Plan Review Details - Permit 03031105
Plan Review Stops For Permit 03031105
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-10 Cont ID  
Sent By hpiskura Date 2003-07-10 Time 14:30 Rev Time 0.00
Received By hpiskura Date 2003-07-10 Time 14:15 Sent To FIRE
Notes
2003-07-10 00:00:00PAY IMPACT FEES TO COUNTY

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-29 Cont ID  
Sent By hpiskura Date 2003-05-29 Time 15:51 Rev Time 0.00
Received By hpiskura Date 2003-05-29 Time 12:47 Sent To  
Notes
2003-05-29 00:00:00THE DELTA FIRE SPRINKLER PLANS DO NOT
 HAVE COMPLETE DESIGN INFORMATION AND
 WERE NOT PREPARED BY AN ENGINEER.SEE
 FBC 104.2 AND THE FL ADMINISTRATIVE
 CODE CHAPTERS 61G15-31 AND 61G15-32.
  
 THE PLANS DO NOT SHOW THE DRAFTSTOPPING
 IN THE EXTERIOR WOOD TRUSS CANOPY IN
 ACCORDANCE WITH FBC 2305.2.4.
  
 THE HORTON AUTOMATIC NOA 03-0306.05 IS
 MISSING PAGES.NOA 00-0512.12 IS
 EXPIRED AND ILLEGIBLE.
  
 THE SW FLEMING NOA 97-0327.01 IS
 EXPIREDNOA 01-0129.09 IS MISSING PAGES
 AND IS ILLEGIBLE.
  
 NOA 00-0508.01 HAS THE WRONG DRAWINGS
 ATTACHED TO IT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-15 Cont ID  
Sent By hpiskura Date 2003-04-15 Time 09:21 Rev Time 0.00
Received By hpiskura Date 2003-04-14 Time 15:04 Sent To Z
Notes
2003-04-15 00:00:00THE FIRE SPRINKLER PROTECTION PLANS ARE
 REQUIRED TO BE INCLUDED WITH THE
 BUILDING PERMIT PLANS. SEE FBC
 140.3.1.1 #5.
  
 IF TEST AND OR NOTICE OF ACCEPTANCE
 REPORTS FOR THE DOORS WINDOWS AND ROOF
 COVERING ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION, A SEPARATE PERMIT
 AND FEES WILL BE REQUIRED.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL (561) 233-5025 FOR
 MORE INFORMATION.
  
 THE EXTERIOR CANOPY/CORNICE REQUIRES
 DRAFTSTOPPING IN ACCORDANCE WITH FBC
 2305.4.
  
 THE FOAM BASED ARCHITECTURAL TRIM SHOWN
 IN SECTION 2/A2.2 IS PROHIBITTED BY FBC
 F102.2.7 AS AMENDED BY THE CITY.
 (NON-COMBUSTIBLE MATERIAL OR FRT LUMBER
 IS REQUIRED.)

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-09 Cont ID  
Sent By dpalmer Date 2003-07-09 Time 17:33 Rev Time 1.50
Received By dpalmer Date 2003-07-09 Time 17:32 Sent To  
Notes
2003-07-09 00:00:00********** NOTES REDLINED *********
  
 PLEASE SEE NOTE REDLINED ON RISER
 DIAGRAM. NO MORE THAN 8' OF UNPROTECTED
 CONDUCTOR INSIDE BLDG PER LOCAL
 AMENDMENTS 210-70
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS.
  
 MDP PANEL SCHEDULEON E-11 STILL SHOWS
 MLO.
  
 PLEASE REVISE PLANS BEFORE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
  
 IF THERE ARE ANY QUESTINOS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-30 Cont ID  
Sent By btrobaug Date 2003-05-30 Time 14:44 Rev Time 1.00
Received By btrobaug Date 2003-05-30 Time 12:36 Sent To  
Notes
2003-05-30 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING COMMENTS FROM
 THE LAST REVIEW THAT WERE ONLY
 PARTIALLY ADDRESSED OR NOT
 SATIFACTORILY ADDRESSED.
  
