2003-03-20 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW |
| 1) FBC-2001 SEC 424.2.6.1 ENGINEERING |
| DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| ANSI/NSPI-4 92, AND NSPI-5. (ADD TO |
| NOTES) |
| 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) |
| VACUUM NOT FOUND ON POOL LAY OUT, BUT |
| ITS CALLED FOR IN GENERAL SPECIFICATIONS |
| 3) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| THE VACUUM OR PRESSURE CLEANER FITTING |
| SHALL BE LOCATED AT LEAST 6" AND NOT |
| GREATER THAN 12" BELOW THE MINIMUM OPER- |
| ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| THE SKIMMER. (GIVE DETAIL) |
| 4) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 5) GENERAL NOTES #5 NOT APPLICABLE. |
| PLEASE UPDATE TO CORRECT FBC-2001 |
| 6) 50% OF ONE DETAIL SHEET IS BLANK. |
| PLEASE REVIEW PLANS PRIOR TO SIGNING & |
| SEALING. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |