Plan Review Details - Permit 03022335
Plan Review Stops For Permit 03022335
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-02-05 Cont ID  
Sent By shill Date 2004-02-05 Time 12:53 Rev Time 1.00
Received By shill Date 2004-02-05 Time 12:52 Sent To  
Notes
2004-02-05 00:00:00REVISION A4 & A5 1/27/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-01-28 Time 14:26 Rev Time 1.00
Received By shill Date 2004-01-22 Time 10:38 Sent To  
Notes
2004-01-22 00:00:00*****CORRECTIONS*****
 *****REVISION*******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEE PREVIOUS LISTS, 9/16 #6 AND
 12/17 #4.WOOD-TO-WOOD CONNECTORS USED
 IN A WOOD-TO-MASONRY APPLICATION REQUIRE
 EITHER DOCUMENTATION FROM THE
 MANUFACTURER OR CALCULATIONS FROM THE
 DESIGNER.SEE ALSO ATTACHED FS553.80(2)
 (B).A 4X PLAN REVIEW FEE HAS BEEN
 CHARGED AS PER FLORIDA STATUTE AND WILL
 BE CHARGED EACH TIME THE PLAN IS
 RESUBMITTED WITHOUT THE REQUIRED
 INFORMATION.
  
 2.)DO NOT BRING IN REVISIONS AS
 SUBMITTALS AT THE FRONT COUNTER.
 A BZ WAS ISSUED FOR THE LAST REVISION.
 PAY ALL FEES BEFORE RESUBMITTAL. RETURN
 THE OLD BZ WHICH WAS NOT PAID.NEW
 BZ235306, $1333.28 ATTACHED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2003-12-17 Cont ID  
Sent By csiegber Date 2004-01-08 Time 16:50 Rev Time 1.00
Received By shill Date 2003-12-17 Time 11:15 Sent To  
Notes
2003-12-17 00:00:00****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE CORRECTION LIST DATED 9/16/03.
 THE PREVIOUS REVISION HAD BEEN ISSUED
 WITH A PROVISO THAT ITEMS #6 AND #7
 AFFECTING SHEETS A4 AND A5 (CONNECTORS)
 BE REVISED.THESE ITEMS WERE NOT
 ADDRESSED PROPERLY.
  
 2.)SEE ITEM #7, THERE ARE STILL
 REFERENCES TO "LONG STRAPS".WHICH
 STRAPS SHOULD BE USED?SPECIFY A
 BRAND AND SPECIFIC CONNECTOR.
  
 3.)SEE PREVIOUS LIST, ITEM #6.THE
 CONNECTORS' DESIGN UPLIFT EXCEEDS THE
 UPLIFT ALLOWED AS PER THE MANUFACTURER.
 SEE ATTACHED.FOR USP, USE THE GREY BAR
 SHOWING NO STRESS INCREASE FOR STEEL.
 FOR MORE INFORMATION, SEE THE USP
 CATALOG PP 6-7 IN REGARDS TO FBC1609.4.
  
 4.)SEE PREVIOUS LIST, ITEM #6.YOU
 HAVE SPECIFIED WOOD-TO-WOOD CONNECTORS
 IN A WOOD-TO-MASONRY APPLICATION. EITHER
 SPECIFY A DIFFERENT CONNECTOR, SUBMIT
 ENGINEERING FROM THE MANUFACTURER
 SHOWING THAT THIS CONNECTOR CAN BE
 USED AND HAS BEEN TESTED IN THIS
 APPLICATION, OR SUBMIT CALCULATIONS
 SHOWING THAT THIS CONNECTOR CAN BE
 USED IN THIS APPLICATION.
  
 5.)ADDITIONAL FEES, $70 (REVISION FEE,
 NO FREE RESUB FOR REVISIONS),BZ231391.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-12-16 Time 10:35 Rev Time 2.00
Received By sthyng Date 2003-10-02 Time 10:22 Sent To  
Notes
2003-10-06 00:00:00****PROVISO****
 SUBMIT REVISION FOR SHEETS A4 AND A5
 BEFORE ROOF FRAMING
  
 ISSUED W/PROVISO AS PER CONTRACTOR'S
 REQUEST
  
 REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-09-16 Cont ID  
Sent By pkrauss Date 2003-10-01 Time 06:44 Rev Time 3.50
Received By sthyng Date 2003-09-15 Time 17:02 Sent To  
Notes
2003-09-15 00:00:00*****CORRECTIONS*****
 *****REVISION******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDITIONAL FEES DUE, $36.26.
 BZ#230485 ATTACHED; PLEASE PAY AT
 CASHIER (INCREASED VALUE, RADON).
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)THE MINIMUM WALL INSULATION AS PER
 THE ENERGY CALCS SUBMITTED IS R5. REVISE
 ALL APPLICABLE DETAILS, INCLUDING
 WINDOW JAMB A2, STEMWALL SECTION A4,
 WALL SECTION A4.
  