 1} THE PANEL SCHEDULES ARE STILL LISTING
 MLO & MAIN,AND NOW PANELS "C" & "P"
 LIST MCB.IF THE PANEL RATING IN AMPS IS
 225 OR 100,IT SHOULD NOT BE LISTED AS
 IF THAT WERE THE MAIN BREAKER
 SIZE.PLEASE CLARIFY ALL PANEL
 DESIGNATIONS WITH CONSISTENCY.
  
 2} THERE ARE STILL SEVERAL EXIT &
 EMERGENCY LIGHTS ON CIRCUIT A-20(SHEET
 E-2). THIS IS IN VIOLATION OF ARTICLE
 700-12(E).
  
 PLEASE CORRECT AND RESUBMIT FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-24 Cont ID  
Sent By dpalmer Date 2003-03-24 Time 09:11 Rev Time 2.00
Received By dpalmer Date 2003-03-24 Time 09:11 Sent To  
Notes
2003-03-24 00:00:00************* UNSAT ********************
  
  
 1)NOTE: PLEASE SEE GENERAL NOTE FOR
 AIC RATINGS. IT IS NOTED THAT "PANELS"
 ARE TO BE 65K SERIES RATED, PLEASE
 CLARIFY IF THIS IF FOR MAIN DISC ALSO.?
 110-9
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULES. PLEASE SEE RISER
 SHOWS PANELS "C" AND "P" AS 225A AND
 PANEL SCHEDULES SHOW THEM AS 100A.
 PLEASE ALSO CLARIFY PANELS. THEY ARE
 ALL SHOWN AS MLO AND MCB? P RISER SHOWS
 PANELS AS BEING MLO.?
  
 3)NOTE: PLEASE SHOW CIRCUITING FOR
 EM/EXT LTS PER 700-12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-06-26 Cont ID  
Sent By mamini Date 2003-06-26 Time 15:45 Rev Time 1.00
Received By mamini Date 2003-06-26 Time 15:45 Sent To  
Notes
2003-06-26 00:00:00PASSED :
 1. SEE PERMIT # 03061900 FOR UNDERGROUND
 UTILITIES AND SITE WORKS.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-03-19 Cont ID  
Sent By mamini Date 2003-03-19 Time 14:13 Rev Time 2.00
Received By mamini Date 2003-03-19 Time 14:13 Sent To  
Notes
2003-03-19 00:00:00FAILED:
 1. CURB CUT RAMP MUST BE INSTALLED ON
 MAIN APPROACH AT PALM BEACH LAKES BLVD.
 2. MAIN APPROACH; FROM DROP CURB TO THE
 PROPERTY LINE MUST BE CONSTRUCTED USING
 6" CONCRETE.
 3.ALL BROKEN SIDEWALK ALONG THE PROPERTY
 (ALL SIDE) MUST BE REPLACED.
 4. ALL DRIVE APPROACH MUST BE AT MINIMUM
 PER CITY STANDARD.
 5. ALL THE EASEMENTS AS SHOWN MUST BE
 RECORDED IN PUBLIC RECORDS OF PALM BEACH
 COUNTY.
 6. PARKING STALLS MUST BE PAINTED WITH
 DOUBLE 4" WIDE WHITE FOR REGULAR SPACES.
 7. PLEASE SUBMIT TWO COPIES OF CIVIL/
 SITE PLANS TO PUBLIC UTILITIES
 ENGINEERING SERVICES FOR THEIR REVIEW
 AND APPROVAL OF ALL THE CONNECTIONS TO
 CITY SERVICES AND FOR THE LOCATION OF
 BACKFLOWS,METERS, ETC..
 8. PLEASE PROVIDE STORM WATER CALC. AND
 A COPY OF SFWMD PERMIT FOR OUR REVIEW
 AND APPROVAL, SUBMITTALS MUST INCLUDE
 PERVIOUS AND IMPERVIOUS CALC. FOR TOTAL
 SITE AREA.
 9. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK WILL BE REQUIRED
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-07-11 Cont ID  
Sent By mcarsill Date 2003-07-11 Time 07:27 Rev Time 0.00
Received By mcarsill Date 2003-07-11 Time 07:27 Sent To  
Notes
2003-07-11 00:00:001) ON JULY 10, 2003, WRITER CONTACTED
 THE ARCHITECT KENT HAMILTON BY PHONE
 TO DISCUSS THE PLANS. HE ADVISED WHERE
 THE CORRECTIONS COULD BE LOCATED SINCE
 THE RESUBMITTED PLANS WERE DIFFICULT TO
 FOLLOW. THE FOLLOWING ITEMS COULD NOT
 BE LOCATED OR REVIEWED.
  
