Plan Review Details - Permit 03030005
Plan Review Stops For Permit 03030005
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-05-07 Cont ID  
Sent By rbrown Date 2003-05-07 Time 14:22 Rev Time 0.00
Received By rbrown Date 2003-05-07 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-01 Cont ID  
Sent By shernand Date 2003-05-05 Time 11:51 Rev Time 0.00
Received By rbrown Date 2003-05-01 Time 15:48 Sent To  
Notes
2003-05-01 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 MODEL D (REVERSE)
  
 1) SHEET S-1, ROOF FRAMING PLAN.THE
 ROOF TRUSS ANCHOR AT THE WALL BETWEEN
 THE ATRIUM AND BEDROOM 2 IS CALLED UP AS
 DETAIL 5/S-4. SHEET S-4 HAS NO DETAIL 5.
 AMEND THE PLANS TO CORRELATE THE DETAILS
 IF THE REFERENCE ON THE ROOF FRAMING
 PLAN SHOULD BE TO DETAIL 4/S-4, AS DRAWN
 ON SHEET S-4, THEN THE COPIES OF
 SHEET S-1 MAY BE HAND-CORRECTED BY THE
 ENGINEER OF RECORD.SUCH A CORRECTION
 SHALL BE SIGNED AND DATED BY THE
 ENGINEER.
  
 2) SHEET S-1, ROOF FRAMING PLAN.THE
 HIP JACK ANCHOR AT THE PATIO COLUMN IS
 CALLED UP AS CONNECTOR MARK 8.THE
 CONNECTOR SCHEDULE ON S-2 DOES NOT
 INCLUDE A MARK 8.AMEND THE PLANS.
  
 3) NOTE: IF SHEET S-2 IS TO BE AMENDED,
 PLEASE CORRECT THE CONNECTOR MARK 4
 (SIMPSON MGT) ALLOWABLE UPLIFT TO 3965#
 (CURRENTLY SHOWN AS 4200#).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-09 Cont ID  
Sent By dpalmer Date 2003-04-24 Time 12:46 Rev Time 0.00
Received By rbrown Date 2003-04-09 Time 16:13 Sent To  
Notes
2003-04-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 MODEL D REVERSE
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) SHEET S-2, CONNECTOR SCHEDULE.
 MARK 3, LVS26 IS NOT A VALID SIMPSON
 REFERENCE.SHOULD THIS BE LUS26?AMEND
 THE SCHEDULE.
  
 2) SHEET S-1, ROOF FRAMING PLAN.ADD A
 KEY, FOR THE TRUSS ANCHOR REFERENCE
 ANNOTATION, TO CONFIRM IF1MEANS
 CONNECTOR MARK 1, AND IF 'U' IS THE
 DESIGN UPLIFT CAPACITY REQUIRED.WHAT
 IS THE VALUE STATED AS 'R', IS IT THE
 REQUIRED LATERAL LOAD CAPACITY (EITHER
 F1 OR F2)?
  
 3) SHEET S-2, CONNECTOR SCHEDULE.AMEND
 THE SCHEDULE TO INCLUDE THE UPLIFT AND
 THE LATERAL LOAD CAPACITY FOR THE
 SELECTED ANCHORS AND LUMBER GRADE.
  
 4) FBC TABLE 600THE GLASS BLOCK WINDOW
 IS ON THE PROPERTY LINE.AMEND THE
 PLANS TO SHOW THE REQUIREMENT FOR A ONE-
 HOUR FIRE-RATED ASSEMBLY.
  
 5) SHEET S3, PLYWOOD NAILING DETAIL.
 AMEND '10/32 CDX PLYWOOD' TO READ
 '19/32 CDX PLYWOOD'.
  
 6) PROVISO - ROOF TILE PRODUCT APPROVAL
 NOA# 99-1012.02 HAS EXPIRED.SUBMIT A
 CURRENT PRODUCT APPROVAL.
  
 7) PROVISO - OUTSWING STEEL DOUBLE DOOR
 PRODUCT APPROVAL NOA# 99-0311.03 HAS
 EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 8) PROVISO - ALUMINUM SLIDING GLASS
 DOOR PRODUCT APPROVAL NOA# 98-1228.01
 HAS EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 9) PROVISO - ALUMINUM TUBE MULLION
 PRODUCT APPROVAL NOA# 99-0310.01 HAS
 EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 10) PROVISO - SINGLE HUNG WINDOW PRODUCT
 APPROVAL NOA# 98-1222.02 HAS EXPIRED.
 SUBMIT A VALID PRODUCT APPROVAL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-09-02 Cont ID  
Sent By dpalmer Date 2003-09-02 Time 13:31 Rev Time 0.25
Received By dpalmer Date 2003-09-02 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-24 Cont ID  
Sent By bstaples Date 2003-08-19 Time 09:17 Rev Time 0.25
Received By dpalmer Date 2003-04-24 Time 12:46 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 16:40 Rev Time 0.25
Received By dpalmer Date 2003-03-17 Time 15:48 Sent To P
Notes
2003-03-17 00:00:00************** UNSAT *****************
  
 PLEASE SEE NOTES UNDER # 03022281
 MOST NOTES ARE THE SAME.
  
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-19 Cont ID  
Sent By bstaples Date 2003-08-19 Time 09:16 Rev Time 0.00
Received By bstaples Date 2003-08-19 Time 09:16 Sent To E
Notes
2003-08-19 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 11:51 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 11:51 Sent To B
Notes
2003-05-05 00:00:00RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 16:40 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 16:40 Sent To E
Notes
2003-04-17 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-04 Cont ID  
Sent By dpalmer Date 2003-03-04 Time 08:36 Rev Time 0.00
Received By dpalmer Date 2003-03-04 Time 08:36 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-22 Cont ID  
Sent By jleech Date 2003-03-18 Time 18:13 Rev Time 0.25
Received By hmoser Date 2003-03-22 Time 13:19 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-18 Cont ID  
Sent By dpalmer Date 2003-03-17 Time 15:49 Rev Time 0.25
Received By jleech Date 2003-03-18 Time 18:12 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-04 Cont ID  
Sent By dpalmer Date 2003-03-04 Time 08:36 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***