Plan Review Stops For Permit 03030708 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2003-08-07 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2003-08-07 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2003-08-06 |
Time |
13:44 |
Sent To |
|
|
Notes |
2003-08-07 00:00:00 | THE PROPOSED CHANGE TO THE ROOF FROM A | | FLAT ROOF TO A HIPPED ROOF IS SUBJECT | | TO APPROVAL BY THE HISTORIC | | PRESERVATION BOARD AND MAY NOT PERMITTED | | AT THIS TIME.CONTACT MS. SHERRY | | PILAND AT 659-8031 FOR MORE INFORMATION. | | | | A COMPLETE PLAN REVIEW FOR CODE | | COMPLIANCE CANNOT BE ACCOMPLISHED AT | | THIS TIME. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2003-05-30 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2003-05-16 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
2003-05-16 |
Time |
14:07 |
Sent To |
|
|
Notes |
2003-05-16 00:00:00 | SAME AS 4/9/03 COMMENTS.A FLORIDA | | REGISTERED ENGINEER OR ARCHITECT IS | | REQUIRED TO PREPARE THE PLANS AND | | ADDRESS THE STRUCTURAL, FIRE AND LIFE | | SAFETY ISSUES OF THE 2001 FLORIDA | | BUILDING CODE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-04-09 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2003-04-09 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2003-04-09 |
Time |
13:52 |
Sent To |
|
|
Notes |
2003-04-09 00:00:00 | THE PLANS ARE REQUIRED TO BE PREPARED BY | | A FLORIDA REGISTERED ARCHITECT OR | | ENGINEER.SEE FBC 101.4.2. | | | | AS PROVIDED FOR IN FBC 3401.7.2.6 WHEN | | THE REPAIR COST WILL EXCEED 50% OF THE | | VALUE OF THE BUILDING, THE BUILDING AND | | ITS SYSTEMS MUST COMPLY WITH THE CURRENT | | CODE. | | | | SEE FBC 104.3.1.1 FOR MINIMUM PLAN | | REVIEW CRITERIA AS WELL AS THE | | INFORMATION IN J.F. SHIELS, PE LETTER | | ADDRESSED TO THE BOARD OF APPEALS | | CHAIRMAN DATED 2/15/03. | | | | SOME, BUT NOT ALL OF THE CODE ISSUES | | ARE STRUCTURAL DESIGN LOADS | | VERTICAL HANDICAP ACCESSIBILITY | | STANDARDS, COMPONENT AND CLADDING | | PRESSURES, FIRE RESISTANT RATINGS, AND | | SPECIFIC REPAIR PROCEDURES. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2003-08-01 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-08-01 |
Time |
12:59 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2003-07-31 |
Time |
16:35 |
Sent To |
|
|
Notes |
2003-08-01 00:00:00 | FAILED | | ~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE ADDRESS THE FOLLOWING COMMENTS | | AND RESUBMIT FOR REVIEW. | | | | 1} PLEASE NOTE THAT ALL PLANS | | THAT ARE SIGNED AND SEALED BY ARCH/ OR | | ENGINEER ARE REQ`D PER 61G15-23.002 FOR | | ENGINEER AND 61G1-16.004 FOR ARCH. | | SHALL HAVE A TITLE BLOCK. | | | | 2} REMOVE THE DISCONNECT THAT IS AHEAD | | OF THE METERS. FPL WILL NOT HOOK UP TO | | AN UNMETERED SERVICE. | | | | 3} REDRAW RISER TO SHOW LOCATION OF | | RISER AND SERVICE CONDUCTOR SIZE. | | | | 4} PLEASE RECALCULATE THE LOADS TO | | REFLECT THE CORRECT LIGHTING LOAD PER | | TABLE 220-3(A).* | | | | 5} SHOW CONTINUOUS LOADS PER 210-19 | | (125%) * | | | | 6} LIST THE REQUIRED SIGN CIRCUIT PER | | 600-5.* | | | | 7} THE DEMAND FACTORS USED IN THE LOAD | | CALCULATION ARE FOR DWELLING UNITS AND | | ARE NOT ALLOWED TO BE USED IN | | COMMERCIAL APPLICATIONS.PLEASE | | RECALCULATE USING ALLARTICLES THAT | | APPLY. | | | | PLEASE SEE ATTACHED FLORIDA STATUTE 553. | | 80(2)(B). * DENOTES COMMENTS ON PAST | | REVIEW. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-03-17 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2003-07-23 |
Time |
15:26 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-03-17 |
Time |
16:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2003-05-14 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-05-14 |
Time |
16:54 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-05-14 |
Time |
16:23 |
Sent To |
|
|
Notes |
2003-05-14 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | 1} SHOW SUB PANEL LOCATIONS FOR EACH OFF | | ICE. | | | | 2} PLEASE SHOW ALL CONTINUOUS AT | | 125%. (LIGHTING ETC) | | 215-2,215-3,230-42 | | | | 3} PLEASE LIST REQUIRED SIGN CIRCUITS PE | | R 600-5 | | | | 4} PLEASE SHOW HOW THE BATH RECEPTACLES | | COMPLY WITH 210-8(B).GFI. | | | | 5} PLEASE NOTE THAT PLANS ARE TO | | BE SIGNED, DATED AND SEALED BY AN P.E. | | PER FS/FAC 553-79-6A. | | | | 6} THE PANELS SHOWN ON THE RISER DIAGRAM | | DO NOT LIST THE OCP FOR THE FEEDERS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2003-05-15 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2003-05-15 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2003-05-15 |
Time |
14:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2003-03-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-03-21 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-03-21 |
Time |
14:13 |
Sent To |
|
|
Notes |
