Plan Review Details - Permit 03031677
Plan Review Stops For Permit 03031677
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-10-10 Cont ID  
Sent By rmcdouga Date 2003-10-10 Time 13:23 Rev Time 1.00
Received By rmcdouga Date 2003-10-10 Time 13:23 Sent To  
Notes
2003-10-10 00:00:00PROVISO
 1) SUBMIT A SIGNED AND SEALED LETTER
 FROM THE ENGINEER ADDRESSING THE TRUSS
 CONNECTOR AT THE GARAGE WITH UPLIFT OF
 3415 LBS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 11:02 Rev Time 3.00
Received By rmcdouga Date 2003-07-09 Time 15:40 Sent To  
Notes
2003-07-09 00:00:00BUILDING PROVISO
  
 1) A SEPARATE PERMIT & FEES ARE REQUIRED
 FOR STORM PANELS.
  
 2) SUBMIT THE DRAWINGS FOR AN OVERHEAD
 GARAGE DOOR LISTED IN SBCCI REPORT 9606C
 WITH DESIGN PRESSURES WHICH EQUAL OR
 EXCEED THOSE LISTED ON THE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-10 Cont ID  
Sent By kstevens Date 2003-07-07 Time 15:37 Rev Time 3.00
Received By rmcdouga Date 2003-06-10 Time 12:38 Sent To  
Notes
2003-06-10 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALCULATIONS.
  
 3) PAGE 3 SPECIFIES GLASS BLOCK AT THE
 REAR WALL OF THE MASTER BATH AND THE
 REAR ELEVATION ON PAGE TWO INDICATES A
 SINGLE HUNG WINDOW AT THIS LOCATION.
  
 4) SPECIFY THE SIZE OF THE GLASS BLOCK
 RADIUS OPENING IN THE MASTER BEDROOM.
 PROVIDE A PRODUCT APPROVAL FOR GLASS
 BLOCK WITH THIS CONFIGURATION.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLASS BLOCK
 - FIXED GLASS EYEBROW WINDOWS
 - ROOFING MATERIALS
 - SINGLE OUTSWING DOORS (GARAGE & CABANA
 BATH)
 - PARTS OF THE NOAS FOR THE DOUBLE
 OUTSWING DOORS ARE ILLEGIBLE
 - DOUBLE OUTSWING GLAZED DOORS WITH
 SIDELITES
  
 6) THE CONTRACTOR'S SIGNATURE ON THE
 PERMIT APPLICATION IS REQUIRED TO BE
 NOTARIZED.
  
 7) THE DRAWINGS FOR THE STORM PANELS ARE
 LIMITED BY THE ENGINEER TO ONE PERMIT
 ONLY. THEREFORE A SIGNED AND SEALED SET
 OF DRAWINGS IS REQUIRED FOR EACH PERMIT.
 OPENING SIZES ON SCHEDULE DO NOT INCLUDE
 THE FIXED GLASS EYEBROW WINDOW THAT IS
 MULLED TO THE SINGLE HUNG WINDOW. THE
 PRODUCT APPROVAL FOR SAFEGUARD STORM
 PANELS WILL NOT BE ACCEPTED UNTIL THE
 NAME ON THE SBCCI REPORT HAS BEEN
 CHANGED TO THE NEW COMPANY AND THE NEW
 ENGINEER HAS ADOPTED THE WORK OF THE
 ORIGINAL ENGINEER PER FAC 61G15-27.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-28 Cont ID  
Sent By pkrauss Date 2003-06-04 Time 15:08 Rev Time 6.00
Received By rmcdouga Date 2003-04-28 Time 14:36 Sent To  
Notes
2003-04-28 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE PERCENTAGE OF WALL AREA ALLOWED
 TO BE OPENINGS BY FBC TABLE 600 IS
 EXCEEDED AT THE FIRST AND SECOND FLOORS
 ON THE RIGHT ELEVATION.
  
 4) THE UPLIFT VALUE LISTED IN THE
 CONNECTOR SCHEDULE ON PAGE 5 FOR THE (2)
 HETA 20 ANCHORS (MARK C) IS INCORRECT.
 ACCORDING TO THE 2003 SIMPSON CATALOG
 THE UPLIFT VALUE FOR A DOUBLE HETA 20 IS
 2035# FOR A ONE PLY TRUSS AND 2500# FOR
 TWO OR THREE PLY TRUSSES.
  
 5) THE WALL LEGEND ON PAGE 6 SPECIFIES
 THE TOP OF THE CROSS MARKED WALLS TO BE
 10 FEET ABOVE FINISH FLOOR. THESE WALLS
 ARE 12 FEET ACCORDING TO THE ELEVATIONS.
  
 6) SPECIFY ON THE PLANS THE GUARDRAIL
 HEIGHT, THE SPACING OF THE INTERMEDIATE
 RAILS AND THE BOTTOM RAIL AT THE BALCONY
 SEE FBC 1015.3 AND 1026.5.1. SUBMIT
 SHOP DRAWINGS PRIOR TO INSTALLATION.
  
