Plan Review Details - Permit 03021543
Plan Review Stops For Permit 03021543
Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2004-05-03 Cont ID  
Sent By jwitmer Date 2004-05-03 Time 12:21 Rev Time 0.99
Received By jwitmer Date 2004-05-03 Time 12:21 Sent To  
Notes
2004-05-03 00:00:00SWING DOORS SUBMITTED AS REVISION OR
 SUBMITTAL, BUILDING PROVISO, PRODUCT APP
 ROVAL TO BE A SEPEATE PERMIT.
 THIS SWING DOOR COULD COME IN UNDER THE
 GARAGE DOOR PERMIT UP THE VALUE AND
 COMPLETE THE FAILED ITEMS UNDER THE
 GARAGE DOOR PERMIT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-04-26 Time 13:10 Rev Time 0.55
Received By jwitmer Date 2004-04-06 Time 15:36 Sent To  
Notes
2004-04-06 00:00:00REVISION DATED 3-30-04 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2004-03-22 Cont ID  
Sent By jwitmer Date 2004-03-22 Time 09:43 Rev Time 1.00
Received By jwitmer Date 2004-03-22 Time 09:43 Sent To  
Notes
2004-03-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03021543
 ADD: 525 CLEMATIS ST
 CONT: D. B. MARCUS CONST
 TEL: (561)346-5667
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SUBMITTAL: DENIED
  
 1) SEE BUILDING PROVISO ATTACHED:
 2) WHEN PRODUCT APPROVALS ARE REQUIRED
 UNDER SEPERATE PERMIT AND TURNED IN
 AFTER OCT.1, 2003 THE STATE WIDE PRODUCT
 APPROVAL IS IN EFFECT.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-10 Time 14:04 Rev Time 0.25
Received By jwitmer Date 2004-03-04 Time 09:11 Sent To  
Notes
2004-03-04 00:00:00BAR JOIST DETAILSOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-03-03 Cont ID  
Sent By jwitmer Date 2004-03-03 Time 16:00 Rev Time 0.50
Received By jwitmer Date 2004-03-03 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-12-29 Cont ID  
Sent By csiegber Date 2004-03-01 Time 15:28 Rev Time 0.55
Received By jwitmer Date 2003-12-29 Time 08:44 Sent To  
Notes
2003-12-29 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 03021543
 ADDRESS: 525 CLEMATIS ST
 CONT: D. B. MARCUS CONSTRUCTION
 TELL # (561) 346-5667
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 BUILDING PROVISO:
 NO PRODUCT TESTING REPORTS (WINDOWS,
 DOORS OR ROOFING ASSEMBLIES)WERE SUBMIT-
 TED AT TIME OF APPLICATION. AS PER CITY
 MISSILE IMPACT STANDARD, WHEN INSTALLED
 AS A PART OF NEW CONSTRUCTION AND ALL
 REQUIRED INFORMATION IS PROVIDED AT TIME
 OF THE PLAN SUBMITTAL, THE PRIMARY PER-
 MIT FOR THE STRUCTURE WILL BE CONSIDERED
 TO INCLUDE THIS WORK. OTHERWISE, A SEP-
 ERATE PERMIT AND FEES IS REQUIRED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-12-23 Time 08:22 Rev Time 0.75
Received By jwitmer Date 2003-12-11 Time 12:01 Sent To  
Notes
2003-12-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03021543
 ADD: 525 CLEMATIS
 CONT: D. B. MARCUS
 TEL: (561)346-5667
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-10-15 Cont ID  
Sent By hpiskura Date 2003-10-15 Time 11:50 Rev Time 0.00
Received By hpiskura Date 2003-10-15 Time 11:50 Sent To  
Notes
2003-10-15 00:00:00OWES IMPACT FEES, PLAN REVIEW OK PLANS
 DATED 6/3/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-10 Cont ID  
Sent By hpiskura Date 2003-06-10 Time 12:05 Rev Time 0.00
Received By hpiskura Date 2003-06-10 Time 08:28 Sent To  
Notes
2003-06-10 00:00:00PLANS DATED 6/3/03
 PLEASE PROVIDE A RECENT PROPERTY SURVEY
 AS PREVIOUSLY REQUESTED.
  
