2003-03-26 00:00:00 | **********CORRECTIONS************ |
| |
| PLEASE NOTE FBC 3401.7.1 AND 3401.7.2 |
| |
| 1.)IMPACT FEES WERE FOR 386 SQUARE |
| FEET, CABANA ONLY.IMPACT FEES MUST |
| BE PAID ON THE NEW HOUSE ADDITION. |
| THE ACTUAL PERMIT PLANS MUST BE STAMPED |
| BY THAT OFFICE, AND A COPY OF THE PAID |
| RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION.PLEASE CALL 561-233-5025 |
| FOR MORE INFORMATION. |
| |
| 2.)AREA TABULATION IS NOT CORRECT. |
| PLEASE REVISE.AREA OF THE BAY WINDOW |
| SHOULD ALSO BE INCLUDED.IF THE PATIO |
| WAS PREVIOUSLY INDOOR AIR CONDITIONED |
| SPACE, THIS REDUCTION SHOULD ALSO BE |
| REFLECTED IN THE AREA TABULATIONS. |
| IMPACT FEES WILL BE PAID ON ADDITIONAL |
| LIVING AREA INCREASE. |
| |
| 3.)SEPARATE ENERGY CALCS REQUIRED FOR |
| THE CABANA. |
| |
| 4.)PER FBC 104.2.1.1, PROVIDE ROOF |
| FLASHING REQUIREMENTS & WIND RESISTANCE |
| RATINGS THAT ARE REQUIRED TO BE |
| INSTALLED. |
| |
| 5.)A 2X4 SKYLIGHT IS SHOWN HIGHLIGHTED |
| ON SHEET A1.IF THIS IS A PROPOSED |
| SKYLIGHT, SUBMIT PRODUCT APPROVALS.IF |
| THIS IS EXISTING, INDICATE ON THE PLAN. |
| |
| 6.)PROVIDE PRODUCT APPROVALS FOR |
| THE MULLS FOR WINDOW 8 AND FOR THE |
| 45 DEGREE BAY MULLS. |
| |
| 7.)PROVIDE PRODUCT APPROVALS FOR |
| THE EXTERIOR DOORS. |
| |
| 8.)PROVIDE PRODUCT APPROVALS FOR |
| THE CASEMENT WINDOWS #12. |
| |
| 9.)PLEASE DATE THE ARCHITECTURAL |
| SEAL AS PER FLORIDA STATUTE 61G1-16.003. |
| |
| 10.) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 11.)ONE ACCESSIBLE BATHROOM REQUIRED |
| FOR ALL RESIDENCES PER FBC 11-11 (1). |
| |
| 12.)1403.1.6 IN ORDER TO PROVIDE FOR |
| INSPECTION FOR TERMITE INFESTATION, |
| CLEARANCE BETWEEN EXTERIOR WALL COVER- |
| INGS AND FINAL EARTH GRADE ON THE |
| EXTERIOR OF A BUILDING SHALL NOT BE LESS |
| THAN 6 INCHES.PLEASE REVISE WALL |
| SECTION. |
| |
| 13.)PER FBC 1814.3.3, DAMPPROOFING |
| IS REQUIRED FOR CONCRETE SLABS.PLEASE |
| REVISE THE WALL SECTION (TYPICAL |
| CONCRETE SLAB) ON SHEET A8. |
| |
| 14.)EXISTING BEDROOM WINDOWS ARE |
| REQUIRED TO BE EGRESS WINDOWS (FBC1005.4 |
| AND FBC 3401.7.1.2).PLEASE GIVE |
| BEDROOM WINDOW INFORMATION; DIMENSIONS, |
| TYPE, AND DISTANCE FROM FLOOR. |
| |
| 15.)ON WALL SECTIONS AND DETAILS, |
| TWO COURSES OF LINTEL BLOCK W/STEEL IS |
| DESCRIBED BUT ONLY ONE IS SHOWN.PLEASE |
| REVISE IN ALL SECTIONS TO MAKE THE TEXT |
| MATCH THE GRAPHIC. |
| |
| 16.)ATTIC ACCESS IS REQUIRED IN THE |
| CABANA.GIVE SIZE AND LOCATION. |
| |
| 17.)ATTIC ACCESS IS REQUIRED IN THE |
| ADDITION.GIVE SIZE AND LOCATION. |
| |
| 18.)ATTIC ACCESS REQUIRES INSULATION. |
