Plan Review Details - Permit 03022151
Plan Review Stops For Permit 03022151
Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-06 Cont ID  
Sent By kstevens Date 2003-03-06 Time 17:32 Rev Time 1.00
Received By kstevens Date 2003-03-06 Time 17:32 Sent To  
Notes
2003-03-06 00:00:00DRYER ROOM IS A CONFINED SPACE - TWO
 OPENINGS REQUIRED PER SECTION 304.3.1
 OR ONE OPENING PER SECTION 304.3.2(2).
 REQUIRED.
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.