Plan Review Details - Permit 03030326
Plan Review Stops For Permit 03030326
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-12 Cont ID  
Sent By hpiskura Date 2003-03-12 Time 10:45 Rev Time 0.00
Received By hpiskura Date 2003-03-12 Time 09:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-06 Cont ID  
Sent By dpalmer Date 2003-05-06 Time 07:02 Rev Time 0.50
Received By dpalmer Date 2003-05-06 Time 07:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-17 Cont ID  
Sent By dpalmer Date 2003-03-17 Time 06:20 Rev Time 0.33
Received By dpalmer Date 2003-03-17 Time 06:19 Sent To  
Notes
2003-03-17 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SEE TWO DIFFERENT AIC
 RATINGS FOR PANEL. RISER SHOWS 22K AND
 PANEL SHOWS 10K. PLEASE ALSO SUBMIT AIC
 RATING FOR NEW MAIN DISC PER 110-9.
  
 2)NOTE; PLEASE CLARIFY LOAD CALCS,
 PLEASE SEE TWO DIFFERENT LOADS SHOWN?
  
 3)NOTE: PLEASE CLARIFY USE OF MAINT BLDG
 AND ANY POSSIBLE LOCATIONS PER ART 500.
 511?
  
 PLEASE NOTE, IT WAS REDLINED ONPLAN,
 AS PER LOCAL AMEDMENTS 215-5, FEEDERS
 FOR 277/480V ARE BROWN,PURPLE YELLOW(FYI
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-03-11 Cont ID  
Sent By mamini Date 2003-03-11 Time 09:33 Rev Time 0.50
Received By mamini Date 2003-03-11 Time 09:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-05-27 Cont ID  
Sent By nmccray Date 2003-05-27 Time 14:21 Rev Time 0.00
Received By nmccray Date 2003-05-27 Time 14:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-03-28 Cont ID  
Sent By mcarsill Date 2003-03-28 Time 13:22 Rev Time 0.00
Received By mcarsill Date 2003-03-28 Time 13:22 Sent To  
Notes
2003-03-28 00:00:001) PLEASE EXPLAIN EXIT SIGNS AND
 EMERGENCY LIGHTS NEAR OVERHEAD ROLLING
 DOORS. THESE DOORS CANNOT BE USED FOR
 EXITING. PLEASE ADVISE.
  
 2) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 3) PLEASE INDICATE LOCATIONS OF FIRE
 EXTINGUISHERS.
  
 4) WHAT TYPES OF MACHINES OR PROCESSES
 WILL BE STORED OR CONDUCTED IN THE
 BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-02 Cont ID  
Sent By shernand Date 2003-06-02 Time 16:08 Rev Time 0.00
Received By shernand Date 2003-06-02 Time 16:08 Sent To P
Notes
2003-06-02 00:00:00KSTEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2003-04-29 Cont ID  
Sent By sgraham Date 2003-05-09 Time 14:14 Rev Time 0.00
Received By shernand Date 2003-04-29 Time 09:26 Sent To  
Notes
2003-04-29 00:00:00COMM BOARD #14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 14:09 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 14:09 Sent To  
Notes
2003-03-06 00:00:00TO COMM BOARD #13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-03 Cont ID  
Sent By pkrauss Date 2003-05-03 Time 09:03 Rev Time 0.20
Received By pkrauss Date 2003-05-03 Time 09:03 Sent To  
Notes
2003-05-03 00:00:00PLANS APPROVED 3-18-03 - NO CHANGES
 ON THE RESUB.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-18 Cont ID  
Sent By pkrauss Date 2003-03-18 Time 07:48 Rev Time 0.35
Received By pkrauss Date 2003-03-18 Time 07:48 Sent To  
Notes
2003-03-18 00:00:00PROVISO:
  
 IT APPEARS THAT ADDITIONAL MANUAL J
 SIZING CALCULATIONS WHERE SUBMITTED THAT
 DO NOT PERTAIN TO THIS PARTICULAR
 SPACE.PLEASE REMOVE CALCULATIONS THAT
 ARE NOT FOR THIS SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-06-09 Cont ID  
Sent By kstevens Date 2003-06-09 Time 15:34 Rev Time 1.25
Received By kstevens Date 2003-06-09 Time 15:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-05-27 Cont ID  
Sent By shernand Date 2003-06-02 Time 16:08 Rev Time 0.33
Received By kstevens Date 2003-05-27 Time 08:57 Sent To  
Notes
2003-05-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: SHT A1, SHOWER
 SHALL COMPLY WITH SECTION 11-4.21 AND
 ALL SUBSECTIONS. NO DETAIL GIVEN FOR
 SECTIONS 11-4.21.5 (CONTROLS), 11-4.21.6
 (SHOWER UNIT), 11-4.21.7 (CURB). PLEASE
 PROVIDE DETAILS.
 2) FROM PREVIOUS REVIEW: SHT P-1, I
 ACKNOWLAGE RESPONSE FOR THE RELIEF VALVE
 FOR THERMAL EXPANSION PROTECTION, BUT
 A VACUUM RELIEF VALVE IS REQUIRED FOR
 ALL BOTTON FED WATER HEATERS PER SECTION
 504.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-21 Cont ID  
Sent By kstevens Date 2003-03-21 Time 12:17 Rev Time 1.00
Received By kstevens Date 2003-03-21 Time 12:17 Sent To  
Notes
2003-03-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A1, SHOWER SHALL COMPLY WITH
 SECTION 11-4.21 AND ALL SUBSECTIONS.
 PLEASE PROVIDE DETAILS.
 2) SHT P1 WATER HEATER DETAIL, THE
 RELIEF VALVE SHALL NOT BE USED AS A
 MEANS OF CONTROLLING THERMAL EXPANSION.
 SECTION 504.5. PLEASE SHOW EXPANSION
 TANK TO COMPLY WITH 607.3.2
 3) BACKFLOW PREVENTOR REQUIRED ON WATER
 SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-09 Cont ID  
Sent By sgraham Date 2003-05-09 Time 14:14 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***