 4.)ON THE WALL SECTION, A4, LOWEST
 BUILDING FLOOR ELEVATION SHALL BE A MIN.
 4" ABOVE FINISHED GRADE, CITY OF WEST
 PALM BEACH AMENDMENTS FBC1804.1.7.
  
 5.)WALL SECTION, A4, BOTTOM OF FOOTER
 IS REQUIRED TO BE A MINIMUM OF 12" BELOW
 FINISHED GRADE, FBC1804.1.3.
  
 6.)A5, USP TRUSS TIE DOWN SCHEDULE,
 UPLIFT ON SCHEDULE EXCEEDS MAXIMUM
 IN USP 2003 CATALOG FOR RT-T CONNECTORS.
 TARP HAS BEEN DISCONTINUED.RT-T IS
 A WOOD-TO-WOOD CONNECTOR AND CANNOT BE
 USED IN A WOOD-TO-MASONRY APPLICATION.
 THIS PERMIT WAS ISSUED WITH A PROVISO
 TO SUBMIT A NEW ATTACHMENT SCHEDULE.
 REVISE THE ATTACHMENT SCHEDULE, AND
 SPECIFY ALL ATTACHMENTS INCLUDING
 GIRDERS.
  
 7.)THE ROOF PLAN A5, AND THE KNEE WALL
 SECTION REFER TO A "LONG FLAT STRAP".
 SPECIFY WHICH STRAP IS TO BE USED.
  
 8.) THE PLANS SHOW EXISTING ROOF TRUSSES
 AND GIRDERS WHICH ARE TO BE RELOCATED.
 BE ADVISED THAT TRUSS ENGINEERING MUST
 BE PROVIDED AT THE TIME OF INSPECTION,
 INCLUDING THE EXISTING TRUSSES BEING
 RELOCATED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-13 Cont ID  
Sent By pkrauss Date 2003-09-12 Time 08:39 Rev Time 1.00
Received By sthyng Date 2003-05-13 Time 09:17 Sent To  
Notes
2003-05-13 00:00:00******PROVISO******
 PROVIDE NEW CONNECTOR
 UPLIFT INFORMATION
 BASED ON 2003 CATALOG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-18 Cont ID  
Sent By dpalmer Date 2003-05-05 Time 07:36 Rev Time 4.00
Received By sthyng Date 2003-04-17 Time 12:26 Sent To  
Notes
2003-04-18 00:00:00**********CORRECTIONS************
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 2.) BEFORE A PERMIT TO CONSTRUCT MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.THIS MAY BE DONE AFTER THE
 FINAL PLAN REVIEW, BUT BEFORE A PERMIT
 MAY BE ISSUED.
  
 3.)THE WINDOW JAMB AND DOOR JAMB
 DETAILS REFER TO AN ATTACHMENT SCHEDULE
 WHICH IS NOT ON THE PLAN.ALSO REFERS
 TO A DOOR ATTACHMENT WHICH IS
 INCOMPLETE.
  
 4.)FBC 1918.3.1, GABLE MUST BE
 STRUCTURALLY CONTINUOUS BETWEEN POINTS
 OF LATERAL SUPPORT.PLEASE ADDRESS.
  
 5.)NOTE #5, SHEET A-4, PLYWOOD
 SHEATHING NOTE DOES NOT MEET CITY OF
 WEST PALM BEACH REVISED TABLE 2306.1
 FASTENING SCHEDULE.PROVIDE A CORRECT
 ROOF SHEATHING FASTENING SCHEDULE (SEE
 ATTACHED).
  
 6.)THIS PROPERTY IS LOCATED IN THE A5
 FLOOD ZONE.CITY CODE SECTION 94-545
 REQUIRES THAT THE ADDITION HAVE A
 FINISHED FLOOR ELEVATION OF 6" ABOVE THE
 BASE FLOOD ELEVATION, WHICH IS 7'.THE
 FINISHED FLOOR IS REQUIRED TO BE AT 7'6"
 BUT THE PLAN SHOWS 7'.PLEASE REVISE.
  
