Plan Review Details - Permit 03022281
Plan Review Stops For Permit 03022281
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-30 Cont ID  
Sent By rbrown Date 2003-04-30 Time 11:25 Rev Time 0.00
Received By rbrown Date 2003-04-30 Time 11:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-07 Cont ID  
Sent By dpalmer Date 2003-04-24 Time 15:10 Rev Time 0.00
Received By rbrown Date 2003-04-07 Time 14:32 Sent To  
Notes
2003-04-07 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 MODEL B
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) SHEET S-1, ROOF FRAMING PLAN.NO
 TRUSS ANCHORS ARE SPECIFIED ALONG THE
 FAMILY ROOM WALL.
  
 2) SHEET S-1, ROOF FRAMING PLAN.ADD A
 KEY, FOR THE TRUSS ANCHOR REFERENCE
 ANNOTATION, TO CONFIRM IF1MEANS
 CONNECTOR MARK 1, AND IF 'U' IS THE
 DESIGN UPLIFT CAPACITY REQUIRED.WHAT
 IS THE VALUE STATED AS 'R', IS IT THE
 REQUIRED LATERAL LOAD CAPACITY (EITHER
 F1 OR F2)?
  
 3) SHEET S-2, CONNECTOR SCHEDULE.AMEND
 THE SCHEDULE TO INCLUDE THE UPLIFT AND
 THE LATERAL LOAD CAPACITY FOR THE
 SELECTED ANCHORS AND LUMBER GRADE.
  
 4) FBC TABLE 600THE GLASS BLOCK WINDOW
 IS ON THE PROPERTY LINE.AMEND THE
 PLANS TO SHOW THE REQUIREMENT FOR A ONE-
 HOUR FIRE-RATED ASSEMBLY.
  
 5) SHEET S3, PLYWOOD NAILING DETAIL.
 AMEND '10/32 CDX PLYWOOD' TO READ
 '19/32 CDX PLYWOOD'.
  
 6) PROVISO - ROOF TILE PRODUCT APPROVAL
 NOA# 99-1012.02 HAS EXPIRED.SUBMIT A
 CURRENT PRODUCT APPROVAL.
  
 7) PROVISO - OUTSWING STEEL DOUBLE DOOR
 PRODUCT APPROVAL NOA# 99-0311.03 HAS
 EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 8) PROVISO - ALUMINUM SLIDING GLASS
 DOOR PRODUCT APPROVAL NOA# 98-1228.01
 HAS EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 9) PROVISO - ALUMINUM TUBE MULLION
 PRODUCT APPROVAL NOA# 99-0310.01 HAS
 EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 10) PROVISO - SINGLE HUNG WINDOW PRODUCT
 APPROVAL NOA# 98-1222.02 HAS EXPIRED.
 SUBMIT A VALID PRODUCT APPROVAL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-24 Cont ID  
Sent By bstaples Date 2003-08-19 Time 08:57 Rev Time 0.25
Received By dpalmer Date 2003-04-24 Time 15:09 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-13 Cont ID  
Sent By shernand Date 2003-04-17 Time 16:33 Rev Time 0.50
Received By dpalmer Date 2003-03-13 Time 07:07 Sent To P
Notes
2003-03-13 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SIZE SEC PER 310-15
  
 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 PER 250-66, ONCE SEC`S ARE SIZE.
  
 3)NOTE: PLEASE CORRELATE SERVICE AMP/
 LOAD. 144A`S, SEE A`S ON A&B.
  
 4)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUIT(S) PER 210-52D/210-11-C-3
  
 5)NOTE: PLEASE SEE NOTE AT THE BOTTOM
 OF LOAD CALCS. MENTIONS SERVICE TO BE
 SIZED @75% PER 220-17. PLEASE SEE 220-17
 THIS IS FOR APPL LOADS ONLY.
  
 7)NOTE: PLEASE CORRELATE SCALE SHOWN
 FOR PLANS SUBMITTED. 1/4"= 1'
  
 8)NOTE: PLEASE SEE RECEPT SPACING,
 MISSING PER 210-52
  
 9)NOTE: PLEASE NOTE:FEEDER TO PANEL "A"
 IS SHOWN AT 2/0`S, THIS IS PERMITTED,
 HOWEVER IF SHOWN ON PLANS, THEN 2/0`S
 WILL BE REQ`D TO BE INSTALLED. PLEASE
 VERIFY THIS W/ CONTRACTOR/BLDER.
  
 10)NOTE: PLEASE CORRELATE LOADS SHOWN
 ON PANEL "B" AND LOAD CALCULATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-19 Cont ID  
Sent By bstaples Date 2003-08-19 Time 08:57 Rev Time 0.00
Received By bstaples Date 2003-08-19 Time 08:57 Sent To E
Notes
2003-08-19 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 16:33 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 16:33 Sent To E
Notes
2003-04-17 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-28 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 17:03 Rev Time 0.00
Received By btrobaug Date 2003-02-28 Time 17:02 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-17 Cont ID  
Sent By jleech Date 2003-03-15 Time 12:33 Rev Time 0.33
Received By rregueir Date 2003-03-17 Time 19:06 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-15 Cont ID  
Sent By dpalmer Date 2003-03-13 Time 07:07 Rev Time 0.33
Received By jleech Date 2003-03-15 Time 12:33 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-04 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 17:03 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***