)822-1435

Review Stop Z ZONING
Rev No 5 Status N Date 2004-08-18 Cont ID  
Sent By mmclean Date 2004-08-18 Time 10:20 Rev Time 0.00
Received By mmclean Date 2004-08-18 Time 10:20 Sent To I
Notes
2004-08-18 00:00:00NO ZONING REQUIRED.

Review Stop Z ZONING
Rev No 4 Status F Date 2004-08-17 Cont ID  
Sent By agiannio Date 2004-08-17 Time 09:31 Rev Time 2.00
Received By agiannio Date 2004-08-17 Time 09:31 Sent To  
Notes
2004-08-17 00:00:00L-2.1 PLEASE PROVIDE PLAZA FLOOR
 ELEVATIONS AS IN ORIGINAL DRAWING 3/L-1
 L-3.2 PLEASE CONFIM ON DRAWINGS THAT
 SIDEWALKS ARE A MINIMUM OF 8 FT. CLEAR
 WIDTH FROM FACE OF CURB TO FACE OF
 PLANTERS.PLEASE CONFIRM THAT PAVERS ON
 CLEMATIS ST. MATCH EXISTING STREETSCAPE
 IN COLOR AND PATTERN.
 PLEASE RECONSIDER THE FORM OF THE STEEL
 PIPE RAILING.
 PLEASE PROVIDE PLANTING AND IRRIGATION
 DETAILS FOR PROPOSED STREET TREES INCLUD
 INCLUDING THE PLANTING VAULTS & GRADING.
 A-2.04 STEP CONFIGURATION DOES NOT
 REFLECT CHANGES ON L-2.1

Review Stop Z ZONING
Rev No 3 Status P Date 2004-06-09 Cont ID  
Sent By aaponte Date 2004-06-09 Time 13:09 Rev Time 0.00
Received By aaponte Date 2004-06-09 Time 13:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-11-26 Cont ID  
Sent By agiannio Date 2003-11-18 Time 14:02 Rev Time 6.00
Received By agiannio Date   Time   Sent To  
Notes
2003-11-18 00:00:00PROVISO:
 1.MOVE DRINKING FOUNTAIN AGAINST
 ARCADE OR COLUMN.
 2.SEC.94-114(A) COLUMN B REQ. A CERT.
 OF OCCUPANCY WILL NOT BE GIVEN UNTIL ONE
 PERCENT OF TOTAL DEVELOPMENT COST (BASED
 ON VALUE OF BUILDING PERMIT)DEDICATED
 TO "WORK OF ART" (AS DEFINED IN THE CITY
 ART IN PUBLIC PLACES ORDINANCE).
 3.ARTICULATE "CAP" (8TH STORY) WHERE
 WINDOWS WERE ELIMINATED CONSISTENT WITH
 CENTER TOWER DESIGN.

Review Stop Z ZONING
Rev No 1 Status F Date 2003-11-12 Cont ID  
Sent By shernand Date 2003-04-25 Time 15:12 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-05-23 00:00:00A RESOLUTION FOR AIR RIGHTS ON THE
 BALCONIES
2003-05-07 00:00:00DENIED
 1. SEC.94-11(A)(4)
 A. COLUMN A REQUIREMENT:
 I. PUBLIC OPEN SPACE MUST HAVE AN
 ADA ACCESSIBLE PATH LEADING THE
 MAIN LOBBY ENTRANCE.
 II. AS NOTED IN THE PPRC COMMENTS,THE
 FINISHED ELEVATION OF THE PLAZA
 AND THE ARCADE THAT FACES THE
 PLAZA MUST BE THE SAME SO THAT
 THEY ARE PERCEIVED AS ONE SPACE.
 III. PLEASE INCLUDE THE SQUARE FOOTAGE
 OF THE ARCADE THAT FACES THE PLAZA
 IN THE PUBLIC OPEN SPACE (POS)
 CALCULATIONS. DO NOT INCLUDE THE
 "SNIPPETS" AS THEY DO NOT MEET THE
 INTNENT OF POS.
 B. COLUMN B REQUIREMENTS:
 A CERTIFICATE OF OCCUPANCY WILL NOT
 BE ISSUED UNTIL ONE PERCENT OF
 TOTAL DEVELOPMENT COST (BASED ON THE
 VALUE OF THE BLDG PERMIT) IS
 DEDICATED TO "A WORK PF ART" (AS
 DEFINED IN THE CITY'S ART IN PUBLIC
 PLACES ORDINANCE). PLEASE INITIATE
 DESIGN/APPROVAL PROCESS.
 2. SEC.94-11(8). TOWER UNITS SHOWN ON
 UU/5.20 AND EE/5.13 SHOW EIGHTH
 STORY UNITS 22.8 IN HT.THE MAXIMUM
 FF TO FC HT. IS 14' PLEASE REVISE.
 3. SEC.94-113(B)(7) THE S/W ARE NOT
 DIMENSIONED ON CLEMATIS OR DATURA.
 PLEASE REVISE TO DEMOSTRATE 8' MIN.
 DEPTH HAS BEEN MET. ADJUST PLANTERS
 ACCORDINGLY.
 4.SEC.94-113(F)(10). DEMONSTRATE THAT
 THIS PROVISION HAS BEEN MET.
 5.SEC.94-113(I)(2). LANDSCAPE UNITS ARE
 REQUIRED ON CLEMATIS & DATURA.
 6. SEC94-113(I)(3). TREES ON CLEMATIS &
 DATURA EXCEED THE 40'O.C. REQUIRE-
 MENT. PLEASE REVISE.
 7. SHEET A-101. INDICATES 7-PARKING
 SPACES ON CLEMATIS; SITE PLAN &
 DRAINAGE PLAN DEPICT 8.
 8. ON-STREET PARKING SPACE DIMENSIONS
 ARE 22' LONG FOR END SPACES & 20'
 LONG FOR INTERIOR SPACES.
 9. ARCHITECTURAL DESIGN GUIDELINES: B3.8
 BALCONIES SHALL EXTEND NO MORE THAN 3
 FT FROM BLDG FACADE. PROPOSED
 BALCONIES ARE 4'. PLEASE REVISE.
 10. ARCHITECTURAL DESIGN GUIDELINES:B3.1
 8. PLEASE PROVIDE REFLECTED CEILING
 PLAN FOR ARCADES TO DEMONSTRATE THAT
 THIS PROVISION HAS MET.
 11. THE PLAZA IS REQUIRED TO HAVE 1-
 DRINKING FOUNTAIN AS PER OPEN
 SPACE REQUIREMENTS