Plan Review Stops For Permit 03022051 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-03-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-03-05 |
Time |
13:17 |
Rev Time |
0.75 |
Received By |
btrobaug |
Date |
2003-03-05 |
Time |
13:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-03-04 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-03-04 |
Time |
09:01 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-03-04 |
Time |
09:00 |
Sent To |
|
|
Notes |
2003-03-04 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | 1} PLEASE NOTE THAT ALL PLANS | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | ING A TITLE BLOCK, MUST BE SIGNED, | | DATEDAND SEALED BY THE ARCH/ENGINEER OF | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | 2} PLEASE NOTE THAT TWO SETS OF PLANS | | ARE REQUIRED FOR REVIEW. | | | | 3} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | | | 4} PLEASE LIST THE REQ`D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | CIRCUIT PROTECTION. PER 210-12 | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 5} NFPA-72 8-1.4.2 PROHIBITS SMOKE | | DETECTORS IN THE KITCHEN. A HEAT | | DETECTOR IS ACCEPTABLE AND MEETS THE | | INTENT OF 8-1.4.1.6(2). | | | | 6} PLEASE INDICATE IF THE GARAGE IS TO | | REMAIN OR BE TURNED INTO LIVING SPACE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|
|
|