2003-03-21 00:00:00 | 1) BUILDING ADDRESS NOT NOTED ON PROPER | | ELEVATION. | | | | 2) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | | | 3) NO INFORMATION PROVIDED ON ANY | | EXISTING EXIT SIGNS OR EMERGENCY | | LIGHTS. | | | | 4) NO INFORMATION CONCERNING FIRE | | EXTINGUISHERS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2003-07-30 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2003-07-23 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2003-07-23 |
Time |
15:26 |
Sent To |
|
|
Notes |
2003-07-30 00:00:00 | TO COMM BD #9 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-05-14 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-14 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-14 |
Time |
11:43 |
Sent To |
|
|
Notes |
2003-05-14 00:00:00 | COMM BOARD #19 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-03-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-03-11 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-03-11 |
Time |
14:01 |
Sent To |
|
|
Notes |
2003-03-11 00:00:00 | TO COMM BOARD #12 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2003-08-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-08-04 |
Time |
11:17 |
Rev Time |
0.10 |
Received By |
pkrauss |
Date |
2003-08-04 |
Time |
11:15 |
Sent To |
|
|
Notes |
2003-08-04 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR | | REVIEW. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2003-04-09 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2003-04-09 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2003-07-31 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-07-31 |
Time |
06:07 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2003-07-31 |
Time |
06:07 |
Sent To |
|
|
Notes |
2003-07-31 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | FLORIDA STATUTES | | | | 1) FROM PREVIOUS REVIEWS: PER TABLE | | 403.1 A DRINKING FOUNTAIN IS REQUIRED. | | ALSO SEE SECTION 410.1 | | 2) IF TOILET ROOM ARE PROVIDED THEN EACH | | PUBLIC AND COMMON USE TOILET ROOM SHALL | | COMPLY WITH 11-4.22 - 11-4.1.3(11). | | THE FOLLOWING INFORMATION NOT SHOWN ON | | PLANS. 11-4.16.5 FLUSH CONTROLS, | | 11-4.19.2 HEIGHT & CLEARANCES, 11-4.19.3 | | CLEAR FLOOR SPACE, 11-4.19.4 EXPOSED | | PIPES AND SURFACES, 11-4.19.5 FAUCETS, | | AND 11-4.22.3 AN UNOBSTRUCTED TURNING | | SPACE. | | 3) NEW COMMENT: SHT 2, DOORS SHALL NOT | | SWING INTO THE CLEAR FLOOR SPACE REQUIR- | | ED FOR ANY FIXTURE. | | 4) NEW COMMENT: SEE ATTACHED SHEET FOR | | ENGINEER'S TITLE BLOCK. 61G15-23.002 | | 5) FLORIDA STATUTE 553.80(2)(B) | | SEE ATTACHED SHEET. - INFORMATIONAL | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2003-05-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-05-16 |
Time |
08:42 |
Rev Time |
0.50 |
Received By |
sgraham |
Date |
2003-05-16 |
Time |
08:42 |
Sent To |
|
|
Notes |
2003-05-16 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) FROM PREVIOUS REVIEW: PER TABLE 403.1 | | A DRINKING FOUNTAIN IS REQUIRED. ALSO | | SEE SECTION 410.1 | | 2) FROM PREVIOUS REVIEW: IF TOILET ROOMS | | ARE PROVIDED THEN EACH PUBLIC AND COMMON | | USE TOILET ROOM SHALL COMPLY WITH SEC | | 11-4.22. - 11-4.1.3(11).PLEASE SUBMIT | | DETAILS FOR COMPLIANCE WITH 11-4.22 AND | | ALL SUBSECTIONS. | | 3) FROM PREVIOUS REVIEW: IF BATHING | | ROOMS ARE PROVIDED, THEN EACH PUBLIC AND | | COMMON USE BATHROOM SHALL COMPLY WITH | | 11-4.23. - 11-4.1.3(11) - PLEASE SUBMIT | | DETAILS FOR COMPLIANCE OF 11-4.23 AND | | ALL SUBSECTIONS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-03-22 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-05-14 |
Time |
16:55 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2003-03-22 |
Time |
09:49 |
Sent To |
|
|
Notes |
2003-03-22 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) SUBMIT A SANITARY RISER DIAGRAM AND | | A WATER RISER DIAGRAM PER FBC ADMIN. | | CODE SEC. 104.3.1.1 | | 2) PER TABLE 403.1 A DRINKING FOUNTAIN | | IS REQUIRED. ALSO SEE SECTION 401.1 | | 3) IF TOILET ROOMS ARE PROVIDED THEN | | EACH PUBLIC AND COMMON USE TOILET ROOM | | SHALL COMPLY WITH 11-4.22. 11-4.1.3(11) | | PLEASE SUBMIT DETAILS FOR COMPLIANCE | | WITH 11-4.22 AND ALL SUBSECTIONS. | | 4) IF BATHING ROOMS ARE PROVIDED, THEN | | EACH PUBLIC AND COMMON USE BATHROOM | | SHALL COMPLY WITH 11-4.23. 11-4.1.3(11) | | PLEASE SUBMIT DETAILS FOR 11-4.23 AND | | ALL SUBSECTIONS. | | 5) BACKFLOW REQUIRED ON WATER SERVICE. | | 6) PLEASE PROVIDE CALCULATIONS FOR PRIM- | | ARY AND SECONDARY ROOF DRAINS PER SEC'S | | 1106 AND 1107. INCLUDE 1/2 AREA OF ALL | | VERTICAL WALLS INCLUDING PARAPETS. SHOW | | LOCATION OF ALL PRIMARY AND SECONDARY | | ROOF DRAINS, AND INDICATE SQUARE FOOTAGE | | DRAINED BY EACH, | | 7) PROVIDE A STORM RISER DIAGRAM. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-03-11 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2003-03-11 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
I |
|
Notes |
|
|