 SHOW A CONNECTION DETAIL FOR THE BAR
 JOISTS TO THE BUILDING.
  
 SHOW THE METAL DECKING AND THE FASTENING
 METHOD TO THE BAR JOISTS.
  
 IF THE ENGINEERING DESIGN IS DELEGATED
 TO A SPECIALTY ENGINEER NOTE THE
 LOCATION, DIRECTION, NATURE AND
 MAGNITUDE OF THE LOADS TO BE RESISTED.
  
 WHAT ISTHE NATURE AND QUANTITY OF THE
 COMMODITIES TO BE STORED IN THE
 WAREHOUSE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-10 Cont ID  
Sent By hpiskura Date 2003-03-10 Time 07:54 Rev Time 0.00
Received By hpiskura Date 2003-03-07 Time 15:44 Sent To Z
Notes
2003-03-10 00:00:00PLEASE PROVIDE A RECENT SIGNED AND
 SEALED PROPERTY SURVEY.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY THE PERMIT PLANS STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICTION.
 CALL 561-233-5025 FOR MORE INFORMATION.
  
 THIS NEW CONSTRUCTION WILL CREATE TWO
 ZERO LOT LINE BUILDINGS ON THE SAME
 PROPERTY.SHOW THE EXISTING BUILDING
 WALL THAT IS ADJACENT TO THE PROPOSED
 BUILDING AS HAVING A THREE HOUR FIRE
 RATING, (TYPEV CONSTRUCTION) AND NO
 OPENINGS FOR ITS FULL HEIGHT OR
 MODIFICATIONS TO EFFECT THOSE
 CONDITIONS.SEE FBC TABLE 600.
  
 SHEET SP1.SHOW THE CONSTRUCTION
 DETAILS FOR THE NEW HC RAMP, THE SIGN
 FOR THE HC PARKING SPACE, AND THE
 APPROPRIATE STRIPING FOR THE HC PARKING
 SPACE.SEE FBC 11-4.
  
 SHEET A3, THE "TIE COLUMN BRACE DETAIL"
 WHERE IS THAT USED?
  
 THIS BUILDING WILL BE LOCATED IN THE
 DESIGNATED FIRE DISTRICT AND WILL
 REQUIRE TWO HOUR FIRE RATED EXTERIOR
 WALLS ON THENORTH, SOUTH AND EAST
 ELEVATIONS.SEE FBC F102.2.6 AS
 AMENDED BY THE CITY.
  
 SHOW A CONSTRUCTION DETAIL AND DESIGN
 LOAD FOR THE PALLET RACKS SHOWN ON
 SHEET A1.SEE FBC 104.2
  
 WHAT IS THE NATURE AND QUANTITY OF THE
 COMMODITIES TO BE STORED IN THIS
 BUILDING?SEE FBC 104.2
  
 SHEET A4 ROOF FRAMING.SHOW THE JOIST
 DESIGNATIONS FROM THE 1997 SJI SPECS.
 SHOW THE END SUPPORT CONNECTION,
 AND UPLIFT
 REQUIREMENTS. SEE FBC 104.2.
  
 DEMONSTRATE COMPLIANCE WITH FBC 1803.2
 FOR THE FOUNDATION WHERE APPLICABLE.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-04-03 Cont ID  
Sent By btrobaug Date 2004-04-03 Time 12:29 Rev Time 0.50
Received By btrobaug Date 2004-04-03 Time 12:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-03-18 Cont ID  
Sent By alange Date 2004-03-31 Time 15:23 Rev Time 0.50
Received By btrobaug Date 2004-03-18 Time 17:20 Sent To  
Notes
2004-03-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE #2 FEEDERS TO THE 200 AMP PANELS
 ARE UNDERSIZED, SEE 310.16 NEC.
  
 2} THE 2/0 FEEDERS TO THE DISCONNECTS
 FROM THE METERS ARE INCORRECT PER
 310.16.
  
 3} THE 200 AMP SERVICE IS A REVISION
 FROM THE PREVIOUSLY SUBMITTED PLAN,
 PL;EASE INDICATE IT AS A REVISION.
  