 7.)FYI - HUGHES BRAND IS NO LONGER
 AVAILABLE.
  
 8.)SHOW HORIZONTAL REINFORCEMENT
 FOR COLUMNS IN THE WALL SECTION.
  
 9.)THE BOND BEAM IS REFERRED TO AS
 BOTH A SINGLE AND DOUBLE COURSE.PLEASE
 CLARIFY.
  
 10.)ON THE ENERGY CALC FORM, SIGN
 THE OWNER/AGENT LINE ON BOTH COPIES.
  
 11.)ADDITIONAL FEES REQUIRED.
  
 IF YOU HAVE ANY QUESTION, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-04-20 Cont ID  
Sent By dpalmer Date 2004-04-20 Time 11:27 Rev Time 50.00
Received By dpalmer Date 2004-04-20 Time 11:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-09-26 Cont ID  
Sent By csiegber Date 2004-04-16 Time 14:27 Rev Time 0.75
Received By dpalmer Date 2003-09-26 Time 09:41 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-09-24 Time 14:44 Rev Time 0.00
Received By dpalmer Date 2003-08-25 Time 13:30 Sent To P
Notes
2003-08-25 00:00:00**************** UNSAT *************
  
 PLEASE SEE NOTES SET FORTH FROM ORIGINAL
 PROVISO. PLEASE SEE THAT SOME ITEMS
 WERE NOT CORRECTED.
  
 1)NOTE: PLEASE SEE 250-66 FOR GROUNDING
 ELECTRODE CONDUCTOR. ONE SHOWN AT #4,
 OTHER SHOWN AT #6.?
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISCONNECT
 TO PANEL. 250-24/250-122
  
 3)NOTE: PLEASE SEE MISSING FRONT AND
 REAR RECEPTS. 210-52E
  
 4)NOTE: PLEASE SEE MISSING BATH RECEPT
 FOR BATH / POWDER RM. 210-52D
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-05 Cont ID  
Sent By alange Date 2003-08-18 Time 11:51 Rev Time 0.75
Received By dpalmer Date 2003-05-05 Time 07:22 Sent To B
Notes
2003-05-05 00:00:00************PROVISO/REVISE ************
  
 PLANS STILL MISSING THE FOLLOWING AND
 NEED TO BE REVISED BEFORE FINAL.
  
 1)NOTE: PLEASE SHOW SD`S INSIDE AND
 OUTSIDE BEDROOM. NFPA-72 8-1.4.2
  
 2)NOTE: PLEASE SHOW EQUIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN DISC AND PANEL.
 250-24/250-122
  
 3)NOTE: PLEASE SHOW ALL KITCHEN COUNTER-
 -SPACE RECEPTS AS GFI/GFI PROTECTED.
 210-8-A-6
  
 4)NOTE: PLEASE SEE MISSING REAR RECEPT
 PER 210-52E.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-28 Time 14:21 Rev Time 0.50
Received By dpalmer Date 2003-04-03 Time 04:50 Sent To P
Notes
2003-04-03 00:00:00**************** UNSAT **************
  
 1)NOTE : PLEASE SUBMIT AIC RATING FOR
 ALL NEW EQUIPMENT BEING INSTALLED. PER
 110-9/215-5
 MAINS/PANELS/BRKRS ARE ALL TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT.
  
 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 PER 250-66.
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND PANEL.
  
 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12 ON PANEL
 SCHEDULE.
  
 5)NOTE: PLEASE CLARIFY ONLY ONE SMALL
 APPLIANCE CIRCUIT SHOWN ON PANEL SCHED?
 PLEASE NOTE, A MIN OF TWO IS REQ`D PER
 NEC 210-11C-1
  
