Plan Review Details - Permit 03030318
Plan Review Stops For Permit 03030318
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-06 Cont ID  
Sent By jwitmer Date 2004-04-06 Time 17:02 Rev Time 0.55
Received By jwitmer Date 2004-04-06 Time 16:54 Sent To  
Notes
2004-04-06 00:00:00BUILDING PLAN REVIEW
 REV#2 OKJW
 REVISION # 2 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-05 Cont ID  
Sent By jwitmer Date 2003-05-05 Time 08:40 Rev Time 1.45
Received By jwitmer Date 2003-05-05 Time 07:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-07 Cont ID  
Sent By hmoser Date 2003-04-07 Time 14:40 Rev Time 3.00
Received By jwitmer Date 2003-04-07 Time 14:51 Sent To  
Notes
2003-04-07 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03030318
 ADD: 1009 BANYAN BLVD
 CONT: BURKHARDT CONSTRUCTION
 TEL: (561)659-1400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 S-4 FOUNDATION REQUIREMENTS (1) RECOMEN-
 DATIONS ON SOILS AND FOUNDATIONS INVEST-
 IGATION PREPAARED BY AND APPROVED TEST-
 ING LABORATORY PRIOR TO FOUNDATION
 WORK.
  
 2)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. NO INFORMATION IS SUBMITTED ON
 THE SITE PLAN TO GET FROM THE HANDICAP-
 PED PARKING TO THE BUILDING.
  
 3) 11-4.1.6(H) IF A PARTICULAR
 ENTRANCE IS NOT MADE ACCESSIBLE, APPRO-
 PRIATE ACCESSIBLE SIGNAGE INDICATING THE
 LOCATION OF THE NEAREST ACCESSIBLE
 ENTRANCE(S) SHALL BE INSTALLED AT OR
 NEAR THE INACCESSIBLE ENTRANCE, SUCH
 THAT A PERSON WITH DISABILITIES WILL
 NOT BE REQUIRED TO RETRACE THE APPROACH
 ROUTE FROM THE INACCESSIBLE ENTRANCE.
  
 1003.2.7 CHANGES IN LEVEL IN MEANS OF
 EGRESS SHALL BE EITHER BY A RAMP OR A
 STAIR WHERE THE ELEVATION DIFFERENCE IS
 MORE THAN 21". INDICATE HANDICAPPED
 EGRESS, SEE 1012.1.2 EGRESS DOORS TO
 BE SIDE SWINGING.
  
 4)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 FIRST FLOOR RESTROOM DOOR AND EXTERIOR
 DOOR, INROOM 103 BY ROOM 104.
  
 5)11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 STRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
  
 6) 11-4.1.3(9)IN BUILDINGSOR FACILITIES,
 OR PORTIONS OF BUILDINGS OR FACILITIES,
 REQUIRED TO BE ACCESSIBLE, ACCESSIBLE
 MEANS OF EGRESS SHALL BE PROVIDED IN THE
 SAME NUMBER AS REQUIRED FOR EXITS REQUIR
 ED BY LOCAL BUILDING/ LIFE SAFETY REGU-
 LATIONS. WHERE A REQUIRED EXIT FROM AN
 OCCUPIABLE LEVEL ABOVE OR BELOW A LEVEL
 OF EXIT DISCHARGE IS NOT ACCESSIBLE,
 AN AREA OF RESCUE ASSISTANCE SHALL BE
 PROVIDED ON EACH SUCH LEVEL.
  
 7) EXTERIOR EXIT STAIRWAYS 1006.2.4
 EXTERIOR STAIRS SHALL BE SEPERATED FROM
 THE INTERIOR OF THE BUILDING BY WALLS
 WITH A FIRE RESISTANCE RATING OF NOT
 LESS THAN 1 HR WITH FIXED OR SELF-CLOS-
 ING OPENING PROTECTIVES OF NOT LESS THAN
 1-HR.
 OPENINGS WITHIN THE 10' HORIZONTAL EXTEN
 TIONOFTHE PROTECTED WALLS BEYOND THE
 STAIRWAY SHALL BE EQUIPED WITH FIXED
 3/4 HR ASSEMBLIES. SEE ATTACHMENT.
  