 7) THE STAIR WINDERS ARE REQUIRED TO
 HAVE A MINIMUM TREAD DEPTH OF 6 INCHES
 AT THE NARROW EDGE AND HAVE A MINIMUM
 TREAD DEPTH OF 11 INCHES AT A POINT 12
 INCHES FROM THE NARROW EDGE. SEE
 FBC 1007.8.1
  
 9) THE WALL SECTION ON PAGE 4 SPECIFIES
 R-30 INSULATION IN THE 2X6 WALL. PLEASE
 CORRECT.
  
 10) INDICATE THE LOCATIONS AND SIZES OF
 THE ATTIC ACCESS OPENINGS AT THE GARAGE
 AND THE SECOND STORY. SEE FBC 2309.6.
  
 11) THE WALL SECTION ON PAGE 4 SPECIFIES
 A VENTED ALUMINUM SOFFIT. SUBMIT THE
 PRODUCT APPROVALS AND MANUFACTURER'S
 SPECIFICATIONS FOR THIS ITEM.
  
 12) PLEASE CLARIFY THE 1/4 NAILER AND
 1/4 WINDOW BUCK LISTED ON THE WALL
 SECTION ON PAGE 4.
  
 13) INDICATE FIREBLOCKING ON THE WALL
 SECTIONS WHERE THE FURRED SPACE OF WALL
 AND CEILING MEET PER FBC 2305.1. THE
 CONCEALED SPACES BETWEEN THE STAIR
 STRINGERS ARE REQUIRED TO BE FIREBLOCKED
 AT THE TOP AND BOTTOM OF RUNS PER FBC
 2305.1.4.
  
 14) INDICATE THE LOCATION AND MATERIAL
 THAT WILL BE USED TO TO PROVIDE THE
 DRAFTSTOPPING REQUIRED BY FBC 2305.2.2
 TO DIVIDE THE FLOOR/CEILING ASSEMBLY
 INTO AREAS NO GREATER THAN 500 SQFT.
 SEE FBC 2305.2.6 FOR APPROVED MATERIALS.
  
 15) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. THE
 SBCCI REPORT (PRODUCT APPROVAL) THAT WAS
 SUBMITTED FOR STORM PANELS IS EXPIRED.
 SUBMIT CURRENT REPORT.
  
 16) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL MULLIONS
 - GLASS BLOCK
 - SINGLE OUTSWING DOORS AT THE GARAGE
 AND CABANA BATH
 - THE SEVEN PAGES OF DRAWINGS THAT ARE
 PART OF THE SINGLE HUNG WINDOW NOA
 - FIXED GLASS EYEBROW WINDOWS
 - FIXED GLASS TRANSOM ABOVE (3) 26 SH
 WINDOWS AT LIVING ROOM ( THE PRODUCT
 APPROVAL SUBMITTED DOES NOT INCLUDE
 NINE FEET PLUS WIDE WINDOWS OR EYEBROW
 WINDOWS)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-07 Cont ID  
Sent By dpalmer Date 2003-07-07 Time 10:50 Rev Time 0.50
Received By dpalmer Date 2003-07-07 Time 10:50 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-06-11 Cont ID  
Sent By shernand Date 2003-07-02 Time 11:26 Rev Time 1.00
Received By dpalmer Date 2003-06-11 Time 09:30 Sent To  
Notes
2003-06-11 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT ONLY ONE PANEL
 SCHEDULE AND LOAD CALCULATIONS.
 SOME ITEMS THAT WERE NOTES ON FIRST
 REVIEW WERE ADDRESSED ON ORIGINAL SHEET
 AND NOT THE SAME ON ATTACHED PANEL SCH.?
  
 2)NOTE: KITCHEN COUNTERSPACE STILL
 MISSING RECEPTS REQ`D PER 210-52C1
 PLEASE ALSO NOTE, NO HAND DRAWN PENCIL
 CHANGES ARE PERMITTED UNLESS DRAWN IN,
 IN INK AND SIGNED/DATED BY THE EGINEER
 OF RECORD.
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED "CIRCUITS" ON PANEL SCHEDULE.
 210-12. PLANS SHOW NOTE THAT MENTIONS
 ARC RECEPTS? PLEASE NOTE, AS OF TODAYS
 DATE, ARC FAULT RECEPTS HAVE NOT YET
 COME OUT.
  
 4)NOTE: PLEASE SEE MISSING RECEPT PER
 210-52 BR#3
  
 5)NOTE: PLEASE SEE TWO DIFFERENT PANEL
 SCHEDULES. ONE SHOWS MCB AND OTHER MLO?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By kstevens Date 2003-05-31 Time 16:43 Rev Time 0.75
Received By dpalmer Date 2003-04-03 Time 17:27 Sent To M
Notes
2003-04-03 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE MISSING SD ON LOWER
 LEVEL AT BOTTOM OF STAIRS. NFPA-72
 8-1.4.2
  
 2)NOTE: PLEASE CLARIFY/VERIFY KW RATING
 FOR TANKLESS WATER HEATERS SHOWN AT 800W
 `S. PLEASE NOTE 800W TLWH ARE NOT A
 TYP SIZE FOR A HOUSE THIS SIZE.
 PLEASE SUBMIT SPECS ON UNITS BEING
 INSTALLED AND REDO LOAD CALCULATIONS.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULE,
 MANY ITEMS ARE SHOWN AS 2-POLE AND ONLY
 TAKE ONE SPACE IN PANEL AND ARE LABELED
 FOR 1-POLE??33,34,35 ,,,
  