 A) ITEM # 9 FROM PREVIOUS COMMENTS.
 HOW DOES THE MONUMENT SIGN NOT
 INTERFERE WITH ACCESS TO THE PROPOSED
 FIRE HYDRANT.
  
 B) ITEM # 2 FROM PREVIOUS COMMENTS.
 ELECTRONIC SWITCHES ARE REQUIRED FOR
 THE FIRE LINE BACKFLOW DEVICE.
  
 C) ACCORDING TO MR. HAMILTON, NO
 SECURITY DEVICES WILL NOT INTERFERE
 WITH EGRESS FROM BUILDING. MR.
 HAMILTON, ALL EGRESS DOORS EXCEPT
 THE MAIN DOORS WILL BE EQUIPPED WITH
 PANIC HARDARE AND WILL HAVE FREE
 EGRESS AT ALL TIMES.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status   Date   Cont ID  
Sent By hpiskura Date 2003-07-10 Time 14:31 Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-06-24 Cont ID  
Sent By nmccray Date 2003-06-24 Time 14:53 Rev Time 0.00
Received By nmccray Date 2003-06-24 Time 14:53 Sent To  
Notes
2003-06-24 00:00:00*************DENIED********************
 PLEASE NOTE THE PREVIOUS COMMENTS FROM
 THE LAST REVIEW WERE ONLY PARTIALLY
 ADDRESSED OR NOT ADDRESSED.
  
 FIRE SPRINKLER PLANS DO NOT HAVE
 COMPLETE DESIGN INFORMATION AND FLOW
 DATA. AND THE PLANS ARE NOT SEALED.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-04-04 Cont ID  
Sent By mcarsill Date 2003-04-04 Time 14:40 Rev Time 0.00
Received By mcarsill Date 2003-04-04 Time 14:40 Sent To  
Notes
2003-04-04 00:00:001) THE BUILDING IS LOCATED IN THE
 CITY FIRE LIMITS. CERTAIN RESTRICTIONS
 APPLY. PLEASE SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 2) ELECTRONIC SWITCHES ARE REQUIRED
 ON THE FIRE LINE BACKFLOW DEVICE.
  
 3) THE AUTOMATIC DOORS SHALL COMPLY
 WITH NFPA 101, THE LIFE SAFETY CODE,
 2000 EDITION, SECTION 7.
  
 4) PLEASE OBTAIN YOUR KNOX-BOX
 APPLICATION FROM THIS OFFICE SO YOU
 CAN ODER IT.
  
 5) WOOD NOTED ON EXTERIOR. AGAIN
 CERTAIN RESTRICTIONS APPLY IN THE
 FIRE LIMITS.
  
 6) THE BUILDING ADDRESS IS REQUIRED
 ON THE PROPER ELEVATION.
  
 7) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR HANDRAILS.
  
 8) HOW DOES THE MONUMENT SIGN NOT
 INTERFERE WITH ACCESS TO THE PROPOSED
 FIRE HYDRANT.
  
