Plan Review Stops For Permit 03030459 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2003-05-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-05-07 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-05-07 |
Time |
10:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2003-05-01 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-05 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-05-01 |
Time |
09:06 |
Sent To |
|
|
Notes |
2003-05-01 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6716 | | E-MAIL: [email protected] | | | | MODEL D | | | | 1) SHEET S-1, ROOF FRAMING PLAN.THE | | ROOF TRUSS ANCHOR AT THE WALL BETWEEN | | THE ATRIUM AND BEDROOM 2 IS CALLED UP AS | | DETAIL 5/S-4. SHEET S-4 HAS NO DETAIL 5. | | AMEND THE PLANS TO CORRELATE THE DETAILS | | IF THE REFERENCE ON THE ROOF FRAMING | | PLAN SHOULD BE TO DETAIL 4/S-4, AS DRAWN | | ON SHEET S-4, THEN THE COPIES OF | | SHEET S-1 MAY BE HAND-CORRECTED BY THE | | ENGINEER OF RECORD.SUCH A CORRECTION | | SHALL BE SIGNED AND DATED BY THE | | ENGINEER. | | | | 2) SHEET S-1, ROOF FRAMING PLAN.THE | | HIP JACK ANCHOR AT THE PATIO COLUMN IS | | CALLED UP AS CONNECTOR MARK 8.THE | | CONNECTOR SCHEDULE ON S-2 DOES NOT | | INCLUDE A MARK 8.AMEND THE PLANS. | | | | 3) NOTE: IF SHEET S-2 IS TO BE AMENDED, | | PLEASE CORRECT THE CONNECTOR MARK 4 | | (SIMPSON MGT) ALLOWABLE UPLIFT TO 3965# | | (CURRENTLY SHOWN AS 4200#). | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | TELEPHONE: (561) 805 6716ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-04-10 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2003-03-31 |
Time |
17:36 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-04-10 |
Time |
09:54 |
Sent To |
|
|
Notes |
2003-04-10 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | MODEL D | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | 1) SHEET S-2, CONNECTOR SCHEDULE. | | MARK 3, LVS26 IS NOT A VALID SIMPSON | | REFERENCE.SHOULD THIS BE LUS26?AMEND | | THE SCHEDULE. | | | | 2) SHEET S-1, ROOF FRAMING PLAN.ADD A | | KEY, FOR THE TRUSS ANCHOR REFERENCE | | ANNOTATION, TO CONFIRM IF1MEANS | | CONNECTOR MARK 1, AND IF 'U' IS THE | | DESIGN UPLIFT CAPACITY REQUIRED.WHAT | | IS THE VALUE STATED AS 'R', IS IT THE | | REQUIRED LATERAL LOAD CAPACITY (EITHER | | F1 OR F2)? | | | | 3) SHEET S-2, CONNECTOR SCHEDULE.AMEND | | THE SCHEDULE TO INCLUDE THE UPLIFT AND | | THE LATERAL LOAD CAPACITY FOR THE | | SELECTED ANCHORS AND LUMBER GRADE. | | | | 4) FBC TABLE 600THE GLASS BLOCK WINDOW | | IS ON THE PROPERTY LINE.AMEND THE | | PLANS TO SHOW THE REQUIREMENT FOR A ONE- | | HOUR FIRE-RATED ASSEMBLY. | | | | 5) SHEET S3, PLYWOOD NAILING DETAIL. | | AMEND '10/32 CDX PLYWOOD' TO READ | | '19/32 CDX PLYWOOD'. | | | | 6) PROVISO - ROOF TILE PRODUCT APPROVAL | | NOA# 99-1012.02 HAS EXPIRED.SUBMIT A | | CURRENT PRODUCT APPROVAL. | | | | 7) PROVISO - OUTSWING STEEL DOUBLE DOOR | | PRODUCT APPROVAL NOA# 99-0311.03 HAS | | EXPIRED.SUBMIT A CURRENT PRODUCT | | APPROVAL. | | | | 8) PROVISO - ALUMINUM SLIDING GLASS | | DOOR PRODUCT APPROVAL NOA# 98-1228.01 | | HAS EXPIRED.SUBMIT A CURRENT PRODUCT | | APPROVAL. | | | | 9) PROVISO - ALUMINUM TUBE MULLION | | PRODUCT APPROVAL NOA# 99-0310.01 HAS | | EXPIRED.SUBMIT A CURRENT PRODUCT | | APPROVAL. | | | | 10) PROVISO - SINGLE HUNG WINDOW PRODUCT | | APPROVAL NOA# 98-1222.02 HAS EXPIRED. | | SUBMIT A VALID PRODUCT APPROVAL. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2003-09-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-09-25 |
Time |
06:23 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2003-09-25 |
Time |
06:23 |
Sent To |
|
|
Notes |
2003-09-25 00:00:00 | FLD LT LTR |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2003-09-22 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-24 |
Time |
16:36 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2003-09-22 |
Time |
20:05 |
Sent To |
|
|
Notes |
2003-09-22 00:00:00 | ************** UNSAT ************* | | | | 1)NOTE: PLEASE SEE FS 471.025/ FAC | | 61G15.23.002 | | PLEASE HAVE ALL LETTERS BE ORIGINAL | | DATE, SIGNATURE. | | | | 2)NOTE: PLEASE ALSO SEE THE LETTERS ARE | | ADDRESSED TO PAM BEACH COUNTY PZB. | | WE ARE CITY OF WEST PALM BEACH | | CONSTRUCTION SERVICES DEPT. | | | | | | 3)NOTE; CMB MUST HAVE CERTIFICATE OF | | AUTHORIZATION # ON TITLE BLOCK PER | | 61G15-23.002 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2003-09-02 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-22 |
Time |
15:26 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2003-09-02 |
Time |
12:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-04-24 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2003-08-19 |
Time |
09:14 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2003-04-24 |
Time |
06:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-03-21 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-17 |
Time |
16:29 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2003-03-21 |
Time |
14:21 |
Sent To |
P |
|
Notes |
2003-03-21 00:00:00 | **************** UNSAT ************ | | | | 1)NOTE: PLEASE SEE NOTES # 03022281 | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2003-09-24 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-24 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-09-24 |
Time |
16:36 |
Sent To |
E |
|
Notes |
2003-09-24 00:00:00 | TO DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2003-09-22 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-22 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-09-22 |
Time |
15:26 |
Sent To |
E |
|
Notes |
2003-09-22 00:00:00 | TO DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2003-08-19 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2003-08-19 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
bstaples |
Date |
2003-08-19 |
Time |
09:14 |
Sent To |
E |
|
Notes |
2003-08-19 00:00:00 | TO DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2003-05-05 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-05 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-05 |
Time |
11:00 |
Sent To |
B |
|
Notes |
2003-05-05 00:00:00 | RB DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-04-17 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-17 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-17 |
Time |
16:29 |
Sent To |
E |
|
Notes |
2003-04-17 00:00:00 | DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-03-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-03-06 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-03-06 |
Time |
13:39 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-03-31 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2003-03-22 |
Time |
08:47 |
Rev Time |
0.50 |
Received By |
rregueir |
Date |
2003-03-31 |
Time |
17:36 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2003-03-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-03-21 |
Time |
14:21 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2003-03-22 |
Time |
08:47 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-03-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-03-06 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
P |
|
Notes |
|
|