 4} A 2ND PANEL AND DISCONNECT HAVE BEEN
 ADDED,PLEASE INDICATE THEIR LOCATIONS ON
 THE PLAN.
  
 5} PLEASE GIVE A PANEL SCHEDULE FOR THE
 2ND PANEL.
  
 6} PLEASE NOTE THAT THE CIRCUIT NUMBERS
 ON THE PANEL SCHEDULE ARE NOT THE SAME
 AS LISTED AT THE DEVICES, PLEASE
 CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-03-10 Time 14:05 Rev Time 0.33
Received By dpalmer Date 2004-02-09 Time 14:53 Sent To  
Notes
2004-02-09 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS HAVE NOT BEEN
 CORRECTED FROM PREVIOUS REDLINES.
 EM/ EXT LIGHTING TO BE WIRED AHEAD OF
 LOCAL "LIGHTING BRANCH CIRCUITS".
 NOT AHEAD OF MAIN.
  
 2)NOTE: PLEASE SEE PLANS,PLANS NOTE IN
 THE REV COL A REV #2, HOWEVER PLANS DO
 NOT INDICATE ANY REV'S (2). ??
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-12-09 Cont ID  
Sent By dpalmer Date 2003-12-09 Time 09:13 Rev Time 0.50
Received By dpalmer Date 2003-12-09 Time 09:13 Sent To  
Notes
2003-12-09 00:00:00REDLINED CIRCUITING PER 700.12E FOR
 EM/EXT LTS.
 AHEAD OF LOCAL BRANCH CIRCUIT SW.
 NOT AHEAD OF MAIN.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-09-22 Cont ID  
Sent By dpalmer Date 2003-09-22 Time 19:51 Rev Time 0.50
Received By dpalmer Date 2003-09-22 Time 19:51 Sent To  
Notes
2003-09-22 00:00:00******* NOTE REDLINED ****
  
  
 PLANS STILL SHOW EMERGENCY AND EXIT LTS
 ON THEIR OWN CIRCUITS,, PLEASE SEE
 700.12E. CIRCUIT WITH LIGHTING BRANCH
 CIRCUIT.
  
 NEW PLANS WILL NEED TO HAVE HISTORIC
 STAMP NEW SHEETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-06-11 Cont ID  
Sent By dpalmer Date 2003-06-11 Time 11:18 Rev Time 0.50
Received By dpalmer Date 2003-06-11 Time 11:18 Sent To  
Notes
2003-06-11 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE NOTE FROM FIRST
 REVIEW. PLEASE SHOW ALL CIRCUITING
 INCLUDING EM/EXT LTS. PLEASE SEE 700-12E
 FOR CIRCUITING OF EM/EXT LTS.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 AS ON PREVIOUS NOTES. 220-3,220-10,220-1
 1, ETC. PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%. 215-3/230-42
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISC TO
 PANEL AND SIZE PER 250-122
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL..
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-05 Cont ID  
Sent By dpalmer Date 2003-03-05 Time 06:44 Rev Time 0.50
Received By dpalmer Date 2003-03-05 Time 06:43 Sent To  
Notes
2003-03-05 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE. PANEL SCHEDULE IS SHOWING
 10 CIRCUITS FOR LIGHTING AND ONLY 10
 FIXTURES? THE SAME FOR RECEPTS.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATION PER
 220-3, 220-11, 220-13.
 PLEASE SHOW ANY CONTINUOUS LOADS AT 125%
 SHOWN AS RESIDENTIAL LOAD CALC.
 3)NOTE: PLEASE SHOW CONDUCTOR BETWEEN'MA
 IN DISC AND PANEL.
  