 9) SECURITY DEVICES INSTALLED SHALL
 NOT INTERFERE WITH ANY EGRESS FROM
 THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-31 Cont ID  
Sent By lsmith Date 2003-10-31 Time 09:40 Rev Time 0.00
Received By lsmith Date 2003-10-31 Time 09:40 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 12:13 Rev Time 0.00
Received By csiegber Date 2003-10-06 Time 12:13 Sent To P
Notes
2003-10-06 00:00:00TO KS BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 16:20 Rev Time 0.00
Received By alange Date 2003-08-04 Time 16:20 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-22 Cont ID  
Sent By sgraham Date 2003-07-14 Time 16:32 Rev Time 0.00
Received By shernand Date 2003-05-22 Time 09:43 Sent To  
Notes
2003-05-22 00:00:00COMM BOARD #38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:50 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 10:50 Sent To  
Notes
2003-03-14 00:00:00COMM BOARD #59

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-10 Cont ID  
Sent By pkrauss Date 2003-04-10 Time 11:46 Rev Time 1.40
Received By pkrauss Date 2003-04-10 Time 11:46 Sent To  
Notes
2003-04-10 00:00:00MECHANICAL PERMIT REQUIRED - PROVIDE
 MANUFACTURER INSTALLATION INSTRUCTIONS
 FOR THE FIRE DAMPER ON THE JOBSITE AT
 TIME OF INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719

Review Stop P PLUMBING
Rev No 6 Status P Date 2003-11-01 Cont ID  
Sent By kstevens Date 2003-11-01 Time 12:06 Rev Time 0.50
Received By kstevens Date 2003-11-01 Time 12:06 Sent To  
Notes
2003-11-01 00:00:00CONNECTING DOWNSPOUTS TO STORM AND TIE
 TO CATCH BASIN.

Review Stop P PLUMBING
Rev No 5 Status F Date 2003-10-17 Cont ID  
Sent By lsmith Date 2003-10-31 Time 09:40 Rev Time 0.50
Received By kstevens Date 2003-10-17 Time 18:36 Sent To  
Notes
2003-10-17 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) REVISIONS SHALL HAVE CLARITY, AND
 CONTRAST, ALL REVISED SECTIONS OF PLANS
 SHALL BE INDICATED BY THE USE OF CLOUDS
 ECT. UNABLE TO DETERMINE THE REVISION
 BEING SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-07-11 Cont ID  
Sent By csiegber Date 2003-10-06 Time 12:18 Rev Time 1.00
Received By kstevens Date 2003-07-11 Time 14:01 Sent To  
Notes
2003-07-11 00:00:00PASSED/PROVISO
  
 FILLMASTER FILTER NOT APPROVED. FILTER
 SHALL BE NSP APPROVED AND LABELED PER
 SECTION 303.4 - WILL SUBMIT MODEL THAT
 IS LABELED PRIOR TO ROUGH INSPECTION.
  
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN CEILING.

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-07-10 Cont ID  
Sent By kstevens Date 2003-07-10 Time 12:11 Rev Time 1.50
Received By kstevens Date 2003-07-10 Time 12:11 Sent To  
Notes
2003-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 FOLLOWING COMMENTS NOT ADDRESSED FROM
 PREVIOUS REVIEW. FOR CLAIRTY THE COMMENT
 NUMBER FROM FIRST REVIEW WILL BE USED.
  
 4) SHT P-1 #13 FILTER SHALL COMPLY WITH
 NSF STANDARD. MANUF. INFO REQUIRED. -
 INFORMATION RECIEVED AND NSF LISTING NOT
 SHOWN. CHECKED NSF RECORDS AND NO LIST-
 ING SHOWN FOR THIS PRODUCT. SEC 303.4
 7) (IN PART) WATER HAMMER ARRESTORS REQ-
 UIRED BY SEC 406.9 SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE", NOT
 IN THE CEILING AT THE TOP OF THE DROP.
 PDI-WH 201 AND MANUFACTURE INSTALLATION
 INSTRUCTIONS.
  
 NEW COMMENT: SEE ATTACHED SHEET CONCERN-
 ING FLORIDA STATUTE 553.80(2)(B)
  
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-14 Cont ID  
Sent By kstevens Date 2003-06-14 Time 14:03 Rev Time 0.50
Received By kstevens Date 2003-06-14 Time 14:03 Sent To  
Notes
2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 FOLLOWING COMMENTS NOT ADDRESSED FROM
 PRIVIOUS REVIEW. FOR CLAIRTY THE COMMENT
 NUMBER FROM FIRST REVIEW WILL BE USED.
  
 4) SHT P-1, #13 FILTER SHALL COMPLY WITH
 NSF STANDARD. MANUF. INFO REQUIRED.
 7) (IN PART) WATER HAMMER ARRESTORS REQ-
 UIRED BY SEC 406.9 SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFICTIVE RANGE" NOT
 IN THE CEILING AT THE TOP OF THE DROP.
 PDI-WH 201 & MANUF. INSTALLATION
 INSTRUCTIONS.
  
 NEW COMMENT.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-28 Cont ID  
Sent By kstevens Date 2003-03-28 Time 12:49 Rev Time 2.75
Received By kstevens Date 2003-03-28 Time 10:17 Sent To  
Notes
2003-03-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A2.2 PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SEC'S 1106 & 1107. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS, (1106.4), INCLUDING
 PARAPET, (1106.5). SHOW AREA OF ROOFS
 THAT DRAIN ON TO ROOF FROM ABOVE.
 INDICATE SQUARE FOOTAGE DRAINED BY EACH.
 2) SHT 2.2 INDICATE PITCH OF GUTTERS PER
 TABLE 1106.6 AND SHOW SQUARE FOOTAGE
 DRAINED FROM EACH ROOF AREA TO GUTTER.
 3) SHT A2.2 INDICATES 24"X16" SCUPPERS
 AND OVERFLOW SCUPPERS. IT SAYS TYPICAL
 OF 5, BUT ONLY 4 ARE SHOWN. PLEASE
 CLAIRFY.
 4) SHT P-1 #13 FILTER SHALL COMPLY WITH
 NSF STANDARD. MANUF. INFO. REQUIRED.
 5) SHT P-1 #'S 15 & 19, FLOOR DRAINS ARE
 NOT APPROVED FOR INDIRECT WASTE. ALL
 INDIRECT WASTE SHALL DRAIN TO FLOOR SINK
 SECTION 802.3
 6) SHT P-3 DETAILS #3 & 6, FLOOR SINKS
 REQUIRED. SECTION 802.3
 7) SHT P-4 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. WATER HAMMER
 ARRESTORS REQUIRED BY 406.9, (AT QUICK
 CLOSING VALVES), SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 AT THE TOP OF THE DROP IN THE CEILING.
 PDI-WH 201 & MANUF. INSTALLATION INSTR.
 8) IRRIGATION PERMIT REQUIRED. PLUMBING
 CONTRACTOR SHALL TIE INTO WATER SERVICE
 AND SUPPLY SHUT OFF VALVE FOR IRRIGATION
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2003-08-07 Cont ID  
Sent By sgraham Date 2003-08-07 Time 09:57 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-07-14 Cont ID  
Sent By alange Date 2003-08-04 Time 16:20 Rev Time 1.00
Received By sgraham Date   Time   Sent To I
Notes
2003-06-10 00:00:006/10/03 PASS ZONING, GIVEN TO SYLVIA MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-05-23 Cont ID  
Sent By hpiskura Date 2003-04-15 Time 09:53 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-05-23 00:00:00DENIED, APPROVED SITE MUST BE SUBMITTED