 8) SHEET S-4 LIVE LOADS SEE TABLE 1604.1
 FLOOR LOADS LIVE:
 OFFICES50 LBS
 CORRIDORS80 LBS
  
 9) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) MULLIONS
 B) LOUVERS
 C) ROOFING REPORT FOR-75 PRESSURE
  
 10) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 11) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 12) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 13)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 14) DESIGN PROFESSIONALS TO INDICATE ON
 THE STEEL DOOR APPLICATION IF TYPE I APP
 LICATION OR IF TYPE 2 APPLICATION.
  
 15) SHEET S-1 DOESN'T INDICATE WHAT IS
 TO OCCUR THAT THE OVERHEAD DOOR WHERE
 BLOCK IS REMOVED, COLUMN?
  
 16)1503.4 ROOF DRAINS UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF
 DRAINS SHALL BE INSTALLED AT THE LOWEST
 POINT OF THE ROOF. WHERE REQUIRED FOR
 ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED
 AS DETERMINED BY THE ROOF SLOPE AND CON-
 TRIBUTING ROOF AREA.
  
 17)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 18) WHAT IS TO BE STORED IN ROOM # 103?
  
 19) WHAT WILL THE USAGE BE FOR ROOM
 # 104?
  
 20)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-26 Cont ID  
Sent By dpalmer Date 2004-04-26 Time 10:14 Rev Time 0.33
Received By dpalmer Date 2004-04-26 Time 10:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-20 Cont ID  
Sent By dpalmer Date 2004-04-20 Time 13:39 Rev Time 0.50
Received By dpalmer Date 2004-04-20 Time 13:39 Sent To  
Notes
2004-04-20 00:00:00******** UNSAT *************
  
 1)NOTE: PLEASE PROVIDE ALL LICENSE #'S
 REQ'D ON TITLE BLOCK FOR FAC 61G15-23.00
 -2. FS 471.023
 THIS HAS BEEN PREVIOUS NOTED FOR OTHER
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-07 Cont ID  
Sent By dpalmer Date 2003-04-07 Time 04:47 Rev Time 0.50
Received By dpalmer Date 2003-04-07 Time 04:40 Sent To  
Notes
2003-04-07 00:00:00PLANS NOTED/REDLINED FOR
 250-30/450-13
 COLOR CODE FOR 277V FEEDERS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-06 Cont ID  
Sent By nmccray Date 2004-04-06 Time 13:41 Rev Time 0.00
Received By nmccray Date 2004-04-06 Time 13:41 Sent To  
Notes
2004-04-06 00:00:00REVISION DATED 03-15-04 SHEETS A-1, A-2
 AND E-3

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-03-31 Cont ID  
Sent By nmccray Date 2003-03-31 Time 11:43 Rev Time 0.00
Received By nmccray Date 2003-03-31 Time 11:43 Sent To  
Notes
2003-03-31 00:00:00PROVISO:
 1) PLANS BUILDING DATA NOTES INDICATE
 NFPA 101 LIFE SAFETY CODE 1997 EDITION.
 MUST COMPLY WITH 2000 EDITION.
  
 2) ELEVATOR MUST COMPLY WITH CHAPTER 9.4
 NFPA 101 LIFE SAFETY CODE 2000 EDITION.
  
 3) SEPARATE PLAN AND PERMIT IS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-04-05 Time 14:56 Rev Time 0.00
Received By csiegber Date 2004-04-05 Time 14:56 Sent To  
Notes
2004-04-05 00:00:00TO COMM BD#12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 11:06 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 11:06 Sent To M
Notes
2004-01-16 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-27 Cont ID  
Sent By shernand Date 2003-05-27 Time 17:01 Rev Time 0.00
Received By shernand Date 2003-05-27 Time 17:01 Sent To P
Notes
2003-05-27 00:00:00KSTEVENS DESK, RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-29 Time 16:59 Rev Time 0.00
Received By shernand Date 2003-04-29 Time 16:58 Sent To  
Notes
2003-04-29 00:00:00COMM BOARD #5

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2004-04-06 Cont ID  
Sent By pkrauss Date 2004-04-06 Time 14:24 Rev Time 0.15
Received By pkrauss Date 2004-04-06 Time 14:17 Sent To  
Notes
2004-04-06 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVISION

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-01-23 Cont ID  
Sent By pkrauss Date 2004-01-23 Time 06:52 Rev Time 0.40
Received By pkrauss Date 2004-01-23 Time 06:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-06 Cont ID  
Sent By csiegber Date 2004-01-16 Time 11:06 Rev Time 0.35
Received By pkrauss Date 2003-05-06 Time 13:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-04-07 Cont ID  
Sent By hmoser Date 2003-04-07 Time 14:40 Rev Time 0.75
Received By hmoser Date 2003-04-07 Time 14:39 Sent To B
Notes
2003-04-07 00:00:00PLAN DENIED
 1) REFER TO SECTION 606 FBC.SMOKE
 DETECTION FOR SPLIT A/C SYSTEM
 2) CAN NOT READ SPLIT SYSTEM SCHEDUAL
 3) DO NOT UNDERSTAND NOTE #7 ON PAGE M-1
 4) THERE IS NO NOTE #9 ON PAGE M-2
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8221

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-06-02 Cont ID  
Sent By kstevens Date 2003-06-02 Time 10:32 Rev Time 0.75
Received By kstevens Date 2003-05-31 Time 08:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-27 Time 17:01 Rev Time 1.25
Received By kstevens Date 2003-05-15 Time 15:25 Sent To  
Notes
2003-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 DRINKING FOUNTAIN DETAIL,
 PLEASE INDICATE SPOUT HEIGHT PER SECTION
 11-4.15.2.
 2) SHT A-3 DO ROOF DRAIN CALCULATIONS
 INCLUDE 1/2 AREA OF ALL VERTICAL WALLS
 AND AREA OF ANY ROOFS THAT DRAIN ON TO
 THE ROOF FROM ABOVE AS REQUESTED?
 3) SHT P-2 WATER HEATER DETAIL, SECTION
 504.2 VACUUM RELIEF HAS NOT BEEN ADDRESS
 ED. THERE ARE 3 TYPES OF VALVES REQD.
 4) SHTS P-2 & P-3 SERVICE SINK SHALL BE
 SHOWN ON PLUMBING PLANS AND SANITARY
 RISER DIAGRAM AND WATER RISER DIAGRAM TO
 REFLECT FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By kstevens Date 2003-04-03 Time 15:32 Rev Time 1.25
Received By kstevens Date 2003-04-03 Time 15:31 Sent To  
Notes
2003-04-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A1 ENLARGED RESTROOM PLAN. LAV TO
 BE 1'3" OFF WALL. WATER CLOSET SHALL BE
 17" TO 19" MEASURED TO THE TOP OF THE
 TOILET SEAT. 11-4.16.3
 2) SHT A2 DETAIL #3, LAV TO BE 1'3" OFF
 WALL TO CENTER. BREAK ROOM (207) SINK
 TO COMPLY WITH 11-4.24 AND ALL SUBSECT-
 IONS. PLEASE SUBMIT DETAILS. - PLEASE
 SUBMIT DETAILS FOR DRINKING FOUNTAIN TO
 SHOW COMPLIANCE WITH 11-4.15 AND ALL SUB
 SECTIONS. SHOW CLEAR FLOOR SPACE.
 3) SHT A3 PROVIDE CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SEC'S.
 1106, & 1107. SHOW 1/2 AREA OF ALL VERT-
 ICAL WALLS INCLUDING PARAPETS. INCLUDE
 AREAS OF ALL ROOFS DRAINING FROM ABOVE.
 SHOW SIZE OF ALL OPENINGS FOR DOWNSPOUTS
 - SCUPPER
 SHOW SIZE OF ALL DOWNSPOUTS
 4) SHT P1 WILL THERE BE CHEMICALS STORED
 AND USED? IF SO MSDS SHEETS WILL BE REQD
 AND EMERGENCY SHOWER MAY BE REQUIRED DE-
 PENDING ON MSDS SHEETS.
 5) RPZ BACKFLOW REQUIRED ON BLDG WATER
 SERVOCE.
 6) SHT P2 WATER HEATER DETAIL. SECTION
 504.2 VACUUM RELIEF REQUIRED. SECTION
 607.3.2 THERMAL EXPANSION CONTROL REQD.'
 SECTION 504.5 THE RELIEF VALVE SHALL NOT
 BE USED AS MEANS OF THERMAL EXPANSION
 CONTROL.
 7) A SERVICE SINK IS REQUIRED PER TABLE
 403.1 (STORAGE)