 4)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW SERVICE EQUIPMENT BEING INSTALLED.
 110-9/215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATIONFOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-02-28 Cont ID  
Sent By mamini Date 2003-02-28 Time 16:48 Rev Time 1.00
Received By mamini Date 2003-02-28 Time 16:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2004-02-10 Cont ID  
Sent By nmccray Date 2004-02-10 Time 15:06 Rev Time 0.00
Received By nmccray Date 2004-02-10 Time 15:06 Sent To  
Notes
2004-02-10 00:00:00REVISION DATED 01-29-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-12-12 Cont ID  
Sent By mcarsill Date 2003-12-12 Time 07:44 Rev Time 0.00
Received By mcarsill Date 2003-12-12 Time 07:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-09-30 Cont ID  
Sent By nmccray Date 2003-09-30 Time 14:51 Rev Time 0.00
Received By nmccray Date 2003-09-30 Time 14:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-06-13 Cont ID  
Sent By mcarsill Date 2003-06-13 Time 07:55 Rev Time 0.00
Received By mcarsill Date 2003-06-13 Time 07:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-03-06 Cont ID  
Sent By mcarsill Date 2003-03-06 Time 09:38 Rev Time 0.00
Received By mcarsill Date 2003-03-06 Time 09:38 Sent To  
Notes
2003-03-06 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR NEW GATES.
  
 2) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION.
  
 3) NO ILLUMINATED EXIT SIGNS OR
 EMERGENCY LIGHTING SHOWN ON ELECTRIC
 PLAN.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 5) PLEASE INDICATE WHAT TYPE OF STORAGE
 WILL OCCUR IN THE BUILDING.WILL THERE
 BE LOW,ORDINARY,OR HIGH HAZARD STORAGE.
  
 6) BUILDING APPEARS TO BE LOCATED IN THE
 CITY FIRE LIMITS. CERTAIN RESTRICTIONS
 APPLY. PLEASE SEE APPENDIX F, THE LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2004-04-26 Cont ID  
Sent By csiegber Date 2004-04-26 Time 13:10 Rev Time 0.00
Received By csiegber Date 2004-04-26 Time 13:10 Sent To B
Notes
2004-04-26 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 08:14 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 08:14 Sent To B
Notes
2004-04-16 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 09:35 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 09:34 Sent To Z
Notes
2004-04-14 00:00:00TO MM/PER JW - REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-12 Time 08:26 Rev Time 0.00
Received By csiegber Date 2004-04-12 Time 08:26 Sent To B
Notes
2004-04-12 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2004-03-31 Cont ID  
Sent By alange Date 2004-03-31 Time 15:23 Rev Time 0.00
Received By alange Date 2004-03-31 Time 15:23 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2004-03-30 Cont ID  
Sent By alange Date 2004-03-30 Time 13:28 Rev Time 0.00
Received By alange Date 2004-03-30 Time 13:28 Sent To  
Notes
2004-03-30 00:00:00TO COMM BD. #39

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2004-03-10 Cont ID  
Sent By csiegber Date 2004-03-10 Time 14:05 Rev Time 0.00
Received By csiegber Date 2004-03-10 Time 14:05 Sent To E
Notes
2004-03-10 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-10 Time 14:04 Rev Time 0.00
Received By csiegber Date 2004-03-08 Time 16:21 Sent To B
Notes
2004-03-08 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-01 Time 15:28 Rev Time 0.00
Received By csiegber Date 2004-03-01 Time 15:28 Sent To B
Notes
2004-03-01 00:00:00TO JW DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 11:52 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 11:52 Sent To  
Notes
2004-02-06 00:00:00TO COMM BD#3

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-12-23 Cont ID  
Sent By csiegber Date 2003-12-23 Time 08:22 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 08:22 Sent To B
Notes
2003-12-23 00:00:00TO JW DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-12-03 Cont ID  
Sent By csiegber Date 2003-12-03 Time 09:30 Rev Time 0.00
Received By csiegber Date 2003-12-03 Time 09:30 Sent To  
Notes
2003-12-03 00:00:00TO COMM BD#64

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-11-07 Cont ID  
Sent By mmclean Date 2003-12-02 Time 14:59 Rev Time 0.00
Received By csiegber Date 2003-11-07 Time 14:31 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-09-23 Time 08:06 Rev Time 0.00
Received By csiegber Date 2003-09-23 Time 08:06 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-17 Time 14:43 Rev Time 0.00
Received By csiegber Date 2003-09-17 Time 14:43 Sent To  
Notes
2003-09-17 00:00:00ON COMM BD#28

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 16:49 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 16:49 Sent To Z
Notes
2003-06-26 00:00:00REMOVED FROM BOARD, SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-09 Cont ID  
Sent By shernand Date 2003-06-09 Time 14:38 Rev Time 0.00
Received By shernand Date 2003-06-09 Time 14:38 Sent To  
Notes
2003-06-09 00:00:00COMM BOARD #5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 14:20 Rev Time 0.00
Received By dpalmer Date 2003-02-27 Time 14:19 Sent To  
Notes
2003-02-27 00:00:00TO COMM BOARD #47
 STILL NEEDS ZONING.