 4)NOTE: PLEASE SEE LOAD CALCUALTIONS,
 LOAD FOR AHU/HEAT ONLY SHOWS ONE OF THE
 10KW UNITS IN LOAD CALCS??
 PLEASE ADJUST PER NEC 220
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE
 PER 210-12
  
 6)NOTE: PLEASE VERIFY LOCATION OF TKLWH
 ON SECOND FLOOR, BEHIND BEDROOM DOOR
 IN BEDROOM #4??
  
 7)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW SERVICE EQUIPMENT BEING INSTALLED.
 ALL MAINS/PANELS/BRKRS ARE TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. 110-9
 215-5
  
 8)NOTE: PLEASE SEE MISSING RECEPT FOR
 KITCHEN COUNTERSPACE. PLEASE SEE 210-52
 C-1. 12" OF COUNTER/WALL SPACE.
  
 9)NOTE: PLEASE SEE 210-52 FOR RECEPTS
 MISSING. 2',6',12' RULE.
  
 10)NOTE: PLEASE CORRELATE PLAN AND PANEL
 SCHEDULE. PLAN SHOWS POOL PUMP AND
 IRRIGATION PUMP AT 220V AND PANEL SCH
 SHOWS 120V??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 11:02 Rev Time 0.00
Received By csiegber Date 2003-10-09 Time 11:02 Sent To B
Notes
2003-10-09 00:00:00TO RM DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 16:55 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 16:54 Sent To B
Notes
2003-07-11 00:00:00RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-02 Cont ID  
Sent By shernand Date 2003-07-02 Time 11:26 Rev Time 0.00
Received By shernand Date 2003-07-02 Time 11:26 Sent To E
Notes
2003-07-02 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-05-30 Time 15:42 Rev Time 0.00
Received By shernand Date 2003-05-30 Time 15:42 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-19 Cont ID  
Sent By sthyng Date 2003-03-19 Time 16:36 Rev Time 0.00
Received By sthyng Date 2003-03-19 Time 16:36 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-06-04 Cont ID  
Sent By pkrauss Date 2003-06-04 Time 15:08 Rev Time 0.35
Received By pkrauss Date 2003-06-04 Time 14:42 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By kstevens Date 2003-05-31 Time 16:48 Rev Time 0.75
Received By rregueir Date 2003-04-03 Time 19:46 Sent To B
Notes
2003-04-03 00:00:00DENIED
  
 FLOOR PLAN LAYOUT DOES NOT MATCH A/C
 PLAN.PLEASE SEE CABANA BATH/WEIGHT
 ROOM AREAS.VERIFY WHICH IS CORRECT
 AND RESUBMIT MATCHING PLANS.IF WEIGHT
 ROOM IS CORRECT, BALANCED R/A IS
 REQUIRED FROM THIS AREA.
 REVIEWED BY RONALD J REGUEIRO
 561-659-8096 X8512

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-07 Cont ID  
Sent By kstevens Date 2003-07-07 Time 15:36 Rev Time 0.50
Received By kstevens Date 2003-07-07 Time 15:36 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-05-31 Cont ID  
Sent By dpalmer Date 2003-07-07 Time 10:51 Rev Time 0.75
Received By kstevens Date 2003-05-31 Time 16:37 Sent To M
Notes
2003-05-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. SECOND FLOOR BATHROOM
 SHALL NOT DRAIN INTO THE VENT FOR THE
 WASH MACHINE. NO DRY HORIZONTAL VENTS.
 D/W SHALL DRAIN INTO DRAIN FOR KIT SINK
 NOT DIRECTLY INTO STACK. NO TRAPS UNDER-
 GROUND FOR W/C'S. UNVENTED FIXTURES ECT.
 ---- PLEASE SEE ATTACHED SANITARY RISER
 DIAGRAM AS AN EXAMPLE OF A SANT. RISER
 THAT REFLECTS THE FLOOR PLAN AND MEETS
 CODE REQUIREMENTS.---------
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-31 Cont ID  
Sent By shernand Date 2003-05-30 Time 15:42 Rev Time 0.50
Received By jleech Date 2003-03-31 Time 19:21 Sent To E
Notes
2003-03-31 00:00:00DENIED;
 PAGE 2OF 10 PLUMBING RISER DIAGRAM DOES
 NOT MATCH FLOOR PLAN. CABANA BATH AND
 BAR SINK MISSING. 1/2 BATH LAV DOWN
 STREAM OF W/C. MASTER BATH LAVS CANNOT
 BE INSTALLED ON SAME STACK. KITCHEN SINK
 SINK SHOULD HAVE A MECHANICAL VENT, NO
 WALL FOR STACK. UTILITY SINK AND W/M ARE
 ON DIFFERENT WALL. UP STAIR BATH NEED
 TWO STACKS FOR LAVS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-19 Time 16:36 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***