 6)NOTE: PLEASE SEE FS/FAC 481/ 61G14
 PLEASENOTE, ALL CHANGES TO PLANS THAT
 ARE SIGNED AND SEALED BY AND ARCH, MUST
 HAVE "EACH" HANDWRITTEN CHANGE,
 INITIALED, DATED BY ARCH OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 14:27 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 14:27 Sent To E
Notes
2004-04-16 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-01-28 Time 14:26 Rev Time 0.00
Received By csiegber Date 2004-01-28 Time 14:26 Sent To B
Notes
2004-01-28 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2004-01-08 Cont ID  
Sent By csiegber Date 2004-01-08 Time 16:50 Rev Time 0.00
Received By csiegber Date 2004-01-08 Time 16:50 Sent To B
Notes
2004-01-08 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 10:35 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 10:35 Sent To B
Notes
2003-12-16 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-24 Time 14:44 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 14:44 Sent To E
Notes
2003-09-24 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-08-18 Cont ID  
Sent By alange Date 2003-08-18 Time 11:47 Rev Time 0.00
Received By alange Date 2003-08-18 Time 11:46 Sent To E
Notes
2003-08-18 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-08-18 Cont ID  
Sent By mmclean Date 2003-08-18 Time 11:02 Rev Time 0.00
Received By sthyng Date 2003-08-18 Time 09:59 Sent To Z
Notes
2003-08-18 00:00:00ADDITION - NEEDS ZONING

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-08-12 Cont ID  
Sent By mmclean Date 2003-08-18 Time 09:40 Rev Time 0.00
Received By dbaxter Date 2003-08-12 Time 11:34 Sent To Z
Notes
2003-08-12 00:00:00TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 14:00 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 14:00 Sent To B
Notes
2003-05-14 00:00:00STHYNG DESK. SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 14:20 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 14:20 Sent To E
Notes
2003-04-28 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 11:51 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 11:51 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 08:12 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 08:12 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-19 Cont ID  
Sent By sthyng Date 2003-03-19 Time 10:48 Rev Time 0.00
Received By sthyng Date 2003-03-19 Time 10:48 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-28 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 17:08 Rev Time 0.00
Received By btrobaug Date 2003-02-28 Time 17:07 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-10-01 Cont ID  
Sent By pkrauss Date 2003-10-01 Time 06:44 Rev Time 0.25
Received By pkrauss Date 2003-10-01 Time 06:44 Sent To B
Notes
2003-10-01 00:00:00PROVISO:
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-12 Cont ID  
Sent By kstevens Date 2003-09-30 Time 12:35 Rev Time 0.20
Received By pkrauss Date 2003-09-12 Time 08:38 Sent To B
Notes
2003-09-12 00:00:00PROVISO:
  
 BALANCED AIR REQUIRED AS PER 2001 FBC(M)
 601.4, PLEASE PROVIDE RETURN AIR FROM
 BEDROOM AREAS.PLAN DOES NOT INDICATE
 DUCT OR GRILLE SIZE FOR RETURN AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-04 Cont ID  
Sent By kstevens Date 2003-09-03 Time 16:10 Rev Time 0.35
Received By pkrauss Date 2003-04-04 Time 10:09 Sent To B
Notes
2003-04-04 00:00:00MECHANICAL PERMIT 03040041

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-09-30 Cont ID  
Sent By kstevens Date 2003-09-30 Time 12:35 Rev Time 0.50
Received By kstevens Date 2003-09-30 Time 12:35 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-09-03 Cont ID  
Sent By dpalmer Date 2003-09-26 Time 09:41 Rev Time 0.50
Received By kstevens Date 2003-09-03 Time 16:07 Sent To M
Notes
2003-09-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM SHALL REFLECT
 THE CHANGES ON THE FLOOR PLAN. BATHROOM
 NEXT TO LAUNDRY ROOM SHOWS SHOWER DELET-
 ED, W/C & LAV MOVED TO ANOTHER WALL.
 IF BATHROOM #1 HAS BEEN CHANGED THEN THE
 RISER DIAGRAM SHALL REFLECT CHANGES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-03 Cont ID  
Sent By dpalmer Date 2003-08-25 Time 13:03 Rev Time 0.25
Received By kstevens Date 2003-04-03 Time 17:49 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2003-08-18 Cont ID  
Sent By sthyng Date 2003-08-18 Time 09:59 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-08-18 00:00:008/18/03 DO NOT NEED ANY ZONING REVIEW
 PER TONI GELO CONTRACTOR/CONTACT PERSON
 MM
 8/18/03 REVIEWED NEED ZONING PASS MM

Review Stop Z ZONING
Rev No 2 Status P Date 2003-03-21 Cont ID  
Sent By dbaxter Date 2003-08-12 Time 11:34 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-03-04 Cont ID  
Sent By sthyng Date 2003-03-19 Time 10:48 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-03-04 00:00:00DENIED, NEED A COMPLETE FLOOR PLAN
 OF EXISTING HOUSE