Review Stop P PLUMBING
Rev No 4 Status N Date 2004-02-09 Cont ID  
Sent By kstevens Date 2004-02-09 Time 16:54 Rev Time 0.33
Received By kstevens Date 2004-02-09 Time 16:54 Sent To  
Notes
2004-02-09 00:00:00NO PLUMBING REVISION SUBMITTED THIS
 REVISION

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-12-09 Cont ID  
Sent By kstevens Date 2003-12-09 Time 13:22 Rev Time 0.50
Received By kstevens Date 2003-12-09 Time 13:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-15 Cont ID  
Sent By kstevens Date 2003-10-15 Time 14:14 Rev Time 1.00
Received By kstevens Date 2003-10-15 Time 14:13 Sent To  
Notes
2003-10-15 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
  
 SECTION 61G1-16.004 SEE ATTACHED SHEET
 CONCERNING REQUIRED INFORMATION REQUIRED
 ON EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-06 Cont ID  
Sent By kstevens Date 2003-03-06 Time 10:27 Rev Time 0.33
Received By kstevens Date 2003-03-06 Time 10:27 Sent To  
Notes
2003-03-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) TABLE 403.1 REQUIRES A DRINKING
 FOUNTAIN.
 2) PLEASE SUBMIT CALCULATIONS FOR ROOF
 DRAINAGE. SHOW 1/2 AREA OF ALL VERTICAL
 WALLS. PLEASE SHOW SIZE OF GUTTER AND
 DOWNSPOUTS.
 3) PLEASE SUBMIT A SANITARY RISER DIA-
 GRAM AND A WATER RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 6 Status P Date 2004-04-15 Cont ID  
Sent By aaponte Date 2004-04-15 Time 10:57 Rev Time 0.00
Received By aaponte Date 2004-04-15 Time 10:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2003-12-02 Cont ID  
Sent By csiegber Date 2004-04-14 Time 09:35 Rev Time 0.00
Received By mmclean Date 2003-12-02 Time 14:59 Sent To I
Notes
2003-12-02 00:00:0012/2/03 OK PER ANTHEA GIANNIOTES MM

Review Stop Z ZONING
Rev No 4 Status P Date 2003-12-01 Cont ID  
Sent By agiannio Date 2003-12-01 Time 14:19 Rev Time 1.00
Received By agiannio Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2003-09-25 Cont ID  
Sent By csiegber Date 2003-11-07 Time 14:31 Rev Time 0.00
Received By dlittle Date   Time   Sent To  
Notes
2003-09-25 00:00:001.FENCE MAY NOT EXCEED 6'-0"
 2.PARKING AREA MUST COMPLY WITH LANDSC
 APE REQUIREMENTS FOR PARKING (5'-0" MIN.
 LANDSCAPE AREA)
 3.PARKING STALL STRIPING MUST MATCH TH
 AT PER CODE
 4.PARKING DIMENSIONS, IF CHANGED TO MA
 TCH CODE REQUIREMENTS, WILL PROVIDE ENOU
 GH SPACE TO ALLOW FOR LANDSCAPE AREA

Review Stop Z ZONING
Rev No 2 Status F Date 2003-06-27 Cont ID  
Sent By mmclean Date 2003-06-27 Time 15:31 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-06-27 00:00:006/27/03 DENIED, AFFIDAVIT REQUIRED TO
 RELEASE SEPERATION REQUIREMENT FROM
 ADJACENT OWNER CALL ANTHIA 659/8031 MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-03-20 Cont ID  
Sent By shernand Date 2003-06-26 Time 16:49 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-03-20 00:00:00DENIED,WINDOWS LESS THAN 10' FROM THE
 ADJACENT BLDG.