| ALSO, THE DETAIL TEXT REFERS TO A LADDER |
| BUT IS NOT SHOWN.PLEASE REVISE THE |
| DETAIL. |
| |
| 19.)IF THE FIREPLACE IS NOT FACTORY- |
| BUILT, PLEASE PROVIDE A DETAIL.IF IT |
| IS FACTORY BUILT, PLEASE COMPLY WITH |
| NOTES 20 THROUGH 24. |
| |
| 20.) 2804.4.1 FACTORY-BUILT CHIMNEYS |
| FACTORY BUILT CHIMNEYS SHALL BE LISTED |
| AND SHALL BE INSTALLED IN ACCORDANCE |
| WITH THE CONDITIONS OF THE LISTING, AND |
| MANUFACTURER'S INSTRUCTION. |
| |
| 21.) 2804.4.4. FACTORY-BUILT CHIMNEYS |
| FOR USE WITH CLOSED COMBUSTION WOOD |
| BURNING APPLIANCES SHALL COMPLY WITH |
| THE TYPE HT REQUIREMENT UL 103. |
| |
| 22.) CHIMNEYS FOR THE USE WITH FACTORY- |
| BUILT FIREPLACES SHALL MEET THE |
| REQUIREMENTS OF UL 127. |
| |
| 23.) 2806.1.2 FACTORY BUILT FIREPLACES |
| SHALL BE TESTED IN ACCORDANCE WITH AND |
| MEET THE REQUIREMENTS OF UL 127. |
| |
| 24.) 2810 FRESH AIR INTAKES, FRESH AIR |
| INTAKESSHALL BE SCREENED WITH A CORRO- |
| SION RESITANT MATERIAL NOT LARGER THAN |
| 1/2 INCH MESH. FRESH AIR INTAKES SHALL |
| NOT BE TAKEN FROM A LOCATION CLOSER THAN |
| 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR |
| SANITARY SEWER VENT OUTLET, UNLESS SUCH |
| VENT IS NOT LESS THAN 24" ABOVE THE |
| FRESH AIR VENT. FRESH AIR INTAKE VENTS |
| LOCATED ON THE ROOFS WILL BE PROPERLY |
| MARKED WITH A UNIVERSAL MARKING, |
| ***"INTAKE"***, PERMANETLY ATTACHED. |
| SEE 705.1.1.4 FOR FIRE PROTECTION. |
| |
| 25.)PLEASE PROVIDE ADDITIONAL |
| INFORMATION IN REGARDS TO THE METHOD |
| OF SHORING. |
| |
| 26.)PLEASE PROVIDE INFORMATION IN |
| REGARDS TO THE SIDING MATERIAL. |
| |
| 27.) PROVIDE STORM PANEL INFORMATION W/ |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| FBC 1606.1.4. |
| |
| 28.)FIRESTOP REQUIRED.PLEASE REVISE |
| WALL SECTION DETAILS. |
| |
| 29.)PROVIDE A DETAIL FOR THE BAY |
| WINDOW. |
| |
| 30.)PROVIDE STRUCTURAL INFORMATION |
| ON THE EXISTING PATIO WALLS.ARE THERE |
| EXISTING COLUMNS?PROVIDE STRUCTURAL |
| CALCULATIONS AND A DETAIL FOR THE |
| PROPOSED PORCH TIE BEAM, INCLUDING |
| THE CANTALEVERED SECTION OVER THE BAY |
| WINDOW. |
| |
| 31.)FOR FOUNDATION DETAIL 1/A3, GIVE |
| ALL DIMENSIONS. |
| |
| 32.)FOR DETAIL 2/A3, GIVE CONNECTION |
| INFORMATION AT THE TOP OF THE POST. |
| |
| 33.)PROVIDE ADDITIONAL INFORMATION IN |
| REGARDS TO UPLIFT AND CALCULATED LOADS. |
| |
| 34.)PROVIDE LOADING INFORMATION FOR |
| THE TRUSSES. |
| |
| 35.)THE POOL IS TO COMPLY WITH FBC |
| 424.2.17.1.INDICATE COMPLIANCE ON |
| THE PLAN, EITHER AS EXISTING OR |
| PROPOSED. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| SAMANTHA THYNG |
| 561-659-8096, EXTENSION 8340, OR |
| 561-805-6724 |