Plan Review Details - Permit 03031260
Plan Review Stops For Permit 03031260
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-24 Cont ID  
Sent By dpalmer Date 2003-03-24 Time 07:12 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2003-03-24 00:00:00***********PROVISO***********
 1. DRAWING MUST BE SUBMITTED SHOWING
 METHOD OF PROTECTION FROM HOUSE OPENINGS
 TO POOL PER FBC2001 CHAPTER 4

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-28 Cont ID  
Sent By dpalmer Date 2003-03-28 Time 10:46 Rev Time 0.25
Received By dpalmer Date 2003-03-28 Time 10:46 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-26 Time 14:27 Rev Time 0.25
Received By dpalmer Date 2003-03-24 Time 07:12 Sent To B
Notes
2003-03-24 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SHOW TIME CLOCK AS REQ`D
 UNDER FBC.
  
 2)NOTE: PLEASE SEE WHERE THERE IS ONLY
 HALF OF ONE SHEETS SUBMITTED AND YET
 IT IS SIGNED AND SEALED BY ENGINEER?
 PLEASE ALSO SUMIT TITLE BLOCK INFORMAT-
 -ION AS SET FORTH UNDER FS AND FAC
 61G15-23.002. MUST ALSO CONTAIN LIC #.
 PLEASE SEE SHEET MISSING TITLE BLOCK.
  
 3)NOTE: PLEASE SHOW HOW HEATER IS BEING
 CONNECTED. NOT SHOWN ON RISER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-26 Cont ID  
Sent By sthyng Date 2003-03-26 Time 14:27 Rev Time 0.00
Received By sthyng Date 2003-03-26 Time 14:27 Sent To E
Notes
2003-03-26 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 16:17 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 16:17 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-02 Cont ID  
Sent By kstevens Date 2003-04-02 Time 04:42 Rev Time 0.33
Received By kstevens Date 2003-04-02 Time 04:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-20 Cont ID  
Sent By dpalmer Date 2003-03-28 Time 10:46 Rev Time 0.50
Received By kstevens Date 2003-03-20 Time 18:19 Sent To E
Notes
2003-03-20 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92, AND NSPI-5. (ADD TO
 NOTES)
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 VACUUM NOT FOUND ON POOL LAY OUT, BUT
 ITS CALLED FOR IN GENERAL SPECIFICATIONS
 3) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (GIVE DETAIL)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) GENERAL NOTES #5 NOT APPLICABLE.
 PLEASE UPDATE TO CORRECT FBC-2001
 6) 50% OF ONE DETAIL SHEET IS BLANK.
 PLEASE REVIEW PLANS PRIOR TO SIGNING &
 SEALING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-17 Cont ID  
Sent By sthyng Date 2003-03-14 Time 16:17 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***